Summary
  • Nordyne R-410A - page 1

    Outdoor Heat Pump 13 SEER R-410A High Effi ciency Split System User’ s Inf ormation/Installation Instructions These units hav e been designed and tested f or capacity and effi ciency in accordance with A.R.I. Standards. Split System Heat Pump units are designed f or use with a wide variety of f ossil fuel fur naces , electric fur naces, air han ...

  • Nordyne R-410A - page 2

    2 ...

  • Nordyne R-410A - page 3

    3 2. Set the ther mostat temper ature to the desired temperature le v el using the temperature selector . Please ref er to the separate detailed thermostat user’ s manual f or complete instructions regarding ther mostat prog ramming. The outdoor unit and indoor blo wer will both cycle on and off to maintain the indoor temperature at the desired h ...

  • Nordyne R-410A - page 4

    4 of snow and ice on the heat tr ansfer coil. This is nor mal, and the unit will periodically defrost itself . Dur ing the defrost cycle, the outdoor f an will stop , and the compressor will continue to run and heat the outdoor coil, causing the snow and ice to melt. After the snow and ice ha ve melted, some steam ma y rise from the outdoor unit as ...

  • Nordyne R-410A - page 5

    5 GENERAL INFORMA TION Read the f ollowing instructions completely before perf or ming the installation. CA UTION: This unit uses refrigerant R-410A. DO NO T under an y circumstances use any other refrigerant besides R-410A in this unit. Use of another refrigerant will damage this unit. Outdoor Unit Section — Each outdoor unit is shipped with a r ...

  • Nordyne R-410A - page 6

    6 outdoor unit must be installed in such a manner that airfl o w through the coil is not obstr ucted and that the unit can be ser viced. Facility Prerequisites — Electrical pow er supplied must be adequate f or proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes ...

  • Nordyne R-410A - page 7

    7 Wire Size based on N.E.C . for 60° type copper con- ductors. COPPER WIRE SIZE — AWG (1% Voltage Drop) Supply Wire Length-Feet Supply Circuit 200 150 100 50 Ampacity 6 8 10 14 15 468 1 2 2 0 468 1 0 2 5 446 1 0 3 0 3468 3 5 3468 4 0 2346 4 5 2346 5 0 Wiring Diagram/Schematic — A wiring diagram/schematic is located on the inside co ver of the ...

  • Nordyne R-410A - page 8

    8 GR W 2 CE O Y Thermostat Green Red Br own G R W 2 Orange Grey OY R C Air Handler Heat Pump OD Section T ypical Heat Pump with Standard Air Handler W 2 C W NO TE: Jumper between W2 and E is required when no OD T -Stat is used. For 2-Stage Heater Kits ...

  • Nordyne R-410A - page 9

    9 GR W 2 CE O Y Thermostat Green Red White G R Grey O Y R C Air Handler Heat Pump OD Section T ypical Heat Pump with Outdoor Thermostat and Air Handler W 2 C W E A typical installation with a heat pump ther mostat, air handler , and heat pump with an outdoor ther mostat. ...

  • Nordyne R-410A - page 10

    10 Functional Chec kout: CA UTION: If equipped with a compressor crankcase heater , wait 24 hours prior to performing a function c heck out to allow f or heating of the compressor crankcase. F ailure to comply ma y result in damage and could cause premature failure of the system. Indoor Blower — Set the thermostat function s witch to COOLING and ...

  • Nordyne R-410A - page 11

    11 Figure 2. Comfort Alert TM Diagnostics Module POWER ALERT TRIP TRIP LED (Red): indicates there is a demand signal from the ther mostat b ut no current to the compressor is detected by the module . The TRIP LED typically indicates the compressor protector is open or ma y indicate missing supply power to the compressor . The scroll compressor’ s ...

  • Nordyne R-410A - page 12

    12 T able 1. Interpreting the Diagnostic LEDS Status LED Sta tus LED Description Status LED T roubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” Thermostat demand signal 1 . Compressor protector is open Y is present, but the 2 . Outdoor unit power disconnect is open compressor ...

  • Nordyne R-410A - page 13

    13 T able 2. Module Wiring T r oubleshooting f or any unusual noises . If present, locate and deter mine the source of the noise and correct as necessar y . OUTDOOR THERMOST A T (if supplied) The outdoor ther mostat pre v ents the electrical auxiliar y heat (if used) from operating abo v e a desired set point. Selection of the set point is deter mi ...

  • Nordyne R-410A - page 14

    14 13 SEER SPLIT SYSTEM HEA T PUMP ORIFICE USA GE Model System Charge Number Indoor Outdoor R-22 (oz.) 1-1/2 Ton .050 .042 112 2 Ton .055 .045 138 2-1/2 Ton .065 .048 145 3 Ton .073 .052 168 3-1/2 Ton .077 .055 243 4 Ton .080 .058 248 5 Ton .089 .062 248 Restrictor Bore Size (in.) 2. With compressor running in heat mode, fi rst jump the “T2”-? ...

  • Nordyne R-410A - page 15

    15 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts *Note: All pressures are listed in psig. and all temperatures in deg. F. - Shaded bo x es indicate fl ooded conditions - Rated design v alues. Suction Pressure will be low er than design value if indoor air fl ow , entering dr y bulb , or entering we ...

  • Nordyne R-410A - page 16

    16 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts 024K OUTDOOR TEMPERA TURE ( deg. F ) 70 75 80 85 90 95 100 105 Suc. Press. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press . Dis. T emp. Liq. Press. Dis. T emp . Liq. Press . Dis. T emp. Liq. ...

  • Nordyne R-410A - page 17

    17 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts 036K OUTDOOR TEMPERA TURE ( deg. F ) 70 75 80 85 90 95 100 105 Suc. Press. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press. Dis. T emp . Liq. Press . Dis. T emp. Liq. ...

  • Nordyne R-410A - page 18

    18 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts 048K OUTDOOR TEMPERA TURE ( deg. F ) 70 75 80 85 90 95 100 105 Suc. Press. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press . Dis. T emp. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press . Dis. T emp . Liq. Press. Dis. T emp. Liq. ...

  • Nordyne R-410A - page 19

    19 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 018K O UT DO O R T EM PE RAT URE ( DEG . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Dis c h. S uc. Liquid Disc h. S uc. Liquid Disc h. S uc. Liquid Disc h. S uc . Liquid Dis c h. Suc . Liquid Disc h. S uc. Liquid Disc h. Pre ss Press. Temp . Pre ss. Pre ss. ...

  • Nordyne R-410A - page 20

    20 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 030K O UT DO O R T EM P ERAT URE ( DE G . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Disc h. Suc . Liquid Disc h. S uc. Liquid Disc h. Suc . Liquid Dis ch. Suc . Liquid Disc h. Suc . Liquid Disc h. Suc . Liquid Disc h. Pre ss Pre ss. Temp . Press. Pre ss. T ...

  • Nordyne R-410A - page 21

    21 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 042K O UT DO O R T EM P ERAT URE ( DE G . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Disc h. Suc . Liquid Disc h. Suc . Liquid Dis ch. Suc . Liquid Disc h. Suc . Liquid Dis ch. S uc. Liquid Disc h. Suc . Liquid Dis ch. Pre ss Pre ss. Temp . Press. Pre ss. T ...

  • Nordyne R-410A - page 22

    22 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 060K O UT DO O R T EM PE RAT URE ( DEG . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Dis ch. Suc . Liquid Disc h. Suc . Liquid Dis ch. S uc. Liquid Disc h. Suc . Liquid Dis ch. S uc. Liquid Disc h. Suc . Liquid Disc h. Pre ss Pre ss. Temp . Press. Pre ss. T ...

  • Nordyne R-410A - page 23

    23 ...

  • Nordyne R-410A - page 24

    INST ALLER: PLEASE LEA VE THESE INST ALLA TION INSTR UCTIONS WITH THE HOMEO WNER. 7084100 Specifi cations and illustrations subject to change without notice and without incurring obligations. Printed in U.S .A. (08/05) ¢708410p¤ 7084100 ...

メーカー Nordyne カテゴリー Electric Heater

Nordyne R-410Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- R-410Aの取扱説明書
- Nordyneの製品カード
- パンフレット
- またはNordyne R-410Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Nordyne R-410Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Nordyne R-410Aの取り付け説明書、サービスマニュアル、簡易説明書、またはNordyne R-410Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Nordyne R-410Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Nordyne R-410Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがNordyne R-410Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのNordyne R-410Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Nordyneの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Nordyne R-410Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははNordyne R-410Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Nordyne R-410Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Nordyne R-410Aデバイスの基本機能を使うにあたってのヒント。 Nordyne R-410Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Nordyne R-410Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるNordyne R-410Aのメーカー/サービスへの連絡先に関する情報。

Nordyne R-410Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもNordyne R-410Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがNordyne R-410Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)