    SIMA TIC NET S7-CPs for Industrial Ethernet Manual Part B3L CP 343-1 Lean 6GK7 343 − 1CX10 − 0XE0 as of hardware version 2, as of firmware version V2.0 for SIMA TIC S7 − 300 / C7 − 300 Release 03/2007 C79000-G8976-C198-04 TP port: 2 x 8 − pin RJ − 45 socket (beneath the front panel) LED displays X = Placeholder for hardware version ...

  • Siemens CP 343-1 - page 2

    Notes on the Product B3L − 2 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Notes on the Product Product Names This description contains information on the following product S CP 343 − 1 Lean Order number 6GK7 343 − 1CX10 − 0XE0 as of hardware version 2 and firmware version V2.0 for SIMA TIC S7 ...

  • Siemens CP 343-1 - page 3

    Contents B3L − 3 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Contents Contents − Part A Ethernet CPs − General information see general part . . . . . . . . . . . . . . . . . . . Note Please remember that Part A of the device manual also belongs to the description of the CP . Among other things, ...

  • Siemens CP 343-1 - page 4

    Contents B3L − 4 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.4.2 Initialization and Configuration B3L − 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5 Example of Configuration and Programming B3L − 30 . . . . . . . . . . . . . . . . . . . . . 7 Web Diagnostics B3L ? ...

  • Siemens CP 343-1 - page 5

    1 Properties / Services B3L − 5 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 1 Properties / Services Application The CP 343 − 1 Lean communications processor is designed for operation in a SIMA TIC S7-300 programmable logic controller . It allows attachment of the S7 − 300 to Industrial Ethernet ...

  • Siemens CP 343-1 - page 6

    1 Properties / Services B3L − 6 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 S T ime-of-day synchronization over Industrial Ethernet using the following configurable modes: − SIMA TIC mode The CP receives MMS time frames and synchronizes its local time and the time of the CPU (accuracy approx. +/ ...

  • Siemens CP 343-1 - page 7

    1 Properties / Services B3L − 7 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Configuration It is possible to download the configuration data to the CP over MPI or LAN/Industrial Ethernet. Y ou require STEP 7 with NCM S7 for Industrial Ethernet (NCM IE) with the following version: T able 1-1 V ersion ...

  • Siemens CP 343-1 - page 8

    2 Requirements for Use B3L − 8 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 2 Requirements for Use General Operation The CP can be operated in the following device families: S S7 − 300 stations with the CPU types − Standard − Compact − Modular S C7 control systems in C7 packaging system The ...

  • Siemens CP 343-1 - page 9

    2 Requirements for Use B3L − 9 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T able 2-1 Use of the CP with S7 − 300 CPU Order Number CPU 314 IFM 6ES7 314 − 5AE03 − 0AB0 6ES7 314 − 5AE10 − 0AB0 CPU 314C − 2 DP 6ES7 314 − 6CF00 − 0AB0 6ES7 314 − 6CF02 − 0AB0 6ES7 314 − 6CG03 − 0 ...

  • Siemens CP 343-1 - page 10

    2 Requirements for Use B3L − 10 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T able 2-2 Use of the CP in C7 Control Systems C7 Order Number C7 − 613 6ES7 613 − 1CA01 − 0AE03 6ES7 613 − 1CA02 − 0AE3 C7 − 633 DP 6ES7 633 − 2BF02 − 0AE03 C7 − 635 Keys 6ES7 635 − 2EC01 − 0AE3 6ES7 ...

  • Siemens CP 343-1 - page 11

    3 Installation and Commissioning B3L − 11 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 3 Installation and Commissioning 3.1 Procedure / Steps Step Explanation / Meaning 1. Install the CP on the S7 standard rail. 2. Establish the connection via the enclosed bus connector to the backplane bus. Slots 4 ...

  • Siemens CP 343-1 - page 12

    3 Installation and Commissioning B3L − 12 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Slider for setting the chassis ground contact Attachment to Industrial Ethernet: 2 x 8-pin RJ-45 jack Figure 3-1 Connectors of a CP 343 − 1 Lean with the Front Panel Open Ground/Chassis Ground Concept Notice Ple ...

  • Siemens CP 343-1 - page 13

    3 Installation and Commissioning B3L − 13 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Note The hinged front panel must be kept closed during operation. The module must be installed so that its upper and lower ventilation slits are not covered, allowing adequate ventilation. ! W arning When used und ...

  • Siemens CP 343-1 - page 14

    4 Displays B3L − 14 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 4 Displays The display on the front panel consists of 8 LEDs that indicate the operating mode and the communication status. Front panel: SF BF RX/TX RUN STOP P1 P2 DC5V The LEDs have the following meaning: S SF: Group error S BF: Bus f ...

  • Siemens CP 343-1 - page 15

    4 Displays B3L − 15 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 LEDs for displaying the mode The different combinations of the LEDs on the front panel indicate the status: SF(red) BF (red) RUN (green) STOP (yellow) CP Operating Mode − S Starting up afte r power “ON” or S Stopped (STOP) with e ...

  • Siemens CP 343-1 - page 16

    4 Displays B3L − 16 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 LEDs for displaying the CP communication status In addition to the LEDs that signal the CP state, the following LEDs provide information about the status of the CP interface to Industrial Ethernet. T able 4-1 LED Display Meaning RX/TX ...

  • Siemens CP 343-1 - page 17

    5 Performance Data B3L − 17 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 5 Performance Data 5.1 Number of Poss ible Connections over Ethernet T able 5-1 Characteristic Explanation / V alues Permitted number of simultaneous connections in total over Industrial Ethernet 12 maximum Example of Maximum L ...

  • Siemens CP 343-1 - page 18

    5 Performance Data B3L − 18 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 5.3 Characteristics of the SEND/RECEIVE Interface T able 5-3 Characteristic Explanation / V alues Number of ISO-on-TCP connections + TCP connections + UDP connections in total 8 maximum Notes: S All UDP connections are also pos ...

  • Siemens CP 343-1 - page 19

    5 Performance Data B3L − 19 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 5.4 Characteristic Data for PROFINET IO CP as PROFINET IO device The CP supports the following maximum configuration as a PROFINET IO device: T able 5-5 Characteristic Explanation / V alues Size of the input area of the PROFINE ...

  • Siemens CP 343-1 - page 20

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 20 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6 Configuring and Programming the CP as a PROFINET IO Device “Intelligent” PROFINET IO Device A CP 343 − 1 Lean can be configured so that the SIMA TIC 300 station can be addressed ...

  • Siemens CP 343-1 - page 21

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 21 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.2 Principle of Data Exchange over PROFINET IO Data Exchange between controller and CP as PROFINET IO device Data exchange between a PROFINET IO controller and PROFINET IO device invol ...

  • Siemens CP 343-1 - page 22

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 22 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.3 Configuration Configuring the CP as a PROFINET IO device involves the two following activities in STEP 7: 1. The CP is inserted in a SIMA TIC 300 station in HW Config and enabled fo ...

  • Siemens CP 343-1 - page 23

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 23 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 2. Check and, if necessary , correct the IP address in the “Properties Ethernet” dialog. Notice The IP address of the PROFINET IO device and the IP address of the PROFINET IO contro ...

  • Siemens CP 343-1 - page 24

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 24 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.3.2 Assigning the PROFINET IO Device to a PROFINET IO Controller PROFINET IO Controller This section describes the configuration of PROFINET IO controllers with STEP 7. This includes: ...

  • Siemens CP 343-1 - page 25

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 25 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Result: Y ou will see the connector symbol for the PROFINET IO system beside the PROFINET IO controller . Step 2: Configuring the PROFINET IO device on the PROFINET IO controller 1. Ope ...

  • Siemens CP 343-1 - page 26

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 26 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Step 3: Configuring the properties of the CP as PROFINET IO device Continue configuration in HW Config as follows: 1. Open the properties dialog of the PROFINET IO device that you inser ...

  • Siemens CP 343-1 - page 27

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 27 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 No further parameter assignment of the modules is necessary . Note By selecting suitable network components and setting the network properties (Section 9.2) make sure that in PROFINET I ...

  • Siemens CP 343-1 - page 28

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 28 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Data consistency The length information in the block call must be identical to the total length of the input or output data configured for this PROFINET IO device. The entire input or o ...

  • Siemens CP 343-1 - page 29

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 29 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Reasons for reinitialization The PROFINET IO device requests reinitialization by the user program in the following situations: S The length information of the input and output areas in ...

  • Siemens CP 343-1 - page 30

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 30 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.5 Example of Configuration and Programming The configured input/output modules must be accessed in the user program of the PROFINET IO device using FCs. The FCs provide the process da ...

  • Siemens CP 343-1 - page 31

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 31 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T ransfer the process inputs (DB10) to the I addresses with PNIO_SEND For the configured I addresses, you will need to make data areas available on the PROFINET IO device, for example i ...

  • Siemens CP 343-1 - page 32

    6 Configuring and Programming the CP as a PROFINET IO Device B3L − 32 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T ransfer the O addresses to the process outputs (DB1 1) with PNIO_RECV For the configured O addresses, you will need to make data areas available on the PROFINET IO device, for example ...

  • Siemens CP 343-1 - page 33

    7 Web Diagnostics B3L − 33 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7 Web Diagnostics With W eb diagnostics, the CP provides you with the option of calling up the most important settings of a connected station and the status of their network connections and communication partners from an HTTP cl ...

  • Siemens CP 343-1 - page 34

    7 Web Diagnostics B3L − 34 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 3. Select the display language you require from the “Language” drop-down list box at the top right. The following languages are available: S English S Deutsch S Français S Español S Italiano 4. Y ou open the other pages us ...

  • Siemens CP 343-1 - page 35

    7 Web Diagnostics B3L − 35 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.1 Start Page This page displays general device data and the status of the connected CP . Parameter Function General Station name Configured name of the station in which the CP is installed. Module name Configured name of the ...

  • Siemens CP 343-1 - page 36

    7 Web Diagnostics B3L − 36 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.2 Identification Here, you can see a variety of information on the CP for identification and maintenance. Parameter Function Identification Plant designation 1) Plant designation of the CP if this was configured. Location id ...

  • Siemens CP 343-1 - page 37

    7 Web Diagnostics B3L − 37 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.3 Rack Configuration The slots of the station and general data along with the status of the devices is displayed here. Parameter Function Rack Configuration (rack name) Slot Slot of the individual modules in the rack Status ...

  • Siemens CP 343-1 - page 38

    7 Web Diagnostics B3L − 38 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Parameter Function V ersion Firmware version of the module LED Status LED display of the module: S Gray (inactive LED, the LED is off) S Colored (active LED, the LED is lit) The number of type of the LEDs depends on the particul ...

  • Siemens CP 343-1 - page 39

    7 Web Diagnostics B3L − 39 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.4 Diagnostic Buffer This table lists all the events in the chronological order in which they were received. The latest entry is at the start and the oldest entry at the end of the table. By clicking on the various tabs above ...

  • Siemens CP 343-1 - page 40

    7 Web Diagnostics B3L − 40 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.5 Industrial Ethernet “Parameters” T ab This page shows you the various parameters of the MAC address, the IP address and the LAN attachments. Parameter Function Network attachment MAC address (active) Active MAC address ...

  • Siemens CP 343-1 - page 41

    7 Web Diagnostics B3L − 41 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 “Statistics” T ab This page displays information on sent and received frames since the last module restart. Parameter Function Data packets sent Number of error-free frames sent, number of unicast, multicast and broadcast fr ...

  • Siemens CP 343-1 - page 42

    7 Web Diagnostics B3L − 42 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.6 PROFINET IO This page provides you with information on the most important parameters of the PROFINET IO configuration. Parameters of a PROFINET IO Device Parameter Function PROFINET IO Configuration Mode PROFINET IO mode o ...

  • Siemens CP 343-1 - page 43

    7 Web Diagnostics B3L − 43 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Parameter Function Status Status of the device: S OK (problem-free operation) S No connection to PROFINET IO controller (connection disrupted or broken down) S PROFINET IO blocks are not called correctly (the blocks are not call ...

  • Siemens CP 343-1 - page 44

    8 Compatibility with Predecessor Products B3L − 44 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 8 Compatibility with Predecessor Products 8.1 Extended Functionality New: Enhanced functions compared with module 6GK7 343 − 1CX10 − 0XE0 with firmware version V1.0 The following properties, services ...

  • Siemens CP 343-1 - page 45

    8 Compatibility with Predecessor Products B3L − 45 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Module Replacement When replacing an older module with the module described here, keep to the steps outlined below: T able 8-1 Originally configured module Configuration Steps 6GK7 343 − 1CX00 − 0XE0 ...

  • Siemens CP 343-1 - page 46

    9 Further Notes on Operation B3L − 46 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 9 Further Notes on Operation 9.1 Memory Reset A vailable Functions The CP has a two-level function available for resetting memory: S Clear / reset Following this memory reset, the CP retains the preset MAC address and ...

  • Siemens CP 343-1 - page 47

    9 Further Notes on Operation B3L − 47 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Behavior after Memory Reset The CPU in the S7 station does not recognize that the CP memory was reset. The CP therefore changes to the “stopped with error” state (see Chapter 4). The configuration data must then b ...

  • Siemens CP 343-1 - page 48

    9 Further Notes on Operation B3L − 48 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Automatic Setting or Individual Network Settings As default, the CP is configured for automatic detection (autosensing). As soon as you define a configuration manually when configuring the CP with STEP 7/HW Config (in ...

  • Siemens CP 343-1 - page 49

    9 Further Notes on Operation B3L − 49 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 S Recommendation: Change “individual network settings” only over MPI. If you modify the LAN settings in the properties dialog of the CP in the “Port Parameters” tab, these changes will be adopted by the CP and ...

  • Siemens CP 343-1 - page 50

    9 Further Notes on Operation B3L − 50 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Access Permissions using Community Name The CP uses the following community names for assigning permissions: S For read access: “public” S for read and write access: “private” (note the use of lower − case l ...

  • Siemens CP 343-1 - page 51

    9 Further Notes on Operation B3L − 51 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 S The connections on which a job on the communication bus with a data length > 240 bytes is being processed are aborted temporarily . S FETCH/WRITE connections are temporarily aborted. On the FC interface in the us ...

  • Siemens CP 343-1 - page 52

    9 Further Notes on Operation B3L − 52 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 9.8 Restart after Detection of a Duplicate IP Address in the Network T o save you time-consuming troubleshooting in the network, the CP detects double addressing in the network. When you eliminate the cause by removin ...

  • Siemens CP 343-1 - page 53

    10 How to Load New Firmware B3L − 53 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 10 How to Load New Firmware Requirements Y ou download new firmware to a SIMA TIC NET CP using the firmware loader shipped with STEP 7 / NCM S7. Requirements for Downloading S T o download firmware, you require an Indu ...

  • Siemens CP 343-1 - page 54

    1 1 T echnical Specifications B3L − 54 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 1 1 T echnical Specifications Transmission rate 10 Mbps and 100 Mbps Interfaces Connection to Ethernet 2 x RJ − 45 jack Power supply DC +24 V (permitted range: +20.4 V through +28.8 V) Current consumption S from ba ...

  • Siemens CP 343-1 - page 55

    1 1 T echnical Specifications B3L − 55 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Notice The approvals printed on the purchased device apply . In addition to this, all the information in the S7 − 300 reference manual “Module Data” /1/ in the chapter “General T echnical Specifications” ap ...

  • Siemens CP 343-1 - page 56

    1 1 T echnical Specifications B3L − 56 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 ...

メーカー Siemens カテゴリー Switch

Siemens CP 343-1のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- CP 343-1の取扱説明書
- Siemensの製品カード
- パンフレット
- またはSiemens CP 343-1の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Siemens CP 343-1の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Siemens CP 343-1の取り付け説明書、サービスマニュアル、簡易説明書、またはSiemens CP 343-1のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Siemens CP 343-1の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Siemens CP 343-1デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがSiemens CP 343-1を使用するのを助ける技術的文書のことです。説明書は通常、全てのSiemens CP 343-1ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Siemensの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Siemens CP 343-1の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははSiemens CP 343-1の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Siemens CP 343-1に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Siemens CP 343-1デバイスの基本機能を使うにあたってのヒント。 Siemens CP 343-1のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Siemens CP 343-1に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問