    Installation and Operation Instructions Docyment 1246 H2343400- Modulating Boiler Model BRHHH Modulating W ater Heater Model BRHHV U.S. Patent No. 6,644,393 Canada Patent Pending W ARNING If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life. Do not store ...

  • Bradford-White Corp BRHHH - page 2

    B RADFORD W HITE C ORP . Page 2 ...

  • Bradford-White Corp BRHHH - page 3

    Brute Magnum Page 3 T able of Contents SECTION 1 General Information 1.1 Introduction ...................................................... 5 1.2 Model Identification .......................................... 5 1.3 W arranty .......................................................... 6 1.4 Dimensions .............................................. ...

  • Bradford-White Corp BRHHH - page 4

    B RADFORD W HITE C ORP . Page 4 T able 1 Clearances ........................................................ 6 T able 2 V ent / Air Pipe Sizes .......................................... 7 T able 3 Horizontal V ent and Air T erminals for Indoor Installations ....................................... 8 Figure 1 Dimensional Drawing ..................... ...

  • Bradford-White Corp BRHHH - page 5

    Brute Magnum Page 5 Section 1 GENERAL INFORMA TION USING THIS MANUAL – Because the Brute Magnum Boilers and Brute Magnum W ater Heaters are identical appliances, with the exception of materials of manufacture, labels and ultimate use application, this manual provides information for the pr oper installation, operation and maintenance of both prod ...

  • Bradford-White Corp BRHHH - page 6

    B RADFORD W HITE C ORP . Page 6 (13) Revision 2 = Second version (14) Heat Exchanger E = Glass-lined steel with copper tubes F = Glass-lined steel with cupronickel tubes (15) Control Option Code X = Standard, meets CSD-1 boiler standard A = Control Pack A: CSD-1, CA, FM, IL, IRI, Alarm Bell B = Control Pack B: CSD-1, CA, FM, IL, LDS, MN F = Non CSD ...

  • Bradford-White Corp BRHHH - page 7

    Brute Magnum Page 7 Figure 1. Dimensional Drawing. Size Intake Exhaust Intake Exhaust Size Size Maximum Run Maximum Run 1200 6" (15 cm) dia. 6" (15 cm) dia. 50 linear feet with 5 elbows 50 linear feet with 5 elbows 1600 8" (20 cm) dia. 6" (15 cm) dia. 50 linear feet with 5 elbows 50 linear feet with 5 elbows 2000 8" (20 cm) ...

  • Bradford-White Corp BRHHH - page 8

    B RADFORD W HITE C ORP . Page 8 2.1.2 Intake Combustion Air The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal, shown in T able 3. See T able 2 to select the appropriate diameter air pipe. When taken from the roof, a field-suppl ...

  • Bradford-White Corp BRHHH - page 9

    Brute Magnum Page 9 T erm Description Pipe Single-wall galvanized steel pipe, 24 gauge minimum (sized per section 1.9) Joint Permanent duct tape or aluminum tape Sealing Insulation Not required, but recommended R5 insulation for cold installations (consult American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) handbook ...

  • Bradford-White Corp BRHHH - page 10

    B RADFORD W HITE C ORP . Page 10 Figure 3. Combustion Air and V ent Through Side Wall. *When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9m) above the air inlet. U.S. Installations (see note 1) Canadian Installations (see note 2) A= Clearance above grade, veranda, porch, 12 i ...

  • Bradford-White Corp BRHHH - page 11

    Brute Magnum Page 1 1 1. The figure in this addendum shows the requirements for mechanical vent terminal clearances for the U.S. and Canada. 2. V ent terminals for condensing appliances or appliances with condensing vents are not permitted to terminate above a public walkway , or over an area where condensate or vapor could create a nuisance or haz ...

  • Bradford-White Corp BRHHH - page 12

    B RADFORD W HITE C ORP . Page 12 (c) MANUF ACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufactur er of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equi ...

  • Bradford-White Corp BRHHH - page 13

    Brute Magnum Page 13 At the time of removal of an existing boiler , the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation. 1. Seal any unused openings in the common venting system ...

  • Bradford-White Corp BRHHH - page 14

    B RADFORD W HITE C ORP . Page 14 7. All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas. 8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kpa). 9. The unit must ...

  • Bradford-White Corp BRHHH - page 15

    Brute Magnum Page 15 medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler . The boiler piping system of a hot water heating boiler connected to heating coils located in air handling appliances where they may be exposed to refrigerated air circulation must be equipped with flow co ...

  • Bradford-White Corp BRHHH - page 16

    B RADFORD W HITE C ORP . Page 16 4B.3 W ater Flow Requirements — W ater Heater In a water heating application (an open system), new water is constantly being introduced. W ith the new water comes a fresh supply of minerals that can be deposited on the unit’ s heat exchanger . This is commonly known as scaling. The amount of minerals will depend ...

  • Bradford-White Corp BRHHH - page 17

    Brute Magnum Page 17 If the water at the inlet of the copper heat exchanger is less than 140°F (60°C), water from the outlet of the copper heat exchanger will be directed back to the inlet of the copper heat exchanger , and will mix to bring the inlet water up to 140°F (60°C). Once through the copper heat exchanger , the water picks up another ...

  • Bradford-White Corp BRHHH - page 18

    B RADFORD W HITE C ORP . Page 18 4B.4 Combined W ater (potable) Heating and Space Heating NOTE: These systems are not allowed in the Commonwealth of Massachusetts. Piping and components connected to this water heater for the space heating application shall be suitable for use with potable water . T oxic chemicals, such as used for boiler treatment, ...

  • Bradford-White Corp BRHHH - page 19

    Brute Magnum Page 19 Figure 7. Internal Piping Schematic. 4B.5 Freeze Protection – W ater Heater Brute Magnum heaters are not designed to be placed outdoors, due to the potential for condensate to freeze in the unit. Power outage, interruption of gas supply , failure of system components, activation of safety devices, etc., may prevent a heater f ...

  • Bradford-White Corp BRHHH - page 20

    B RADFORD W HITE C ORP . Page 20 Figure 8. W ater Heater Piping — One Heater , One T ank. ...

  • Bradford-White Corp BRHHH - page 21

    Brute Magnum Page 21 Figure 9. W ater Heater Piping — Multiple Heaters, One T ank. ...

  • Bradford-White Corp BRHHH - page 22

    B RADFORD W HITE C ORP . Page 22 Figure 10. W ater Heater Piping — One Heater , Multiple T anks. ...

  • Bradford-White Corp BRHHH - page 23

    Brute Magnum Page 23 Figure 1 1. Water Heater Piping — Multiple Heaters, Multiple T anks. ...

  • Bradford-White Corp BRHHH - page 24

    B RADFORD W HITE C ORP . Page 24 Section 5 ELECTRICAL CONNECTIONS W ARNING The appliance must be electrically grounded in accordance with the requirements of the authority having jurisdiction or , in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFP A 70, in the U.S. and with latest edition of CSA C ...

  • Bradford-White Corp BRHHH - page 25

    Brute Magnum Page 25 temperature is less than 140°F (60°C), internal mixing will keep the outlet temperature at 160-165°F (71- 74°C), and this will mix with the tank temperature to maintain a lower temperature in the tank. If the return temperature is 140°F (60°C) or higher , the outlet temperature of the heater will be the return temperature ...

  • Bradford-White Corp BRHHH - page 26

    B RADFORD W HITE C ORP . Page 26 tank is drawing down, the heater will react to sustain a minimum tank temperature. Boilers generally have higher differentials than water heaters, to minimize short cycling (see throttling range). The dif ferential is set by removing the cover of the A350 control and adjusting the potentiometer marked “DIFF” (se ...

  • Bradford-White Corp BRHHH - page 27

    Brute Magnum Page 27 5.5.6 Integration Constant The proportional control used on the Brute Magnum has internal circuitry that helps to minimize overshoot that can sometimes be associated with proportional plus integral (PI) controls. There are three field-selectable integration constants (slow , medium and fast), and an off position on the proporti ...

  • Bradford-White Corp BRHHH - page 28

    B RADFORD W HITE C ORP . Page 28 another 20-25°F (1 1-14°C) (when at high fire), and it leaves the boiler at 160-165°F (71-74°C). This hot water is then sent to the system. If the water at the inlet of the copper heat exchanger is 140°F (60°C), or higher , the water will be allowed to flow through the copper heat exchanger and directly to the ...

  • Bradford-White Corp BRHHH - page 29

    Brute Magnum Page 29 The second menu “Add” has to do with the N2 address. Pressing enter when “Add” is displayed will display “255”, which stands for 255 unique addresses. The up and down arrows change this value, and enter saves the value if it is changed. Changing the “Add” value will have no affect on the Brute Magnum, unless a c ...

  • Bradford-White Corp BRHHH - page 30

    B RADFORD W HITE C ORP . Page 30 Figure 17. Wiring Diagram, Size 1200, Standard and Codes A and F . ...

  • Bradford-White Corp BRHHH - page 31

    Brute Magnum Page 31 Figure 18. Wiring Diagram, Sizes 1600, 2000 and 2400, Standard and Codes A and F . ...

  • Bradford-White Corp BRHHH - page 32

    B RADFORD W HITE C ORP . Page 32 Figure 19. Wiring Diagram, Size 1200, Code B. ...

  • Bradford-White Corp BRHHH - page 33

    Brute Magnum Page 33 Figure 20. Wiring Diagram, Sizes 1600, 2000 and 2400, Code B. ...

  • Bradford-White Corp BRHHH - page 34

    B RADFORD W HITE C ORP . Page 34 Figure 21. Wiring Schematic, Model 1200, Standard and Codes A and F . Figure 22. Wiring Schematic, Models 1600, 2000 and 2400, Standard and Codes A and F . ...

  • Bradford-White Corp BRHHH - page 35

    Brute Magnum Page 35 Figure 23. Wiring Schematic, Model 1200, Code B. Figure 24. Wiring Schematic, Models 1600, 2000 and 2400, Code B. ...

  • Bradford-White Corp BRHHH - page 36

    B RADFORD W HITE C ORP . Page 36 Section 6 OPERA TING INSTRUCTIONS 6.1 Filling the Boiler System 1. Ensure the system is fully connected. Close all bleeding devices and open make-up water valve. Allow system to fill slowly . 2. If make-up water pump is employed, adjust pressure switch on pumping system to provide a minimum of 12 psi (81.8 kPa) at t ...

  • Bradford-White Corp BRHHH - page 37

    Brute Magnum Page 37 Figure 25. Gas/Air T est Panel. Figure 26. T est Panel V alves. panel are closed (see Figure 26). 5. Remove the two plugs from the + and – ports of the air orifice taps, thread hose barbs into the 1/8" NPT connections, and attach the manometer pressure lines to the barbs. Be sure all connections are gas tight. 6. Switch ...

  • Bradford-White Corp BRHHH - page 38

    B RADFORD W HITE C ORP . Page 38 (c) Open gas shutoff valve. Restart the appliance. The ignition sequence will start again and the burner will start. The appliance will return to its previous mode of operation. Caution Should any odor of gas be detected, or if the gas burner does not appear to be functioning in a normal manner , CLOSE MAIN SHUTOFF ...

  • Bradford-White Corp BRHHH - page 39

    Brute Magnum Page 39 Figure 27. Gas T rains. ...

  • Bradford-White Corp BRHHH - page 40

    B RADFORD W HITE C ORP . Page 40 Figure 28. Gas T rains.                    ? ...

  • Bradford-White Corp BRHHH - page 41

    Brute Magnum Page 41 shutoff valve. Remove the front and right-side panels from the unit. Disconnect the union between the valve body and the blower . Label the four pr essure tubes that are connected to the valve actuator , to ensur e that they will be replaced corr ectly . Remove the valve actuator , per the instructions above. Unscrew the valve ...

  • Bradford-White Corp BRHHH - page 42

    B RADFORD W HITE C ORP . Page 42 7.2.10 Mixing Actuator The mixing actuator connects to both mixing valves and takes its signal from the mixing control to properly set the valves to protect the copper heat exchanger . T o remove the actuator, remove the screw on the front to take the cover off. Disconnect the wires. T ake the 2 nuts off the U-bolt, ...

  • Bradford-White Corp BRHHH - page 43

    Brute Magnum Page 43 8. Clean the heat exchanger: A light accumulation of soot or corrosion on the outside of the heat exchanger can be easily removed. Use a wire brush to remove loose soot and scale from the heat exchanger . Do not use water or compressed air for cleaning. 9. NOTE: While the heat exchanger is out of the unit, inspect the firewall ...

  • Bradford-White Corp BRHHH - page 44

    B RADFORD W HITE C ORP . Page 44 6. When the call for heat is complete, or the unit reaches its setpoint temperature, the gas valve will close, and the fan will continue to run for its 30 second post-purge. If a pump time delay is used, the pump will continue to run for the specified amount of time (adjustable from 0.1 to 10 minutes). 8.2 Resolving ...

  • Bradford-White Corp BRHHH - page 45

    Brute Magnum Page 45 8.5 Short Cycling — W ater Heater Short cycling will generally occur only in combination space heating and water heating applications when the water heater is operating in the space-heating mode. Because the Brute Magnum is a modulating water heater and its input will reduce when there is a reduction in heating load, short cy ...

  • Bradford-White Corp BRHHH - page 46

    B RADFORD W HITE C ORP . Page 46 9.2 Parts List COMBUSTION COMPONENTS – See Figure 30 1200 1600 2000 2400 2 Base assembly 24A1200 24A1200 24A1200 24A1200 3 Panel, top, combustion chamber 24B2600 24B2600 24B2600 24B2600 4 Panel, bottom, combustion chamber 24A2400 24A2400 24A2400 24A2400 5 Panel, left, combustion chamber 24A2100 24A2100 24A2100 24A ...

  • Bradford-White Corp BRHHH - page 47

    Brute Magnum Page 47 50 T ubing/Fittings (gas train repair kit) R2020700 R2020700 R2020700 R2020700 51 Air filter box assembly (with gasket and hardware) Nat 12B5000 16B5000 20B5000 24B5000 51 Air filter box assembly (with gasket and hardware) LP 12B5020 16B5020 20B5020 24B5020 52 Air filter A2108300 A2108300 A2108300 A2108300 53 Gasket kit, air ...

  • Bradford-White Corp BRHHH - page 48

    B RADFORD W HITE C ORP . Page 48 105 Switch, Low water cutof f, Manual Reset RE2075100 RE2075100 RE2075100 RE2075100 HEA T EXCHANGER / W A TER P A TH – See Figures 34 and 35 1 10 Header cover 12A4200 16A4200 20A4200 24A4200 1 1 1 W ater barrier assembly 12B4100 16B4100 20B4100 24B4100 1 12 Gasket, heat exchanger cover S201 1900 S2102500 S2102600 ...

  • Bradford-White Corp BRHHH - page 49

    Brute Magnum Page 49 Figure 30. Combustion Components. ...

  • Bradford-White Corp BRHHH - page 50

    B RADFORD W HITE C ORP . Page 50 Figure 31. Gas T rain/Combustion Air Components. ...

  • Bradford-White Corp BRHHH - page 51

    Brute Magnum Page 51 Figure 32. Gas T rain Components.                              ? ...

  • Bradford-White Corp BRHHH - page 52

    B RADFORD W HITE C ORP . Page 52 Figure 33. Electrical Components. ...

  • Bradford-White Corp BRHHH - page 53

    Brute Magnum Page 53 Figure 34. Heat Exchanger / W ater Path Components. ...

  • Bradford-White Corp BRHHH - page 54

    B RADFORD W HITE C ORP . Page 54 Figure 35. Heat Exchanger / W ater Path Components. ...

  • Bradford-White Corp BRHHH - page 55

    Brute Magnum Page 55 Figure 36. Jacket Components. ...

  • Bradford-White Corp BRHHH - page 56

    H2343400- ® Ambler , P A 19002 T ech. Service (800) 334-3393 Service Parts (800) 538-2020 www .BradfordWhite.com W arranty Service (800) 531-21 1 1 Litho in U.S.A. © Bradford White 1 102 Document 1246 Bradford White Company reserves the right to change specifications, components, features, or to discontinue products without notice. ...

メーカー Bradford-White Corp カテゴリー Boiler

Bradford-White Corp BRHHHのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- BRHHHの取扱説明書
- Bradford-White Corpの製品カード
- パンフレット
- またはBradford-White Corp BRHHHの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bradford-White Corp BRHHHの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bradford-White Corp BRHHHの取り付け説明書、サービスマニュアル、簡易説明書、またはBradford-White Corp BRHHHのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bradford-White Corp BRHHHの製品を使用するにあたって最も人気のある説明書を閲覧できます。

Bradford-White Corp BRHHHデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBradford-White Corp BRHHHを使用するのを助ける技術的文書のことです。説明書は通常、全てのBradford-White Corp BRHHHユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bradford-White Corpの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bradford-White Corp BRHHHの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBradford-White Corp BRHHHの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bradford-White Corp BRHHHに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bradford-White Corp BRHHHデバイスの基本機能を使うにあたってのヒント。 Bradford-White Corp BRHHHのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bradford-White Corp BRHHHに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBradford-White Corp BRHHHのメーカー/サービスへの連絡先に関する情報。

Bradford-White Corp BRHHHについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBradford-White Corp BRHHHの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBradford-White Corp BRHHHで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)