Summary
  • Lochinvar INS7162 - page 1

    The MP 2 is capable of controlling the supply water tempera- ture for up to nine ON / OFF stages based on out door tem- perature, control for the Domestic Hot W ater (DHW) gener- ation, a set point requirement or optionally an external input signal (0 - 10 V (dc)). A large easy to read display provides current system temperatures and operating stat ...

  • Lochinvar INS7162 - page 2

    This instruction manual is organized into four main sections: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4) T esting and T roubleshooting. The Sequence of Operation section has seven sub-sections. We recommend reading Section A: General Operation of the Sequence of Operation, as this contains import ant informa- tion on the ...

  • Lochinvar INS7162 - page 3

    DISPLA Y Boiler Demand DHW / Setpoint Demand WWSD External Input Signal Offset FIG . 2 SYMBOL DESCRIPTION FIG . 3 3 ...

  • Lochinvar INS7162 - page 4

    The following defined terms and symbols are used through- out this manual to bring attention to the presence of hazards of various risk levels, or to bring attention to important infor- mation concerning the life of the product, see Figure 4 below . SECTION A: GENERAL OPERA TION P OWERING U P THE C ONTROL When the control is powered up, all segment ...

  • Lochinvar INS7162 - page 5

    C OMBUSTION A IR OR A LARM C ONT ACT The control has an isolated contact that can be used as either a combustion air damper contact or an alarm cont act. This selection is made using the C. A. / Alarm DIP switch. Combustion Air (C. A.) When the DIP switch is set to C. A., terminals 12 and 13 can be used as a switch to operate a combustion air dampe ...

  • Lochinvar INS7162 - page 6

    Resetting the Rot ation Sequence T o reset the rotation sequence, set the Rotate / Of f DIP switch to the Off setting for 5 seconds and then return the DIP switch to the Rotate setting. R UNNING T IMES The control displays the accumulated running time of each boiler in the VIEW menu. When using a multi-stage boiler , the running time that is displa ...

  • Lochinvar INS7162 - page 7

    L O / H IO R L O / L O When using multi-stage boilers, a selection must be made regarding the staging order of the boiler(s). This adjustment is made in the ADJUST menu of the control. Lo / Hi If the Lo/Hi staging option is selected the control st ages in sequence all of the stages in a single boiler . Once all of the stages are turned on, the cont ...

  • Lochinvar INS7162 - page 8

    S T AGE D ELA Y The stage delay is the minimum time delay between the fir- ing of stages. After this delay has expired the control can fire the next stage if it is required. This setting can be adjust- ed manually or set to an automatic setting. When the auto- matic setting is used, the control determines the best stage delay based on the operation ...

  • Lochinvar INS7162 - page 9

    B OILER P UMP O PERA TION In certain modes of operation, the control can operate the individual boiler pumps on each boiler in addition to the pri- mary pump. The boiler pump turns on prior to the boiler fir- ing and continues to run after the boiler is turned of f. The amount of time that the boiler pump turns on prior to the boiler firing is dete ...

  • Lochinvar INS7162 - page 10

    type of terminal unit. This improves the control of the air temperature in the building. B OILER I NDOOR D ESIGN T EMPERA TURE The indoor design temperature is the room temperature that was used in the original heat loss calculations for the build- ing. This setting est ablishes the beginning of the character- ized heating curve, see Figure 15 belo ...

  • Lochinvar INS7162 - page 11

    H IGH M ASS R ADIANT (1) This type of a hydronic radiant floor is embedded in either a thick concrete or gypsumpour . This heating system has a large thermal mass and is slow acting (FIG . 17). L OW M ASS R ADIANT (2) This type of radiant heating system is either attached to the bottom of a wood sub-floor , suspended in the joist space, or sandwich ...

  • Lochinvar INS7162 - page 12

    SECTION E: DOMESTIC HOT W A TER OPERA- TION S ECTION E1: D OMESTIC H OT W A TER (DHW) DHW D EMAND A DHW Demand is required for the control to provide heat to the DHW system. A DHW aquastat or set point control is used as a switch in the DHW demand circuit. Once the con- trol detects a DHW demand, the DHW Demand pointer turns on in the LCD and the c ...

  • Lochinvar INS7162 - page 13

    DHW M ODE 4 - DHW IN P RIMARY / S ECONDAR Y WITH P RIORITY When a DHW Demand is present, the Relay 9 / DHW con- tact (terminals 30 and 31) is closed and the primary pump contact is closed. Priority can only be obt ained using exter- nal wiring. During a priority override, the Relay 9 / DHW contact is opened until the heating system has recovered be ...

  • Lochinvar INS7162 - page 14

    N UMBER OF B OILERS U SED F OR DHW G ENERA TION The number of boilers used for DHW generation can be selected from one to the maximum number of boilers using the BOIL DHW setting. This applies when only a DHW Demand is present. If there are other demands present, the control does not limit the number of boilers operated. S ECTION E2: DHW WITH L OW ...

  • Lochinvar INS7162 - page 15

    B OILER T ARGET D URING S ET P OINT The boiler target temperature during a set point demand is increased to at least the Set Point setting. This temperature is maintained as long as the control has a set point demand. S ET P OINT M ODE SETP MODE 1 - Setpoint in Parallel Whenever a set point demand is present, the boiler(s) is operated to maintain t ...

  • Lochinvar INS7162 - page 16

    I NPUT S IGNAL The control can accept either a 0 - 10 V (dc) signal or a 2 - 10 V (dc) signal. The External Input Signal setting must be set to the proper setting based on the signal that is being sent to the control. 0 - 10 V (dc) or 0 - 20 mA When the 0 - 10 V (dc) signal is selected, an input voltage of 1 V (dc) corresponds to a boiler target te ...

  • Lochinvar INS7162 - page 17

    S TEP O NE ----- G ETTING R EADY Check the contents of this p ackage. If any of the contents listed are missing or damaged, please contact your whole- saler or Lochinvar sales representative for assist ance. MP 2 includes: One Boiler Control MP 2 , One Outdoor Sensor TST231 1, T wo T emperature Sensors TST2313, Instruction Manuals INS7141 and INS71 ...

  • Lochinvar INS7162 - page 18

    Set Point Demand T o generate a setpoint demand, a voltage between 24 V (ac) and 230 V (ac) must be applied across the Setp / DHW and Com Dem terminals (8 and 7) (FIG . 26). The DHW MODE must be set to OFF . External Input (0 - 10 V dc) T o generate an external input signal, a voltage between 0 and 10 V (dc) must be applied to the Com - and Out + t ...

  • Lochinvar INS7162 - page 19

    Relay 9 / DHW If a DHW pump or DHW valve is connected to the Relay 9 / DHW contact (30 and 31) (FIG . 30), make sure the power to the pump or valve circuit is off and inst all a jumper between those terminals. When the DHW circuit is powered up, the DHW pump should turn on or the DHW valve should open completely . If the DHW pump or valve fails to ...

  • Lochinvar INS7162 - page 20

    A good quality electrical test meter , capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 ohm, is essential to properly test the wiring and sensors.  T EST T HE S ENSORS In order to test the sensors, the actual temperature at each sensor location must be measured. A good quality digital thermometer with a surface temperat ...

  • Lochinvar INS7162 - page 21

     T EST T HE O UTPUTS Primary Pump (Prim P1) If a primary pump is connected to the Prim P1 terminal (1 1), make sure that power to the terminal block is off and inst all a jumper between the Power L and Prim P1 terminals (10 and 1 1) (FIG . 37). When power is applied to the Power N and Power L terminals (9 and 10) (FIG . 37), the primary pump sho ...

  • Lochinvar INS7162 - page 22

     C ONNECTING T HE C ONTROL Make sure all power to the devices and terminal blocks is off, and remove any remaining jumpers from the terminals. Reconnect the terminal blocks to the control by carefully aligning them with their respective headers on the control, and then pushing the terminal blocks into the headers. The terminal blocks should snap ...

  • Lochinvar INS7162 - page 23

    The Alarm / C.A. DIP switch selects whether a combustion air damper or alarm device is to be connected to the C.A. / Alarm terminals (12 and 13) (FIG . 45). R O TAT E / O FF The Rotate / Of f DIP switch selects whether or not the con- trol is to provide Equal Run T ime Rotation of the boiler stages. If the switch is set to Rot ate, the stages will ...

  • Lochinvar INS7162 - page 24

    24 5 6 ...

  • Lochinvar INS7162 - page 25

    A A A 1 7 8 9 25 ...

  • Lochinvar INS7162 - page 26

    This item is only available if the External Input / Stand Alone DIP switch is set to Stand Alone. The item is only available if the External / Input Stand Alone DIP switch is set to Stand Alone. This item is only available if the External Input / Stand Alone DIP switch is set to Stand Alone. 26 ...

  • Lochinvar INS7162 - page 27

    Boiler Minimum Boiler Maximum Fire Delay 1 Fire Delay 2 Combustion Air Damper Delay Boil Mass Stage Delay Boiler Differential Staging DHW Mode DHW Exchange Occupied DHW Exchange Unoccupied 1 2 3 4 lohi 27 ...

  • Lochinvar INS7162 - page 28

    (This item is only available when DHW MODE is set to OFF .) x m weather (This item is only available if the External Input/ Stand Alone DIP switch is set to Stand Alone.) time that the primary pump will continue to operate after the boiler demand has been removed. 28 ...

  • Lochinvar INS7162 - page 29

    The control has a built-in test routine that is used to test the main control functions. The control continually monitors the sensors and displays an error message whenever a fault is found. See the following pages for a list of the control’ s error messages and possible causes. When the T est but- ton is pressed, the test light is turned on. The ...

  • Lochinvar INS7162 - page 30

    The control was unable to read a piece of information stored in its memory (FIG . 53). Because of this, the control was required to reload the factory settings into all of the items in the ADJUST menu. The control will stop operation until all of the items in the ADJUST menu of the control have been checked by the user or installer . Note: The Inst ...

  • Lochinvar INS7162 - page 31

    The control is no longer able to read the boiler return sen- sor due to an open circuit (FIG . 59). The control will contin- ue to operate normally . Locate and repair the problem as described in INS7141. T o clear the error message from the control after the sensor has been rep aired, press either the Menu or Item button. If the boiler return sens ...

  • Lochinvar INS7162 - page 32

    32 TYPICAL BOILER INST ALLA TION ...

  • Lochinvar INS7162 - page 33

    33 TYPICAL BOILER INST ALLA TION (CONTINUED) ...

  • Lochinvar INS7162 - page 34

    34 MP2 T ekmar 150 Controller TYPICAL DWH PRIORITY HEA TING P ACKAGE SYSTEM ...

  • Lochinvar INS7162 - page 35

    35 NOTES ...

  • Lochinvar INS7162 - page 36

    9/04 - Printed in U.S.A. ...

メーカー Lochinvar カテゴリー Water System

Lochinvar INS7162のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- INS7162の取扱説明書
- Lochinvarの製品カード
- パンフレット
- またはLochinvar INS7162の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Lochinvar INS7162の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Lochinvar INS7162の取り付け説明書、サービスマニュアル、簡易説明書、またはLochinvar INS7162のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Lochinvar INS7162の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Lochinvar INS7162デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがLochinvar INS7162を使用するのを助ける技術的文書のことです。説明書は通常、全てのLochinvar INS7162ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Lochinvarの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Lochinvar INS7162の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははLochinvar INS7162の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Lochinvar INS7162に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Lochinvar INS7162デバイスの基本機能を使うにあたってのヒント。 Lochinvar INS7162のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Lochinvar INS7162に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるLochinvar INS7162のメーカー/サービスへの連絡先に関する情報。