    Save these instructions for future reference 506468-01 Page 1 Risk of electrical shock. Disconnect all remote power supplies before installing or servicing any portion of the system. Failure to disconnect power supplies can result in property damage, personal injury , or death. W ARNING Installation and servicing of air conditioning equipment can b ...

  • Allied Air Enterprises 4HP16LT - page 2

    Page 2 Issue 1004 506 468- 01 INST ALLA TION on the carrier ’s freight bill. T ake special care to examine the unit inside the carton if the carton is damaged. Any concealed damage discovered should be reported to the last carrier immediately , preferably in writing, and should include a request for inspection by the carrier’s agent. If any dam ...

  • Allied Air Enterprises 4HP16LT - page 3

    506 468 -01 Issue 1004 Page 3 NOTE: Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a support frame is constructed, it must not block drain holes in unit base. • When installed in areas where low ambient tempera- tures exist, locate unit so winter prevailing winds do not blow directly into outdoor co ...

  • Allied Air Enterprises 4HP16LT - page 4

    506 468 -01 Page 4 Issue 1004 this sesction as well as the section that follows entitled Flushing Existing Line Set and Indoor Coil. If this unit is being matched with an approved line set or indoor coil which was previously charged with R-22 refrigerand, the line set and coil must be flushed prior to installation. If the unit is being used with an ...

  • Allied Air Enterprises 4HP16LT - page 5

    506 468 -01 Issue 1004 Page 5 Out side Unit Placement and Inst allation Figure 4 Polyol ester (POE) oils used with R410A refrigerant absorb moisture very quickly . It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until ready to make connections. W ARNING Inst ...

  • Allied Air Enterprises 4HP16LT - page 6

    Page 6 Issue 1 0 04 506 468 -01 Figure 6 Refrigerant Line Set s: T ransition from V ertical to Horizont al Anchored Heavy Nylon Wire Tie W all Stud Metal Slee v e V apor Line Wrapped in Armaflex – Liquid Line W all Stud A utomotiv e Muffler-T ype Hanger Strap Liquid Line to V apor Line Metal Slee v e V apor Line Wrapped in Armaflex – Liquid Lin ...

  • Allied Air Enterprises 4HP16LT - page 7

    506 468 -01 Issue 1 0 04 Page 7 Figure 7 Refrigerant Line Set s: Installing V ertical Runs (new construction shown) Outside W all W ood Block Between Studs IMPOR T ANT: Refrigerant lines must not contact wall. V apor Line Liquid Line Wire Tie Inside W all Strap Slee v e Wire Tie Wire Tie Strap W ood Block Slee v e V apor Line Wr apped with Armaflex ...

  • Allied Air Enterprises 4HP16LT - page 8

    Page 8 Issue 1 0 04 506 468 -01 If the existing outdoor unit is equipped with manual shutoff valves AND new R22 refrigerant will be used to flush the system: S tart the existing R22 refrigerant system in cooling mode and close the liquid line valve. Pump all the existing R22 refrigerant back into the outdoor unit. (It may be necessary to bypass the ...

  • Allied Air Enterprises 4HP16LT - page 9

    removed during the first flush. After each system flush, allow the recovery machine to pull a vacuum on the system at the end of the procedure. 9. Close the valve on the inverted R22 cylinder and the gauge set valves. Pump the remaining refrigeraant out of the recovery machine and turn the machine off. 10. Use nitrogen to break the vacuum on the re ...

  • Allied Air Enterprises 4HP16LT - page 10

    Page 10 Issue 1 0 04 506 468 -01 The ball valve is equipped with a service port with a factory-installed Schrader valve. A service port cap protects the Schrader valve from cont amination and serves as the primary seal. Leak T esting After the line set has been connected to the indoor and outdoor unit s, the line set connections and indoor unit mus ...

  • Allied Air Enterprises 4HP16LT - page 11

    506 468 -01 Issue 1 0 04 P age 11 to protect the manifold gauge set from damage caused by high pressure.) 2. With both manifold valves closed, connect the cylin- der of R410A refrigerant. Open the valve on the R410A cylinder (vapor only). 3. Open the high pressure side of the manifold to allow R410A into the line set and indoor unit. Weigh in a tra ...

  • Allied Air Enterprises 4HP16LT - page 12

    ST ART -UP 1. Rotate fan to check for frozen bearings or binding. 2. Inspect all factory and field-installed wiring for loose connections. 3. After evacuation is complete, open liquid line and suction line service valves to release refrigerant charge (contained in outdoor unit) into system. 4. Replace the stem caps and secure finger tight, then tig ...

  • Allied Air Enterprises 4HP16LT - page 13

    506 468 -01 Issue 1 0 04 Pag e 13 Cooling Cycle Use gauge ports on suction line valve and liquid line valve for evacuating refrigerant lines and indoor coil. Use suction gauge port to measure suction pressure during charging. Figure 12 OUTDOOR COIL DEFROST THERMOST A T EXP ANSION/CHECK V AL VE BIFLOW FIL TER / DRIER TO R410A DR UM LOW PRESSURE HIGH ...

  • Allied Air Enterprises 4HP16LT - page 14

    5. Compare the subcooling value with those shown in T able 6. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant. 506468-01 Page 14 T able 5 R410A T emperature/Pressure Chart Temp. E F Pressure Psig Temp. E F Pressure Psig Tem p. E F Pressure Psi g 32 100.8 74 214.0 116 396.0 33 102 ...

  • Allied Air Enterprises 4HP16LT - page 15

    506468-01 Page 15 Issue 1004 T able 7 due to differences in inst allations. Significant differences could mean that the system is not properly charged or that a problem exist s with some component in the system. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is ...

  • Allied Air Enterprises 4HP16LT - page 16

    5. Subtract the outdoor ambient temperature from the liquid line temperture to determine the approach temperature. 506468-01 Page 16 Check Charge Using Normal Operating Pressures Use T able 7 to perform maintenance checks. T able 7 is not a procedure for charging the system. Minor variations in these pressures may be due to differences in inst alla ...

  • Allied Air Enterprises 4HP16LT - page 17

    OPERA TION Outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is moved to the ON position, the indoor blower operates continuously . Filter Drier The unit is equipped with a large capacity bi-flow filter which keeps the system clean and dry . If replacement is necessary , replace with one of s ...

  • Allied Air Enterprises 4HP16LT - page 18

    DEFROST BOARD PRESSURE SWITCH CONNECTIONS The unit’s automatic reset pressure switches (LO PS - S87 and HI PS - S4) are factory-wired into the defrost board on the LO-PS and HI-PS terminals, respectively . (OPTIONAL) Low Pressure Switch (LO-PS) — When the low pressure switch trips, the defrost board will cycle off the compressor , and the strik ...

  • Allied Air Enterprises 4HP16LT - page 19

    Defrost T emperature T ermination Shunt (Jumper) Pins —The defrost board selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C). DELA Y MODE The defrost board has a field-selectable fun ...

  • Allied Air Enterprises 4HP16LT - page 20

    506468-01 Page 20 Issue 1004 ...

  • Allied Air Enterprises 4HP16LT - page 21

    506468-01 Page 21 Issue 1004 Defrost Control Board Diagnostic LEDs ...

  • Allied Air Enterprises 4HP16LT - page 22

    5 06 468 -01 Issue 1 0 04 P age 22 System Diagnostic Module 4HP16L T units cont ain a diagnostic module for trouble- shooting heat pump system failures. By monitoring and analyzing data from the compressor and thermostat demand, the module can accurately detect the cause of electrical and system related failure without any sensors. If a system prob ...

  • Allied Air Enterprises 4HP16LT - page 23

    Page 2 3 Issue 1 0 04 506 468 -01 Flash Codes (cont.) D E L s u t a t S n o i t p i r c s e D t l u a F n o i t a m r o f n I g n i t o o h s e l b u o r T T R E L A ) w o l l e Y ( h s a l F 3 e d o C g n i l c y C t r o h S s i r o s s e r p m o C g n i n n u r y l f e i r b y l n o t n e t t i m r e t n i s i l a n g i s d n a m e d t a t s o m ...

  • Allied Air Enterprises 4HP16LT - page 24

    5 06 468 -01 Issue 1 0 04 Page 2 4 T able 12 Miswired Module T roubleshooting Thermostat Demand Wiring The diagnostic module requires a thermostat demand signal to operate properly . The thermostat demand signal input, labeled Y on the module, should always be con- nected to the compressor contactor coil so that when the coil is energized, the dema ...

  • Allied Air Enterprises 4HP16LT - page 25

    Page 2 5 Issue 1 0 04 506 468 -01 MAINTENANCE Before performing maintenance operations on system, turn the electric power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. Electrical shock could cause personal injury or death. W ARNING Before the start of each heating and cooling season, the following service checks shoul ...

  • Allied Air Enterprises 4HP16LT - page 26

    5 06 468 -01 Issue 1 0 04 Page 2 6 HOMEOWNER INFORMA TION In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most ef ficient level. T urn all electric power to unit OFF at discon- nect switch(es) before performing any mainte- nance operations on s ...

  • Allied Air Enterprises 4HP16LT - page 27

    Page 2 7 Issue 1 0 04 506 468 -01 adjustment; turning the unit off and back on before pressures equalize puts stress on unit compressor . Fan Switch In AUT O or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority . The ON or CONT mod ...

  • Allied Air Enterprises 4HP16LT - page 28

    5 06 468 -01 Issue 1 0 04 Page 2 8 St art-Up and Performance Checklist Job Name _______________________________ Job No. ________________ Date ______________ Job Location _____________________________ City ___________________ S tate ______________ Installer _________________________________ City ___________________ S tate ______________ Unit Model N ...

  • Allied Air Enterprises 4HP16LT - page 29

    506468-01 Page 29 Issue 1004 Single St age Wire Diagram ...

  • Allied Air Enterprises 4HP16LT - page 30

    506468-01 Page 30 Issue 1004 T wo St age Wire Diagram ...

メーカー Allied Air Enterprises カテゴリー Heat Pump

Allied Air Enterprises 4HP16LTのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 4HP16LTの取扱説明書
- Allied Air Enterprisesの製品カード
- パンフレット
- またはAllied Air Enterprises 4HP16LTの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Allied Air Enterprises 4HP16LTの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Allied Air Enterprises 4HP16LTの取り付け説明書、サービスマニュアル、簡易説明書、またはAllied Air Enterprises 4HP16LTのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Allied Air Enterprises 4HP16LTの製品を使用するにあたって最も人気のある説明書を閲覧できます。

Allied Air Enterprises 4HP16LTデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAllied Air Enterprises 4HP16LTを使用するのを助ける技術的文書のことです。説明書は通常、全てのAllied Air Enterprises 4HP16LTユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Allied Air Enterprisesの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Allied Air Enterprises 4HP16LTの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAllied Air Enterprises 4HP16LTの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Allied Air Enterprises 4HP16LTに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Allied Air Enterprises 4HP16LTデバイスの基本機能を使うにあたってのヒント。 Allied Air Enterprises 4HP16LTのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Allied Air Enterprises 4HP16LTに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAllied Air Enterprises 4HP16LTのメーカー/サービスへの連絡先に関する情報。

Allied Air Enterprises 4HP16LTについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAllied Air Enterprises 4HP16LTの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAllied Air Enterprises 4HP16LTで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)