  • Anaheim MBC10SI1 - page 1

    1 #L010185 June 2007 MBC10SI1 Programmable Simple Indexer/Driver User’s Guide 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714) 992-0471 website: www.anaheimautomation.com ANAHEIM AUTOMATION ...

  • Anaheim MBC10SI1 - page 2

    2 #L010185 June 2007 Introduction The MBC10SI1 is an low cost single axis step motor driver integrated with a programmable simple indexer. The MBC10SI1 microstep driver/pulse generator has an output current capability of 1.5A minimum to 10.0A maximum (peak rating). The MBC10SI1 driver operates with a DC voltage of 20VDC to 80VDC. The MBC10SI1’s i ...

  • Anaheim MBC10SI1 - page 3

    3 #L010185 June 2007 A) A Profile input is activated; Ramps up to max speed. B) No limit is active; Max speed is reached (keeps running at max speed). C) No limit is active; Internal counter signals to ramp down to base speed. D) Internal Counter is complete; Base speed is reached. Pulses stop. AB C Max Speed Base Speed Off Time Speed AB CD Max Spe ...

  • Anaheim MBC10SI1 - page 4

    4 #L010185 June 2007 LEDs When powered and operated properly, the status LED will be green. When a communication or program syntax error occurs, the LED will change to RED and an error code will be generated in the error code register. To read and clear the error with the software, click on the “Verify Parameters” button. To read and clear the ...

  • Anaheim MBC10SI1 - page 5

    5 #L010185 June 2007 Connector Description : 2 P r o t c e n n o C # n i P n o i t p i r c s e D 1) C D V 0 ( d n u o r G y l p p u S r e w o P 2) C D V 0 8 - C D V 0 2 ( t u p n I y l p p u S r e w o P 3) A ( 1 e s a h P r o t o M 4) A / ( 3 e s a h P r o t o M 5) B ( 2 e s a h P r o t o M 6) B / ( 4 e s a h P r o t o M 71 x e d n I 82 x e d n I 9 ...

  • Anaheim MBC10SI1 - page 6

    6 #L010185 June 2007 s t n e m e r i u q e R e g a t l o VC D V 0 8 - 0 2 ) 8 d n a 7 s n i P ( s t u p n I e l i f o r Pt r a t S) C D V 0 ( w o L ) n i P ( t u p n I n o i t c e r i D W C) n e p O ( h g i H W W C) C D V 0 ( w o L ) n i P ( t u p n I f f O / n O n O) n e p O ( h g i H f f O) C D V 0 ( w o L ) n i P ( t u p t u O y s u B f f O d n ...

  • Anaheim MBC10SI1 - page 7

    7 #L010185 June 2007 Wiring Diagrams Dimensions and Jumper/Potentiometer Locations ...

  • Anaheim MBC10SI1 - page 8

    8 #L010185 June 2007 Setting the Output Current The output current on the MBC10SI1 is set by the on-board potentiometer R29 (Refer to Dimensions/ Jumper and Potentiometer Locations). This current adjust potentiometer determines the per phase peak output current of the driver. This relationship between the output current and the potentiometer settin ...

  • Anaheim MBC10SI1 - page 9

    9 #L010185 June 2007 Step Motor Configurations Step motors can be configured as 4, 6, or 8 leads. Each configuration requires different currents. Refer to the lead configurations and the procedures to determine their output current. WARNING! Step motors will run hot even when configured correctly. Damage may occur to the motor if a higher than spec ...

  • Anaheim MBC10SI1 - page 10

    10 #L010185 June 2007 8 Lead Motors Series Connection: When configuring the motor windings in series, use the per phase (or unipolar) current rating to determine the current setting potentiometer value. Parallel Connection: When configuring the motor windings in parallel, multiply the per phase (or unipolar) current rating by 2.0 to determine the c ...

  • Anaheim MBC10SI1 - page 11

    11 #L010185 June 2007 Functions Hard Limit Switches: When a hard limit switch is encountered, the pulses will stop. Hard limits are intended as an emergency stop for your system. Soft Limit Switches: These switches cause the indexer to ramp down to the base speed and finish the index, unless encountering a hard limit switch. Profile Inputs: These i ...

  • Anaheim MBC10SI1 - page 12

    12 #L010185 June 2007 SMPG-SMSI Software The SMPG-SMSI software is a handy utility that supports Anaheim Automation’s programmable pulse generators and simple indexers. Connecting your PC to the MBC10SI1, via a USB cable, the software can easily perform the following tasks: • Exercise and monitor the MBC10SI1 • Directly communicate with the M ...

  • Anaheim MBC10SI1 - page 13

    13 #L010185 June 2007 “The Unit is Connected” / “The Unit is NOT Connected” On the right of the T oolbar , the user will find the communication status of the indexer . If communications is not established, please refer to the troubleshooting section. File Menu Setup Menu Ex t ie r a w t f o s N I W 0 1 G P M S e h t t i x E Ct c e n n o. r ...

  • Anaheim MBC10SI1 - page 14

    14 #L010185 June 2007 Program Window e l i f o r P n o i t o M2 r o , 1 s e l i f o r p n o i t o m t c e l e S l e c e D / l e c c A d n e S c e s / s p e t s ( . r e x e d n i e h t o t r e t e m a r a p n o i t a r e l e c e d & n o i t a r e l e c c a e h t d n e S 2 ) d e e p S e s a B d n e S ) c e s s / p e t s ( . r e x e d n i e h t o ...

  • Anaheim MBC10SI1 - page 15

    15 #L010185 June 2007 Direct mode is used to directly control the motion for real time movements through serial communication. The indexer has 14 commands which are easy to remember for direct movement of a step motor . COM Port Settings Baud Rate: 1 15200 Parity: None Data Bits: 8 Stop Bits: 1 Flow Control: Xon/Xoff Unit Selection In order to sele ...

  • Anaheim MBC10SI1 - page 16

    16 #L010185 June 2007 $ - Version Number Register Format : $ Description: This command requests the indexer to return the version number . ! - Error Codes Register Format : ! Description: This command requests the indexer to get the current error code and print it to the screen. +/- - Direction Format: + or - Description: This command sets the dire ...

  • Anaheim MBC10SI1 - page 17

    17 #L010185 June 2007 C - Current Reduce Option Format: C# - where # is 0 or 1 Description: This command enables the driver to reduce current after pulses are done being sent. A 1 will enable current reduction, and a 0 will disable current reduction. This value is saved in the EEProm for standalone use. G - Go Slew (Run) Format : G# - where # is th ...

  • Anaheim MBC10SI1 - page 18

    18 #L010185 June 2007 S - Stop Soft Format: S Description: This command will cause the indexer to ramp down to base speed and run until the index is complete or a hard limit is activated. It can only be used when the unit is indexing. T - Complete Time Format: T#_[value] - where # is the motion profile number 1 or 2 Sample: T1_100 Complete T ime of ...

  • Anaheim MBC10SI1 - page 19

    19 #L010185 June 2007 Visual Basic Direct Mode Programming Examples Example 1: This Example is for Axis=0, and Profile=1 DimConst DefaultT imeout As Single = 0.5 frmMain.MSComm1.Output = "@0A1_100000” & Chr$(13) ‘Set Acceleration Pause DefaultT imeout frmMain.MSComm1.Output = "@0B1_1000” & Chr$(13) ‘Set Base S peed Pause D ...

  • Anaheim MBC10SI1 - page 20

    20 #L010185 June 2007 Troubleshooting Problem: Can not establish communications with the indexer. Possible Solutions: 1) Make sure the indexer has power. Is the Green LED on. 2) Check USB connections. 3) Check for loose cable connection either on the indexer or COM Port. 4) W as the software and drivers installed successfully? 5) Go to Setup | Comm ...

  • Anaheim MBC10SI1 - page 21

    21 #L010185 June 2007 e d o C r o r r E e p y T n o i t p i r c s e D 1 w o l f r e v O e v e i c e R r o r r E r o r r e l a n r e t n i n a s i s i h T . r o r r e g n i v e i c e r a d a h s n o i t a c i n u m m o c l a i r e s e h T . r e t u p m o c e h t y b d e s u a c 2r o r r E e g n a R k c e h C . r o t a r e n e g e s l u p e h t o t t ...

  • Anaheim MBC10SI1 - page 22

    22 #L010185 June 2007 Copyright Copyright 2005 by Anaheim Automation. All rights reserved. No part of this publication may be repro- duced, transmitted, transcribed, stored in a retrieval system, or translated into any language, in any form or by any means, electronic, mechanical, magnetic, optical, chemical, manual, or otherwise, without the prior ...

メーカー Anaheim カテゴリー Computer Accessories

Anaheim MBC10SI1のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MBC10SI1の取扱説明書
- Anaheimの製品カード
- パンフレット
- またはAnaheim MBC10SI1の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Anaheim MBC10SI1の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Anaheim MBC10SI1の取り付け説明書、サービスマニュアル、簡易説明書、またはAnaheim MBC10SI1のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Anaheim MBC10SI1の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Anaheim MBC10SI1デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAnaheim MBC10SI1を使用するのを助ける技術的文書のことです。説明書は通常、全てのAnaheim MBC10SI1ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Anaheimの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Anaheim MBC10SI1の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAnaheim MBC10SI1の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Anaheim MBC10SI1に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Anaheim MBC10SI1デバイスの基本機能を使うにあたってのヒント。 Anaheim MBC10SI1のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Anaheim MBC10SI1に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAnaheim MBC10SI1のメーカー/サービスへの連絡先に関する情報。

Anaheim MBC10SI1についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAnaheim MBC10SI1の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAnaheim MBC10SI1で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)