  • AEG Protect C. R. 2000 VA - page 1

    OPERATING INSTRUCTIONS UPS PROTECT C. R PROTECT C. 1000 R (S) PROTECT C. 2000 R (S) PROTECT C. 3000 R (S) PROTECT C. 6000 R ...

  • AEG Protect C. R. 2000 VA - page 2

    Thank you for purchasing the PROTECT C. R. from AEG Power Solutions. Safety information an d operating instructi ons are included in this manual. To ensure correct use of the UPS, please read this manual thoroug hly before operating it. Save this manual properly . 2 ...

  • AEG Protect C. R. 2000 VA - page 3

    1 Notes on these Operating Instructions Duty to Provide Information These operating instructions will help you to install and operate the U ninterruptible P ower S upply (UPS) PROTECT C. 1000 R (S), PROTECT C. 2000 R (S), PROTECT C. 3000 R (S) o r P R O T E C T C . 6 0 0 0 R as well as the asso ciated external b a t t e r y u n i t s PROTEC T C. 10 ...

  • AEG Protect C. R. 2000 VA - page 4

    The wa rranty does not apply to damage caused by non- co mpli ance wit h th ese ins tru ctio ns (such damage also includes damaging the wa rra nty sea l). AEG w ill accept no liability for consequential damage. AEG rese rves the right to rescind all obligations such as warrant y agreements, service contracts, etc. entered into by AEG and its repre ...

  • AEG Protect C. R. 2000 VA - page 5

    Table of Contents 1 Notes on these Operating Instru ctions ............................ 3 2 General Information ......................................................... 7 2.1 Technology ............................................................... 7 2.2 System Descript ion ................................................... 8 3 Safety .......... ...

  • AEG Protect C. R. 2000 VA - page 6

    6 Signalling and Error Corre ction ......................................38 6.1 Signalling ................................................................. 38 6.2 Fault Diagnosis / Fault Rectification ........................40 6.2.1 Error Messag es ................................................ 40 7 Maintenance ................................. ...

  • AEG Protect C. R. 2000 VA - page 7

    2 General Information 2.1 Technology i PROTECT C.R is an U ninterruptible P ower S upply (UPS) for essential loads such as PCs, workstations, servers, network components, telecommunication equi pment and similar devices. It consis ts of:  Mains filter with overvoltage protection (applia nce protection/class D) a nd main s energy backfeed protect ...

  • AEG Protect C. R. 2000 VA - page 8

    2.2 System Description The UPS is connected bet ween the public utility's m ains and the loads to be protected. The power section of the rectif ier conv erts the mains voltage to DC voltage for supplying the inverter. The circuit technology use d (PFC) enable s sinusoidal current consumption and therefore oper ation with little system disturba ...

  • AEG Protect C. R. 2000 VA - page 9

    3 Safety 3.1 General Safety Instructions Read these operating instruction s prior to start -up of the PROTECT C.R UPS and its external battery module s (special accessories), and observe the safety instruction s! Only use the unit if it is in a technically perfect co ndition and always in accordance wit h its intended pu rpose, while being aware of ...

  • AEG Protect C. R. 2000 VA - page 10

    The UPS carries high voltage. Danger! The unit may only be opened by trained and qualified personnel. Repairs may only be carried out by qualified customer service staff! The output may be live, even if the UPS is not connected to the mains, sin ce the UPS has its own internal power supply (battery)! For health and safety reasons, the unit must be ...

  • AEG Protect C. R. 2000 VA - page 11

     The unit is designed to be installed insid e in heated rooms. Never install the housing in the vicinity of water or in an excessively damp environment!  Condensation may occur if the UPS is broug ht from a cold environment into the room where it is to be instal led. The UPS must be absolutely dry prior t o start-up. As a result, leave it to ...

  • AEG Protect C. R. 2000 VA - page 12

    Whe n replacing the batteries, the follo wing must be obse rved: Only ever use identical maintenance-f ree sealed lead batteries with the same data as the origi nal batteries. Danger! Explosiv e! Never throw batteries into open fire. Never open or damag e batteries. (Electrolyte may leak out and da mage skin and eyes. It may be toxic!) Batteries ca ...

  • AEG Protect C. R. 2000 VA - page 13

    3.3 CE- Certificate 13 ...

  • AEG Protect C. R. 2000 VA - page 14

    14 ...

  • AEG Protect C. R. 2000 VA - page 15

    3.4 Technical Data Type power PROTECT C. 1000 R (S) 1000 VA (cos  = 0.7 lag.) 700 W PROTECT C. 2000 R (S) 2000 VA (cos  = 0.7 lag.) 1400 W PROTECT C. 3000 R (S) 3000 VA (cos  = 0.7 lag.) 2100 W PROTECT C. 6000 R 6000 VA (cos  = 0.7 lag.) 4200 W UPS Input Rated input voltage 220 / 230 / 240 Vac Voltage tolerance range C. 1000 R (S) – C ...

  • AEG Protect C. R. 2000 VA - page 16

    O ve rv ol ta ge RJ11 (phone, fax, modem) dataline protection RJ4 5 (E th ern et 1 0/1 00 M Bit /s) UPS Output Rated output voltage C. 1000 R (S) – C. 3000 R (S) 220 / 230 / 240 Vac ± 2 % C. 6000 R 220 / 230 / 240 Vac ± 1 % (configuration via software “CompuWat ch”) Nominal frequency C. 1000 R (S) – C. 3000 R (S) 50 Hz / 60 Hz ± 0.2 % C. ...

  • AEG Protect C. R. 2000 VA - page 17

    C. 6000 R up to 105 % continuous; > 105 % – < 130 % for 10 min; 130 % for 1 s Then automatic inverter to Bypass in 0 ms (switches back when overload damps = Load < 90 %) Short circuit behavior 3 x I N for 140 ms Battery Autonomy time (full load with internal battery) PROTECT C. 1000 R 6 min. PROTECT C. 2000 R, C. 3000 R and C. 6000 R at ...

  • AEG Protect C. R. 2000 VA - page 18

    PROTE CT C. 2000 R S 9.6 A PROTECT C. 3000 R 1 A PROTECT C. 3000 R S 9.6 A PROTECT C. 6000 R 2 A Recharge time PROTECT C. – model s (to 90% of rated capacity) Coupled battery modules C. 1000 R C. 2000 R C. 3000 R C. 6000 R Integr. battery 5 h - - - 1 24 h 5 h 5 h 5 h 2 40 h 14 h 14 h 14 h 3 - 24 h 24 h 24 h 4 - 32 h 32 h 32 h 5 - 40 h 40 h 40 h T ...

  • AEG Protect C. R. 2000 VA - page 19

    Gener al Data Classification VFI SS 211 to IEC 62040–3 Double conversion technology Overall efficiency (full load) PROTECT C. 1000 R (S ) ≥ 85 % PROTECT C. 2000 R (S ) ≥ 85 % PROTECT C. 3000 R (S ) ≥ 88 % PROTECT C. 6000 R > 88 % Noise level (1m distance) PROTECT C. 1000 R (S ) < 45 dB (A) PROTECT C. 2000 R (S ) < 50 dB (A) PROTECT ...

  • AEG Protect C. R. 2000 VA - page 20

    Outlets PROTE CT C. 1000 R (S) 4 x IEC 320-10A PROTECT C. 2000 R (S ) 4 x IEC 320-10A PROTECT C. 3000 R (S) 1 x IEC 320-10A + 1 x IEC 320-16A PROTECT C. 6000 R 4 x IEC 320-10A + connection via terminal bl ock Equipment colour Black line Weights: PROTECT C. 1000 R 16.5 kg PROTECT C. 1000 R S 9.5 kg PROTECT C. 1000 R BP 19 kg PROTECT C. 2000 R 10 kg ...

  • AEG Protect C. R. 2000 VA - page 21

    Guidelines The PROTECT C.R complies with the pr oduct norm EN 50091. The CE symbol on the unit certifies the compliance to the EG guidelines for 73/23 EEC low voltage and for 89/336 EEC electromagnetic compatibility (EMC), wh en following the installation instructions in the manual. For the 73/23 EEC low voltage guidelines Reference number EN 62040 ...

  • AEG Protect C. R. 2000 VA - page 22

    4 Set-Up and Operation 4.1 Unpacking and Inspection The device has been fully tested and inspe cted. Although the device has been packed and shi pped with the usual degree of care, damage du ring transport cannot be ruled out completely. i Claims for damage during transport must always be made with the transport company! Check the shipping containe ...

  • AEG Protect C. R. 2000 VA - page 23

    Please keep the plastic packaging b ags away from babies and chil dren in order to safeguard against suffocation accidents. Handle the components with care. Please ta ke into account the weight. It may be necessary t o engage the help of a second person, particul arly in the case of the 2 and 3 kVA models and if there are external battery units. 4. ...

  • AEG Protect C. R. 2000 VA - page 24

    4.3 Overview: Connections, Operating / Display Elements 4.3.1 Front view PROTECT C. R (S) with 1000, 20 00, 3000 VA PROTECT C. R with 6000 VA 4.3.2 Re ar vi ew PROTECT C. 1000 R (S) PROTECT C. 2000 R (S) 24 ...

  • AEG Protect C. R. 2000 VA - page 25

    PROTECT C. 3000 R (S) PROTECT C. 6000 R Comments 1. Mains connection (UPS input) PROTECT C. 6000 R via terminal blo ck (Pos. 11) 2. Mains input circuit breake r 3. Load connections (UPS output s) PROTECT C. 3000 R (S) with additional load connection (IEC 320 -16A – Pos.9). PROTECT C. 6000 R additionally via terminal block (Pos.11) 4. Connection f ...

  • AEG Protect C. R. 2000 VA - page 26

    4.3.3 Display Explanations 1. ON-Pushbutton 2. OFF-Pushbutton (Off) / Alarm off 3. Green LED rectifier (UPS ON) 4. Orange LED for battery mode (BATTERY) 5. Orange LED bypass (BYPASS) 6. Green LED for net state (AC INPUT) 7. - 11. Bar graph LEDs ( 7-10 green, 11 orange) for UPS battery utilization re spectively capacity (remaining autonomy time) 7. ...

  • AEG Protect C. R. 2000 VA - page 27

    5 Commissioning 5.1 Mechanical Set-Up Note the following points whe n setting up the UPS system and its external battery units (special accessories):  Make sure the rack is able to support the weight. This is particularly important in conjunction with external b attery units (special accessories).  Install the units so that adequate air ci rc ...

  • AEG Protect C. R. 2000 VA - page 28

    5.2 External Battery Expansions PROTECT C. 2000 R, C. 3 000 R and C. 6000 R require at least one external battery module for ac curate operation. T o a c h i e ve longer backup time, it i s possible to conne ct multi-battery packs. Co nnect exclusively the following products together: PROTECT C. 1000 R with PROTECT C. 1000 R BP PROTECT C. 2000 R wi ...

  • AEG Protect C. R. 2000 VA - page 29

    PROTE CT C.R w ith 2 battery expansions Fig.: PROTECT C. 2000 R and 2 units C. 2030 R BP 1. Check the correct fit of the UPS and the battery unit (compare the stated DC voltage on the label of the UPS and the battery unit). Never connec t different battery voltage lev els with each other! 2. Now connec t the corresponding bat tery connectors using ...

  • AEG Protect C. R. 2000 VA - page 30

    provide d mains conne ction cable to a customa ry shockproof socket. Make sure that the dim ension of the circuit breaker is sufficient. Especially the PROTECT C. 3000 R (S) needs a circuit breaker with 16A. The PROTECT C. 6 000 R is connected directly with the modules via the terminal block. The cable diameter of each conductor is 6 mm². Th e cir ...

  • AEG Protect C. R. 2000 VA - page 31

    4. When being powered on, the UPS will perform self-diagnosis, the Load/Battery level LEDs will be turned on and then off one after another in ascending order. After sy nchronising the inverter successfully t he LED “UPS ON” will go on after some seconds, with the UPS in normal mode. If the power supply i s in order (mains within the range) an ...

  • AEG Protect C. R. 2000 VA - page 32

    5.3 Operating Statuses 5.3.1 Normal Operation Once you have connected the UPS to a suitable main s connection, you can start operation using the UPS main switch (see a lso "Electrical Start-Up" on pag e 29 ). Normally, the UPS o perates continuously. The UPS now su pplies the output with voltage, this being signall ed by the symbols mains ...

  • AEG Protect C. R. 2000 VA - page 33

    5.3.2 Battery Operation / Autonomy Operati on T he mains is not w ithin the r equired toleranc e range or has failed. In this case power is supplied to the inverter from the charged batter y without interruptio n. The power supply to the loads is there fore also ensured in the event of a mains failu re. This drains t he capacity of the battery and ...

  • AEG Protect C. R. 2000 VA - page 34

    5.3.3 Bypass Operation If the inverter is overloa ded or if overtemperature is detected, e.g. also if an inverter defect is detecte d, voltage is supplied to the load via the bypass that swit ches on automatically. This is signalled by the LED BYPASS symbol. This function is also referred to as passive re dundancy. It protects against total failure ...

  • AEG Protect C. R. 2000 VA - page 35

    5.3.4 Unit overload The lo ad on the UPS shou ld never exceed the specifi ed rated load of the unit. If a unit overload occurs nevertheless the fault LED is turned on accompani ed with a signal tone (twi ce per second). The conn ected loads continue to be supplied for a certain time depending on the l evel of the overload. However, the connected lo ...

  • AEG Protect C. R. 2000 VA - page 36

    5.4 Interfaces and communication 5.4.1 Data line protection RJ11 and RJ45 The incoming data lines are conn ected to the “IN” line at th e rear of the UPS. The “OUT” line is connected via data line with your terminal. i The data line protection suppo rts networks with transfer rates between 10 and 100 MBit/s. 5.4.2 Computer interfaces RS232 ...

  • AEG Protect C. R. 2000 VA - page 37

    5.4.4 Shutdown and UPS management software The "Comp uWatch" software specially develop ed for these purposes by AEG continuously checks the mains supply and the UPS status. In conjunction with the "intelli gent" UPS, this ensu res that the availability of IT components and data security is gu aranteed. The "CompuWatch" ...

  • AEG Protect C. R. 2000 VA - page 38

    6 Signalling and Error Correction 6.1 Signalling 1. ON push button (ON): Press the ON switch for about 2 seconds to switch on the UPS. UPS Test : To execute an UPS self test press this button for about 2 second s in the normal ope ration mode. 2. OFF push b utton (OFF): Press the OF F switch for about 2 seconds to swit ch off the UPS Deactivate aco ...

  • AEG Protect C. R. 2000 VA - page 39

    5. LED BYPAS S (bypass): The orang e LED lights up when the UPS system is supplying v oltage provided by the mains power via the bypass. 6. LED AC INP UT (mains status): The green LED lights up if mains voltage is in a specified range of tolerance. The LED ON LINE flashes when the phase and neutral condu ctor have been reverse d at the input of the ...

  • AEG Protect C. R. 2000 VA - page 40

    6.2 Fault Diagnosis / Fault Rectification The PROTECT C.R generate s detailed error messages. Support personal can localise and interpret faults q uickly and precisely. 6.2.1 Error Messages Problem Cause Solution UPS does not start. No indication, no warning tone even though system is connected to mains power supply. Mains and battery voltage not i ...

  • AEG Protect C. R. 2000 VA - page 41

    Emergency supply period shorter than nominal value Batteries not fully charged / batteries old resp. defect Charge the batteries for at least for the charging time acc. Chapter 3.4, page 18 and then check capacity. If the problem still persists, consult your dealer. LED ALARM lights, LED BATTERY blinks, warning tone once a second Charger or Batteri ...

  • AEG Protect C. R. 2000 VA - page 42

    7 Maintenance The PROTECT C.R con sists of advanced and resistant components. To guara ntee a continuous and high availability it is recomme nded to check the u nit (especially the batteries and the fans) in regular intervals (at least every 6 months). CAUTION: Follow safety and security regulations unconditionally! 7.1 Charging the Battery The bat ...

  • AEG Protect C. R. 2000 VA - page 43

    7.2.1 Visual Check Whe n visually checking the unit, check whether:  there is any mechanical damage or foreign bodies c an be found in the system,  any conductive dirt or dust has accumulated in the unit,  accumulation of dus t affects heat supply and dissipation. CAUTION: PROTECT C.R must be disconnected from the power supply prior to ca ...

  • AEG Protect C. R. 2000 VA - page 44

    8 S torage, Dismantling and Disposal 8.1 Storage Long storage times without charging o r discharging the battery at regular intervals may lead to permanent damage of the battery. If the battery is stored at room temperature (20° C to 30° C) it will automatically discharge at a rate of 3 - 6% per month due to internal reactions. Storing the batter ...

  • AEG Protect C. R. 2000 VA - page 45

    9 Glossary 9.1 Technical terms Appliance protection Su rge technolog y term The conventional mains su rge protection consists of an mains earthwire (class B), an overvoltage protection (class C) and an appliance protection (class D) – see also e.g. under http://www.phoenixcontact.de (topic „TRABTECH“ ) Class D see appliance protection DC/DC B ...

  • AEG Protect C. R. 2000 VA - page 46

    Guarantee certificate Type: …….…………………............... .............. ........... .............. Serial-no.: …………………….. ……………............... ................ Date of purchase: …………….............……………………........ Trading stamp / Signature Specifications ar e subject to chang e witho ...

メーカー AEG カテゴリー Uninterruptible power supply (

AEG Protect C. R. 2000 VAのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- Protect C. R. 2000 VAの取扱説明書
- AEGの製品カード
- パンフレット
- またはAEG Protect C. R. 2000 VAの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、AEG Protect C. R. 2000 VAの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、AEG Protect C. R. 2000 VAの取り付け説明書、サービスマニュアル、簡易説明書、またはAEG Protect C. R. 2000 VAのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、AEG Protect C. R. 2000 VAの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

AEG Protect C. R. 2000 VAデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAEG Protect C. R. 2000 VAを使用するのを助ける技術的文書のことです。説明書は通常、全てのAEG Protect C. R. 2000 VAユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

AEGの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. AEG Protect C. R. 2000 VAの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAEG Protect C. R. 2000 VAの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。AEG Protect C. R. 2000 VAに関してこのドキュメントで見つけることができる全てのヒントの目次
3. AEG Protect C. R. 2000 VAデバイスの基本機能を使うにあたってのヒント。 AEG Protect C. R. 2000 VAのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。AEG Protect C. R. 2000 VAに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAEG Protect C. R. 2000 VAのメーカー/サービスへの連絡先に関する情報。

AEG Protect C. R. 2000 VAについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAEG Protect C. R. 2000 VAの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAEG Protect C. R. 2000 VAで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)