    Form No. PDS 650A.24.2 QUANTUM PLUS 13 SEER HEAT PUMP WITH PURON™ REFRIGERANT 650A (60 Hz) Sizes 024 thru 060 The Quantum Plus line of split-system outdoor units has been e xpanded to include the Model 650A 13 SEER heat pump (with efficiencies up to 14.5 SEER). Homeowners will appreci- ate the Quantum Plus with Puron Refrigerant because of its e ...

  • Bryant QUANTUM PLUS 650A - page 2

    —2— DIMENSIONS A94148 ACCESS PANEL 1 1 / 4 "  1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low ambient control is used) max 125 ° F. 2. Maximum o ...

  • Bryant QUANTUM PLUS 650A - page 3

    —3— RECOMMENDED TUBE DIAMETERS * RST—Refrigeration Service T ubing, standard refrigerant gr ade tubing. NO TES: 1. T ube diameters are f or lengths up to 50 ft. For tubing lengths g reater than 50 ft, consult the Application Guideline and Service Manual f or Residential Split- System Air Conditioners and Heat Pumps using Puron Refrigerant. 2. ...

  • Bryant QUANTUM PLUS 650A - page 4

    —4— SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 024-A,C 030-A,C 036-A,C Operating Weight (Lb) 214 205 217 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 Operating V oltage Range* 187—253 Compressor Rated Load Amps 15.1 14.7 15.4 Compressor Locked Rotor Amps 61.0 72.5 83.0 Condenser F an Motor—Full Load Amps 0.8 1.1 1.1 Mi ...

  • Bryant QUANTUM PLUS 650A - page 5

    —5— SPECIFICA TIONS Contin ued * P er missible limits of the v oltage range at which the unit will oper ate satisfactorily . Operation outside these limits may result in unit f ailure. † If other than uncoated (non-plated), 60°C or 75°C (140° or 167°F) insulation, copper wire (solid wire f or 10 A WG and smaller , stranded wire f or large ...

  • Bryant QUANTUM PLUS 650A - page 6

    —6— THERMOST A TS AND A CCESSORIES * Do not use in zoning heat pump applications. † This plate is designed to cov er surrounding wall area located behind ther mostat. ‡ Thermostat conversion kit is a 24-v ac accessor y that can tur n a 4-wire ther mostat application into a 5-wire application. This kit can also be used to replace a broken th ...

  • Bryant QUANTUM PLUS 650A - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Compressor Start Assist—Capacitor and Relay Star t capacitor and star t relay which giv es a “hard” boost to compressor motor at each star t-up. SUGGESTED USE: Installations where interconnecting tube length e xceeds 50 ft. Installations where outdoor design temperature e x ...

  • Bryant QUANTUM PLUS 650A - page 8

    —8— COMBINA TION RA TINGS* See notes on page 9. UNIT SIZE- SERIES INDOOR UNIT CFM†† ARI ST ANDARD RA TINGS* Cooling Heating TC Seasonal Efficiency SEER EER High-T emp Low-T emp HSPF Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ Puron TXV Puron TXV & TDR** TC COP TC COP 024-A,C FX4ANF030† 800 25,000 TDR&a ...

  • Bryant QUANTUM PLUS 650A - page 9

    —9— COMBINA TION RA TINGS Continued * Ratings are net values reflecting the eff ects of circulating fan heat. Supplemental electr ic heat is not included. Ratings are based on: Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit. High-T emp Heating Standard: 70°F ( ...

  • Bryant QUANTUM PLUS 650A - page 10

    —10— 650AN060-B,C FV4A006 650AN048-A,C FV4A005 650AN042-A,C FV4A003 650AN036-A,C FX4A042 650AN030-A,C FX4A030 650AN024-A,C FX4A030 BASED ON INDOOR ENT . AIR A T 70˚F AND A T RA TED CFM 23.4 20.5 17.6 14.7 11.7 8.8 5.9 2.9 80 70 60 50 40 30 20 10 0 -10 OUTDOOR TEMPERA TURE, ˚F BUILDING HEA T LOSS, 1000 BTU/HR UNIT INTEGRA TED HEA TING CAP A ...

  • Bryant QUANTUM PLUS 650A - page 11

    —11— DET AILED COOLING CAP A CITIES* See notes on page 14. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** T o ...

  • Bryant QUANTUM PLUS 650A - page 12

    —12— DET AILED COOLING CAP A CITIES* Continued See notes on page 14. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant QUANTUM PLUS 650A - page 13

    —13— DET AILED COOLING CAP A CITIES* Continued See notes on page 14. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant QUANTUM PLUS 650A - page 14

    —14— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensible capacities are net capacities. Blo ...

  • Bryant QUANTUM PLUS 650A - page 15

    —15— HEA T PUMP HEA TING PERFORMANCE See notes on page 17. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES °F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T ota ...

  • Bryant QUANTUM PLUS 650A - page 16

    —16— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 17. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES °F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtuh† T otal Pwr Capacity MBtu ...

  • Bryant QUANTUM PLUS 650A - page 17

    —17— HEA T PUMP HEA TING PERFORMANCE Continued * The Btuh heating capacity values sho wn are net “integrated” values from which the defrost eff ect has been subtracted. The Btuh heating from supplement heaters should be added to those v alues to obtain total system capacity . † The kw values include the compressor , outdoor f an motor, an ...

  • Bryant QUANTUM PLUS 650A - page 18

    —18— System Design 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor fan e xternal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temper ature f or cooling mode without low-ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temper ature f or cooling ...

  • Bryant QUANTUM PLUS 650A - page 19

    —19— ...

  • Bryant QUANTUM PLUS 650A - page 20

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 650A.24.1 © 1998 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indianapolis, IN 46231 —2 0— PRINTED IN U.S.A. Catalog No. 5265-002 1-99 SERVICE TRAINING Packaged Service Training programs are an excellent ...

メーカー Bryant カテゴリー Heat Pump

Bryant QUANTUM PLUS 650Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- QUANTUM PLUS 650Aの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant QUANTUM PLUS 650Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant QUANTUM PLUS 650Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant QUANTUM PLUS 650Aの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant QUANTUM PLUS 650Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant QUANTUM PLUS 650Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant QUANTUM PLUS 650Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant QUANTUM PLUS 650Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant QUANTUM PLUS 650Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant QUANTUM PLUS 650Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant QUANTUM PLUS 650Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant QUANTUM PLUS 650Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant QUANTUM PLUS 650Aデバイスの基本機能を使うにあたってのヒント。 Bryant QUANTUM PLUS 650Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant QUANTUM PLUS 650Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant QUANTUM PLUS 650Aのメーカー/サービスへの連絡先に関する情報。

Bryant QUANTUM PLUS 650Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant QUANTUM PLUS 650Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant QUANTUM PLUS 650Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)