    PRODUCT DA T A ® U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • All Rights Reserved D896 Automatic V ent Damper GENERAL D896 Automatic V ent Dampers are used with atmospheric type, gas-fired equipment to reduce home heating losses b y closing off the vent betw een heat cycles. FEA TURES • 4-wire plug receptac le. • Includes wir ...

  • Honeywell D896 - page 2

    D896 A UT OMA TIC VENT D AMPER 68-0186 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distr ibutor , ref er to the TRADELINE® Catalog or price sheets for complete ordering number . If you ha ve additional questions, need further information, or would like to comment on our product ...

  • Honeywell D896 - page 3

    D896 A UT OMA TIC VENT D AMPER 68-0186 3 NO TE: A minimum of a 30 V A transf or mer must be used when D896 is installed with S86/S8600/S8610/ S8620. Electrical Connections: F our-wire plug receptacle. Thermostat Anticipator Setting: 0.13A. Operating Times: Appro ximate Damper Opening Time: 30 seconds. Appro ximate Damper Closing Time: 30 seconds. T ...

  • Honeywell D896 - page 4

    D896 A UT OMA TIC VENT D AMPER 68-0186 4 IMPORT ANT 1. The atmospheric draft hood outlet area must be smaller or equal to the inlet area of the damper assembly . 2. If a second gas valv e needs to be installed, refer to the gas valv e manufacturer instructions f or the procedure. 3. Using a dual automatic valv e combination gas control or two separ ...

  • Honeywell D896 - page 5

    D896 A UT OMA TIC VENT D AMPER 68-0186 5 Fig. 3. Installing D896 V ent Damper . IMPORT ANT Ne ver mount the vent damper with the motor actuator abov e or below the vent. Do not install the damper blade plug if the v ent damper is installed on a system with a continuous or standing pilot. The hole provides the minimum v ent area required by code f o ...

  • Honeywell D896 - page 6

    D896 A UT OMA TIC VENT D AMPER 68-0186 6 Fig. 5. D896 with co ver off. Honeywell D892/D896 Wires Honeywell D80B Wires Johnson Q35 Wires EFFIKAL RVG Wires Yellow Orange Green 1 Orange Blue and Red White 2 Blue Black Red 3 Black Yellow Black 4 NORM SERV SERVICE SWITCH HARNESS CABLE CONNECTOR IGNITION GAS PWR LED CALL FOR HEA T LED S3 SWITCH RELA Y 1K ...

  • Honeywell D896 - page 7

    D896 A UT OMA TIC VENT D AMPER 68-0186 7 MV MV/PV PV GND (BURNER) 24V GND 24V SPARK S8600F, H, M; S8610F,H POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS REMOVED; THEN MODULE OPERATES ONLY WHEN VENT DAMPER IS CONNECTED. 1 1 M11375 SENSE TH-W VENT ...

  • Honeywell D896 - page 8

    D896 A UT OMA TIC VENT D AMPER 68-0186 8 Fig. 10. Snap-Tite™ Bo x Connector release. Checkout Heating 1. Tu rn on the po wer supply . 2. If using a thermostat, set the heat anticipator at 0.13A. 3. Set the thermostat or controller to 10 ° F (6 ° C) above the room temperature to call f or heat. 4. Check that the D896 CALL FOR HEA T and IGNITION ...

  • Honeywell D896 - page 9

    D896 A UT OMA TIC VENT D AMPER 68-0186 9 Thermostat Setting Symptom Possible Cause Action Set thermostat 10°F above room temperature to call for heat. No response from D896. Incorrect wiring or blown fuse. • Check the circuit breaker or fuse and, if necessary, reset or replace. • Check the transformer and limit control. • Check for 24 Vac ac ...

  • Honeywell D896 - page 10

    D896 A UT OMA TIC VENT D AMPER 68-0186 10 ANSI ST ANDARDS EXHIBIT A Procedure For Saf ety Inspection of an Existing Appliance Installation The f ollowing procedure is intended as a guide to aid in determining that an appliance is proper ly installed and is in a safe condition f or continuing use. This procedure is predicated on central furnace, boi ...

  • Honeywell D896 - page 11

    D896 A UT OMA TIC VENT D AMPER 68-0186 11 EXHIBIT B Procedure f or Installing Electrically Operated Automatic Vent Damper De vices on Existing Appliances This procedure is intended as a guide to aid in safely installing an electrically operated or mechanically actuated automatic vent damper de vice on an existing appliance . This procedure is based ...

  • Honeywell D896 - page 12

    D896 A UT OMA TIC VENT D AMPER 68-0186 12 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc. Room 3213-3225 Sun Hung Kai Centre No. 30 Harbour Road Wanchai Hong Kong Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 2C9 Honeywell Latin American Div ...

メーカー Honeywell カテゴリー Ventilation Hood

Honeywell D896のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- D896の取扱説明書
- Honeywellの製品カード
- パンフレット
- またはHoneywell D896の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Honeywell D896の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Honeywell D896の取り付け説明書、サービスマニュアル、簡易説明書、またはHoneywell D896のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Honeywell D896の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Honeywell D896デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがHoneywell D896を使用するのを助ける技術的文書のことです。説明書は通常、全てのHoneywell D896ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Honeywellの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Honeywell D896の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははHoneywell D896の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Honeywell D896に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Honeywell D896デバイスの基本機能を使うにあたってのヒント。 Honeywell D896のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Honeywell D896に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるHoneywell D896のメーカー/サービスへの連絡先に関する情報。

Honeywell D896についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもHoneywell D896の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがHoneywell D896で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)