Burnham BOILERSの取扱説明書

48ページ 1.74 mb
ダウンロード

ページに移動 of 48

Summary
  • Burnham BOILERS - page 1

    1 Price - $3.00 INST ALLA TION, OPERA TING AND SER VICE INSTRUCTIONS FOR RSA BOILERS ...

  • Burnham BOILERS - page 2

    2 The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life. DA NG ER Indicates an imm in ently h a zard o us si tuation w hi ch , if n o t a v o id e d , w il l r e su lt in d e a th , se ri ous i nj u ry or subs tant i al propert y ...

  • Burnham BOILERS - page 3

    3 DA NG ER DO N OT sto r e or use g aso li ne o r o ther fl am m able vapo r s o r l iq u ids in the v ic inity o f th is or any othe r app li anc e. WA R N I N G Imp ro p er install ati o n , adjustm en t, al teration , servic e o r m ainte n a nce can cause p r op er ty damage , persona l i nj ury or los s of li fe . Fai lur e t o fol l ow al l i ...

  • Burnham BOILERS - page 4

    4 WA R N I N G A ppli an ce mate r i al s o f c onstr uct i o n, pro duct s of co m bust i on and t h e f uel conta i n al u m i na, si l i ca , he av y me ta l s, ca rb on m on oxi de, ni t rog e n oxides , a l de h yd es a nd/ or ot h er tox ic or harm ful sub stan ces wh ich can cause d eat h o r seriou s inju ry and which ar e kn o wn to th e s ...

  • Burnham BOILERS - page 5

    5 T ables of Contents I. Pre-Installation ..................................... 7 II. Knockdown Boiler Assembly ............... 9 III. Water Piping and Trim ...................... 12 IV. Venting ............................................... 18 V. Electrical and Sequence of Operation 20 Figure 1: RSA Packaged Boiler (RSA85 / RSA135) VI. Oil Piping ...

  • Burnham BOILERS - page 6

    6 Figure 1A: RSA Packaged Boiler (RSA170 / RSA285) Bo il e r Mo d e l Nu m b e r B a r e B o ile r A sse m b l y Mi n i mu m C h i m n e y S i z e s Wa te r Capac i t y G a llo n s Ap p ro x. Sh ip p i ng We ig h t In . x In . x F t. (h ei gh t) In . ( d i a. ) x F t. (h ei gh t) RS A 1 70 WV -29- 10 8 x 8 x 20 7" x 2 0' 4 2. 6 6 00 l b. ...

  • Burnham BOILERS - page 7

    7 A . INSPECT SHIPMENT carefully for any signs of damage. 1. ALL EQUIPMENT is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of the crated boiler to the carrier in good condition. 2. ANY CLAIMS for damage or shortage of shipment must filed immediately against the carrier by the consignee. No claims for varianc ...

  • Burnham BOILERS - page 8

    8 C . PROVIDE AIR SUPPLY AND VENTILATION to accommodate proper combustion. If natural ventila- tion is inadequate, provide a screened opening or duct from the boiler room to the outside. The opening or duct must be sized so the boiler input will not exceed 4,000 BTUH/Sq. In. of free area. If other air consum- ing appliances are near the boiler, the ...

  • Burnham BOILERS - page 9

    9 II. Knock-Down Boiler Assembly H. INSTALLING THE JACKET 1. Before jacket can be secured to boiler assembly tankless heater coil or blank plate must be attached. Using rubber gasket and bolts provided secure heater coil or blank plate to boiler extension by inserting the bolts from the backside of the exten- sion. Refer to Figure 4. A . REMOVAL OF ...

  • Burnham BOILERS - page 10

    10 Figure 5: Burner Mounting ...

  • Burnham BOILERS - page 11

    11 Figure 6: RSA Jacket Assembly ...

  • Burnham BOILERS - page 12

    12 III. W ater Piping and T rim A. Design a piping system and install boiler which will prevent oxygen contamination of boiler water and frequent water additions. 1. There are many possible causes of oxygen contami- nation such as: a . Addition of excessive make-up water as a result of system leaks. b. Absorption through open tanks and fittings. c. ...

  • Burnham BOILERS - page 13

    13 Figure 7: Recommended Piping for Combination Heating and Cooling (Refrigeration) System B . Install Pressure Relief Valve. See Figures 8 and 9. Pressure Relief Valve must be installed with spindle in the vertical position. Installation of the relief valve must be consistent with ANSI/ASME Boiler and Pressure Vessel Code, Section IV. E . After th ...

  • Burnham BOILERS - page 14

    14 Figure 8: Recommended Boiler Piping for Circulator Zoned Heating Systems ...

  • Burnham BOILERS - page 15

    15 Figure 9: Boiler Piping for Zone Valve Zoned Heating Systems ...

  • Burnham BOILERS - page 16

    16 2. TEMPERING OF HOT WATER — Installation of an automatic mixing valve will lengthen the delivery of the available hot water by mixing some cold water with the hot. This prevents the possibil- ity of scalding hot water at the fixtures. In addition, savings of hot water will be achieved since the user will not waste as much hot water while seeki ...

  • Burnham BOILERS - page 17

    17 Figure 11: Schematic Tankless Heater Piping Table 1: Tankless Heater Ratings B oil e r Model S T D. #7524 OP T . #753 0 G PM PS I D G PM PS I D R SA 1 70 3 ¾ 25 ½ 4 26 ½ R SA 1 9 5, 2 4 0, & 2 85 4 29 4 ¼ 31 B oil er M odel S 350 S375 G PM P SID GPM P SID R S A( H ) 85 & 1 1 0 3 1 2 3½ 1 5 R SA1 1 0 ( H ) 1 25 & 1 3 5 3 ¼ 1 6 3 ...

  • Burnham BOILERS - page 18

    18 IV . V enting A . General Guidelines. 1. Vent system installation must be in accordance with these instructions and applicable provisions of local building codes. Contact local building or fire officials about restrictions and installation inspec- tion in your area. 2. The RSA Series is designed to be vented into a fireclay tile-lined masonry ch ...

  • Burnham BOILERS - page 19

    19 Figure 12: Recommended Smokepipe Arrangement and Chimney Requirements Figure 13: Draft Regulator Locations ...

  • Burnham BOILERS - page 20

    20 A . General 1. Install wiring and electrically ground boiler in accordance with requirements of the authority having jurisdiction, or in absence of such require- ments the National Electrical Code, ANSI/NFPA 70, and/or the CSA C22.1 Electric Code. 2. A separate electrical circuit should be run from the main electrical service with a fused discon ...

  • Burnham BOILERS - page 21

    21 Figure 14: “RSAL” Wiring Less Tankless, Single Circulator Figure 15: “RSAT” or “RSAR” Wiring with Tankless, Single Circulator ...

  • Burnham BOILERS - page 22

    22 Figure 16: Circulator Zoned Wiring for Honeywell R8888 ...

  • Burnham BOILERS - page 23

    23 Figure 17: Zone Valve Zoned Wiring for R8889 ...

  • Burnham BOILERS - page 24

    24 Figure 18: Different Manufacturer’s Zone Valve Connections to Honeywell R8889 ...

  • Burnham BOILERS - page 25

    25 NO T IC E The B urnham EC5 0 00 C ontrol i ncl udes a w a te r t emperat u re se nsor . Mount t hi s s ens or t o t he sy s t e m s upp l y pi pi ng. 8. Burnham EC5000 Circulator Zoned System – Refer to Figure 19 of this manual for the electrical diagram for this type of system. Wire the system as indicated in that diagram. Refer to the manual ...

  • Burnham BOILERS - page 26

    26 Figure 19: Circulator Zoning with EC5000 Wiring Schematic ...

  • Burnham BOILERS - page 27

    27 Figure 20: Zone Valve Zoned with EC5000 Wiring Schematic ...

  • Burnham BOILERS - page 28

    28 A . General. 1. Use flexible oil line(s) so that burner can be removed without disconnecting the oil supply. 2. A supply line fuel oil filter is recommended as a minimum for all firing rates but a pleated paper fuel oil filter is recommended for the lowest firing rate application to prevent nozzle fouling. 3. Use Flared fittings only. Do not use ...

  • Burnham BOILERS - page 29

    29 C . Two-Pipe Oil Lines 1. For two-piped systems, where more lift is required, the two-stage fuel unit is recommended. Table 2 (single-stage) and Table 3 (two-stage) show allowable lift and lengths of 3/8 inch and 1/2 inch OD tubing for both suction and return lines. Refer to Figure 22. Figure 22: Two-Pipe Installation T AB L E 2: S INGLE S T A G ...

  • Burnham BOILERS - page 30

    30 VII. System Start-Up A . Verify that the venting, water piping, oil piping, and electrical system are installed properly. Refer to installation instructions contained in this manual. B . Confirm all electrical, water and oil supplies are turned off at the source and that the vent is clear from obstructions. C . Fill entire heating system with wa ...

  • Burnham BOILERS - page 31

    31 SOLID stream without air bubbles for approxi- mately 10 seconds. 3. Close vent fitting and burner flame should start immediately. 4. If the burner does not start immediately, check the manual overload switch on the motor, if so equipped, and the safety switch on the burner primary control. K. ADJUST OIL PRESSURE 1. Locate oil pressure adjusting ...

  • Burnham BOILERS - page 32

    32 instrumentation to obtain a CO 2 of 11.5 to 12.5% with draft of -.02” w.c. in fire box. These settings will assure a safe and efficient operating condition. If the flame appears stringy instead of a solid flame, try another nozzle of the same type. Flame should be solid and compact. After all adjustments have been made, recheck for a draft of ...

  • Burnham BOILERS - page 33

    33 extreme case may become a fire hazard. d. AIR LEAKS— Any such leaks should be repaired, as they may cause erratic burning of the fuel and in extreme cases may become a fire hazard. There may be many possible causes of leaks in oil lines such as: i. Fitting leaks due to misflared tubing or damaged fitting. ii . Fuel line leak due to crushed or ...

  • Burnham BOILERS - page 34

    34 a. Simulate flame failure: • Follow the starting procedure to turn on the burner. • Close the hand valve in the oil supply line. • Safety switch should lock out in approxi- mately 15 seconds. Ignition should stop and oil valve should close. Blower will stop after postpurge period. • Push red reset button to reset safety switch. b. Simula ...

  • Burnham BOILERS - page 35

    35 INST ALLA TION INSTRUCTIONS FOR SHIELD REQUIRED FOR COMBUSTIBLE FLOOR This shield for combustible floors is intended for use only with the following Burnham oil-fired boilers: Use Part Number 6183504 for the following models: RSA(H)85 RSA(H)110 RSA(H)125 RSA(H)135 ADDS 4-3/16” TO BOILER HEIGHT Use Part Number 6183505 for the following models: ...

  • Burnham BOILERS - page 36

    36 VIII. Service and Cleaning A . General. Inspection service and cleaning should be conducted annually. Turn off electric power and close oil supply valve while conducting service or mainte- nance. B . Firetubes and Combustion Chamber. (See Figure 25) NO T IC E B U RN E R SH UT DO W N: O pe n Se r v i c e S witc h t o tu rn o ff b u r n er . Man u ...

  • Burnham BOILERS - page 37

    37 IX. Repair Parts All RSA Repair Parts may be obtained through your local Burnham Wholesale distributor . Should you require assistance in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact your Burnham Regional Sales Office as listed below . Bur nha m C or ...

  • Burnham BOILERS - page 38

    38 NOTE: When ordering parts always give the serial number and model number shown on the boiler. Also provide the name of the part(s) shown below: Figure 26: RSA85-135 Bare Boiler Repair Parts REPAIR PARTS ...

  • Burnham BOILERS - page 39

    39 BO I LE R M O D EL 'A ' 'B ' R S A 85 12 6033501 12 R S A 1 10 16 6033501 16 R S A 125 12 603350212 R S A 135 16 603350216 IT E M N O. QT Y . DE SC RIP T IO N P A RT N O. 1 2 W ing N ut, 1/4 - 20 80860910 2 10 Wa s her , Flat 1/4 (SAE ) 80860633 3 1 C anopy A s sembl y 61 13509 4 2 1/2" Thic k x 1 " x 12-3/8" C ...

  • Burnham BOILERS - page 40

    40 Figure 27: RSA170-285 Boiler Repair Parts NOTE: When ordering parts always give the serial number and model number shown on the boiler. Also provide the name of the part(s) shown below: ...

  • Burnham BOILERS - page 41

    41 B oi ler Model 'A ' 'B' R S A 170 10 6306332 R S A 195 13 6306329 R S A 240 16 6306309 R S A 285 19 6306310 I TEM N O . D ESC R I PTION P AR T N O. 1 J ac k e t T op P a n el A s se m bl y 60435022 2 C an o py A s se m bl y 61 13510 3 ½" T h ic k x 1" x 2 3" C er af el t S tr ip 9206005 4 ½" T h ic k x 1 ...

  • Burnham BOILERS - page 42

    42 I TE M D ESCR I PT I O N P ART NUM BER 1 Jac ket T op P anel 604 3508 6 2 Jac ket W rap -A- Roun d P anel , R SA 85/ 1 1 0 604 3508 7 J ack et W ra p-A -Ro und P a nel , RS A125/ 13 5 604 3508 8 3 T em per atu re / P r es sur e G aug e 80 5616 9U 4 Ho neywe l l L8 148A 10 90 Hi -Li m i t Co nt rol 801 6044 9U Hon eywel l L812 4C1 1 02 Li mit Co ...

  • Burnham BOILERS - page 43

    43 SER VICE SCHEDULE DA TE SER VICE PERFORMED ...

  • Burnham BOILERS - page 44

    44 BECKETT BURNER PARTS LIST FOR RSA SERIES STEEL BOILERS FOR REPLACEMENT OIL BURNER PARTS, CONTACT YOUR WHOLESALER OR THE BURNER MANUFACTURER: R. W . BECKETT CORP . 38251 CENTER RIDGE RD. P . O. BOX 1289 EL YRIA, OHIO 44036 1-800-645-2876 NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Also, provi ...

  • Burnham BOILERS - page 45

    45 Ordering Information for Quality Replacement Parts Figure 29: BECKETT AFG MODEL BURNER ...

  • Burnham BOILERS - page 46

    46 BECKETT BURNER PARTS LIST FOR RSA SERIES STEEL BOILERS FOR REPLACEMENT OIL BURNER PARTS, CONTACT YOUR WHOLESALER OR THE BURNER MANU- FACTURER: R. W . BECKETT CORP . 38251 CENTER RIDGE RD. P . O. BOX 1289 EL YRIA, OHIO 44036 1-800-645-2876 B oil er M odel R S A 170 RSA19 5 RSA2 40/285 Bu rn e r M od el A F A F A F A i r T ube C ombi nati on A F 6 ...

  • Burnham BOILERS - page 47

    47 Ordering Information for Quality Replacement Parts Figure 30: BECKETT AF and SF MODEL BURNERS ...

  • Burnham BOILERS - page 48

    48 ...

メーカー Burnham カテゴリー Boiler

Burnham BOILERSのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- BOILERSの取扱説明書
- Burnhamの製品カード
- パンフレット
- またはBurnham BOILERSの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Burnham BOILERSの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Burnham BOILERSの取り付け説明書、サービスマニュアル、簡易説明書、またはBurnham BOILERSのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Burnham BOILERSの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Burnham BOILERSデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBurnham BOILERSを使用するのを助ける技術的文書のことです。説明書は通常、全てのBurnham BOILERSユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Burnhamの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Burnham BOILERSの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBurnham BOILERSの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Burnham BOILERSに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Burnham BOILERSデバイスの基本機能を使うにあたってのヒント。 Burnham BOILERSのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Burnham BOILERSに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBurnham BOILERSのメーカー/サービスへの連絡先に関する情報。

Burnham BOILERSについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBurnham BOILERSの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBurnham BOILERSで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)