Summary
  • Cornelius CH1500-CH7500 - page 1

    CHILLER Models: CH1500–CH7500 Operator ’ s Manual with Installation, Service, and Parts PRINTED IN U.S.A IMI CORNELIUS INC; 2006 © IMI CORNELIUS INC T elephone (800) 551–4423 Fax (800) 394–5140 Part No. 91961OPR September 12, 2006 Revised: N/A Revision: A THIS DOCUMENT CONT AINS IMPORT ANT INFORMA TION This Manual must be read and understo ...

  • Cornelius CH1500-CH7500 - page 2

    i 91961OPR T ABLE OF CONTENTS Page GENERAL INFORMA TION 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INTRODUCTION 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SPECIFICATION NOTES 1 . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Cornelius CH1500-CH7500 - page 3

    ii 91961OPR T ABLE OF CONTENTS (cont’d) Page LIST OF FIGURES FIGURE 1. INST ALLA TION DET AILS 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FIGURE 2. CHILLER PLUMBING SCHEMA TIC WITH PUMP AND T ANK (ST ANDARD) 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Cornelius CH1500-CH7500 - page 4

    1 91961OPR GENERAL INFORMA TION INTRODUCTION Remcor “CH” Series Refrigerated Recirculating W ater Chillers are designed to provide a continuous flow of clean cooling water at a constant temperature and to handle a variety of closed loop and tank cooling applica- tions. The CH consists of a refrigeration system with associated operating controls ...

  • Cornelius CH1500-CH7500 - page 5

    2 91961OPR INST ALLA TION LOCA TION Install the Chiller indoors in a well ventilated area where ambient temperatures will never fall below 40  F or rise above 1 10  F . T o obtain optimum cooling capacity , the ambient temperature should be 80  F or below . Standard CH Chiller have air-cooled condensers. On air-cooled units it is important ...

  • Cornelius CH1500-CH7500 - page 6

    3 91961OPR ELECTRICAL All wiring must conform to the National Electric Code and any applicable local codes. The Chiller must be PERMANENTL Y wired by means of electrical conduit to a properly fused disconnect of proper amperage or wired to a properly rated power cord and plugged into an outlet with the appropriate disconnect and amperage rating. Th ...

  • Cornelius CH1500-CH7500 - page 7

    4 91961OPR Chiller with Reservoir The reservoir can be filled by removing the water fill cap located on the upper rear of the Chiller (See Fluid Rec- ommendations page). After ensuring that the drain valve is closed, fill the reservoir via the full port with clean water until the water level sight glass on the front of the unit indicates “FULL” ...

  • Cornelius CH1500-CH7500 - page 8

    5 91961OPR RESER VOIR LOW TEMP . CONTROL FROM PROCESS CHILLER INLET EV APORA T OR PUMP BYP ASS V AL VE CHILLER OUTLET T O PROCESS FIGURE 2. CHILLER PLUMBING SCHEMA TIC WITH PUMP AND T ANK (ST ANDARD) CHILLER INLET FROM PROCESS EV APORA T OR LOW TEMP . CONTROL CHILLER OUTLET T O PROCESS FIGURE 3. CHILLER PLUMBING SCHEMA TIC NO T ANK (OPTION) CHILLER ...

  • Cornelius CH1500-CH7500 - page 9

    6 91961OPR THIS P AGE LEFT BLANK INTENTIONALL Y ...

  • Cornelius CH1500-CH7500 - page 10

    7 91961OPR ST ART UP W A T ER FLOW ST A RT -UP Chiller with Pump It is important to check the pump rotation on the three phase units. Remove the lower side panel to expose the pump. T urn the pump power switch to the “ON” position for a few seconds. Observe the motor shaft to ensure that it is turning in the direction indicated by the arrow loc ...

  • Cornelius CH1500-CH7500 - page 11

    8 91961OPR Dual Point Adjustment 1. T o set the “SET POINT” for Level 1. Press and release the “SET” button, Re1 should be displayed. 2. Press the “SET” button, the current SET POINT TEMPERA TURE should be displayed. Press the UP or DOWN button to change the SET POINT . 3. T o set the “SET POINT” for Level 2. Press and release the ? ...

  • Cornelius CH1500-CH7500 - page 12

    9 91961OPR 3. CONTROL POWER LIGHT - A white light that indicates that Chiller control power is present. 4. COOLING LIGHT - A green light that indicates refrigeration system operation. This light cycles on and of f in response to the thermostat. 5. HIGH PRESSURE ALARM LIGHT - A red light that indicates high refrigeration pressure. 6. LOW PRESSURE AL ...

  • Cornelius CH1500-CH7500 - page 13

    10 91961OPR MAINTENANCE CAUTION: Disconnect electrical power before performing any of the following maintenance procedures. The Chiller will require very little normal maintenance. 1. On AIR-COOLED Chillers, the condenser fins should be cleaned by blowing compressed air through the condenser from the fan side as required to eliminate any dirt or de ...

  • Cornelius CH1500-CH7500 - page 14

    11 91961OPR FLUID RECOMMENDA TION Chillers are designed to operate with water to provide maximum performance for tempera- tures of 40  F–100  F. Distilled W ater Acceptable De–Ionized W ater (1–5 MEG/OHMS) Acceptable De–Ionized W ater (5+MEG/OHMS) Acceptable with Stainless Steel & PVC only *No Copper or Brass Propylene Glycol (Lab ...

  • Cornelius CH1500-CH7500 - page 15

    12 91961OPR W ARNING: If repairs are to be made to the refrigeration system, make sure electrical power is disconnected from the unit. TROUBLESHOOTING IMPORTANT : Only qualified personnel should service internal components or electrical wiring. T rouble Probable Cause Remedy CHILLER DOES NOT OPERA TE. CONTROL POWER LIGHT “OFF” A. Control power ...

  • Cornelius CH1500-CH7500 - page 16

    13 91961OPR T rouble Remedy Probable Cause D. Refrigerant loss. D. Check the sight glass. If bubbles are seen flowing through it, the Chiller needs to be leak checked and recharged with refrigerant. E. W ater bypass valve failed. E. Consult technical service department. F . Defective pump. F . Replace pump. HIGH PRESSURE ALARM LIGHT “ON”. A. Re ...

  • Cornelius CH1500-CH7500 - page 17

    14 91961OPR SER VICE When servicing a Chiller , it is important to note the information contained on the data plate located in the upper rear of the unit. If technical assistance is needed, the phone technician will need the Serial Number of your Chiller . That informa- tion is found on the Data Plate along with the model number , voltage requireme ...

  • Cornelius CH1500-CH7500 - page 18

    15 91961OPR THIS P AGE LEFT BLANK INTENTIONALL Y ...

  • Cornelius CH1500-CH7500 - page 19

    16 91961OPR SAFETY CONTROLS Each Chiller is provided with three standard safety controls. These controls are arranged in series in the control circuit to automatically shut down the unit in the event that a condition exists which could be harmful to the re- frigeration system components. This section includes a brief description of each control, it ...

  • Cornelius CH1500-CH7500 - page 20

    17 91961OPR TXV EQUALIZER LINE TXV SENSING BULB TXV EV APORA T OR LIQUID LINE SOL. V AL VE HOT GAS BYP ASS VA LV E COMPRESSOR LOW PRESSURE SWITCH HIGH PRESSURE SWITCH SIGHT GLASS FIL TER/DRIER LIQUID RECEIVER CONDENSER FIGURE 6. REFRIGERA TION PIPING SCHEMA TIC WITH HOT GAS BYP ASS TXV EQUALIZER LINE TXV SENSING BULB TXV EV APORA T OR COMPRESSOR LO ...

  • Cornelius CH1500-CH7500 - page 21

    18 91961OPR P ARTS LIST 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 4 10 FIGURE 8. CHILLER P ARTS BREAKDOWN Index No. Description 1 1/2” FPT Coupling 2 Thermowell, Low T emp. Thermostat (Not Shown) 3 Corner Cover 4 Side Panel 5 Rear Panel 6 Upper Front Panel 7 Lower Front Panel 8 Lid 9 Control Panel 10 FPT Coupling 1 1 T em ...

  • Cornelius CH1500-CH7500 - page 22

    19 91961OPR 1 2 3 4 5 FIGURE 9. PUMP AND T ANK COMPONENTS Index No. Description 1 Thermowell, T emperature Control 2 T emperature Probe 3 T ank Assembly Index No. Description 4 Pump 5 Pump Relief V alve ** Call the Service Department for proper pump identification. ...

  • Cornelius CH1500-CH7500 - page 23

    20 91961OPR 1 2 3 4 5 6 7 FIGURE 10. ELECTRICAL BOX COMPONENTS Index No. Description 1 Lo w T emperature Thermostat 2 Control T ransformer 3 Contactor , Compressor 4 High pressure Control 5 Low Pressure Control Index No. Description 6 Contactor , Pump 7 Overload Relay , 1.0 to 1.6A Overload Relay , 1.4 to 2.0A Overload Relay , 2.0 to 3.0A Overload ...

  • Cornelius CH1500-CH7500 - page 24

    21 91961OPR W ARRANTY IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship un- der normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or W ilshire prod- uct, in your country , please write, fax or telephone the IMI Cornelius office nearest you. Please provide ...

  • Cornelius CH1500-CH7500 - page 25

    ...

  • Cornelius CH1500-CH7500 - page 26

    IMI CORNELIUS INC. www .cornelius.com ...

メーカー Cornelius カテゴリー Refrigerator

Cornelius CH1500-CH7500のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- CH1500-CH7500の取扱説明書
- Corneliusの製品カード
- パンフレット
- またはCornelius CH1500-CH7500の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Cornelius CH1500-CH7500の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Cornelius CH1500-CH7500の取り付け説明書、サービスマニュアル、簡易説明書、またはCornelius CH1500-CH7500のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Cornelius CH1500-CH7500の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Cornelius CH1500-CH7500デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCornelius CH1500-CH7500を使用するのを助ける技術的文書のことです。説明書は通常、全てのCornelius CH1500-CH7500ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Corneliusの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Cornelius CH1500-CH7500の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCornelius CH1500-CH7500の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Cornelius CH1500-CH7500に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Cornelius CH1500-CH7500デバイスの基本機能を使うにあたってのヒント。 Cornelius CH1500-CH7500のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Cornelius CH1500-CH7500に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き