    MS-A•W A · MU-A•W A MSZ-A•NA · MUZ-A•NA · MUZ-A•NA - U MSY -A•NA · MUY -A•NA MSZ-FD•NA · MUZ-FD•NA · MUZ-FD•NA - U MSZ-D•NA · MUZ-D•NA · MUZ-D•NA - U MSY -D•NA · MUY -D•NA · MXZ-A•NA SER VICE TECHNICAL GUIDE CONTENTS 1. MS MICROPROCESSOR CONTROL ·················· 4 2. MSZ, MSY MICROPROCES ...

  • Mitsubishi Electronics MSY-ANA - page 2

    2 Revision A: • MXZ-3A30NA- 1 has been added. Revision B: • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD, MSZ-D and MSY -D have been added. ...

  • Mitsubishi Electronics MSY-ANA - page 3

    1. MS MICROPROCESSOR CONTROL ··························································· 4 Indoor unit models Outdoor unit models MS-A09W A MU-A09W A MS-A12W A MU-A12W A 1-1. COOL OPERA TION ·················································· ...

  • Mitsubishi Electronics MSY-ANA - page 4

    4 MS MICROPROCESSOR CONTROL 1 1-1. COOL ( ) OPERA TION MS-A•W A MU-A•W A 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat’s OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat is ON or OFF by difference between room temperature an ...

  • Mitsubishi Electronics MSY-ANA - page 5

    5 1. Thermostat control Thermostat is ON or OFF by difference between room temperature and set temperature. 2. Indoor fan speed control Indoor fan operates at the set speed by F AN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes V ery Low . In AUTO the fan speed is as follows. 4. Coil frost prevention Coil frost preven ...

  • Mitsubishi Electronics MSY-ANA - page 6

    6 1-3. AUTO V ANE OPERA TION 1. Horizontal vane <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided. Then when the downward blow has been finish ...

  • Mitsubishi Electronics MSY-ANA - page 7

    7 MSZ,MSY MICROPROCESSOR CONTROL 2 2-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat’s OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat is ON or OFF by difference between room temperature and set temperature ...

  • Mitsubishi Electronics MSY-ANA - page 8

    8 Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease. 2-2. DR Y ( ) OP ...

  • Mitsubishi Electronics MSY-ANA - page 9

    9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-D When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66 °F , the fan stops. ( ) if the temperature of room temperature thermistor is 66 °F or more and ( ) if the temperature of indoor coil themistor is less than 32 °F , the fan sto ...

  • Mitsubishi Electronics MSY-ANA - page 10

    set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V . coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane V ery Low (temperature of indoor coil thermistor > 64 °F) 30 seconds 30 seconds 30 seconds 40 seconds 5 seconds 5 seconds 40 seconds OFF OFF OFF ON (HEA T) ON ON ON (HEA T) horizont ...

  • Mitsubishi Electronics MSY-ANA - page 11

    11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEA T mode when 15 minutes have passed with the room temperature 4 °F below the set temperature. HEA T mode changes to COOL mode when 15 minutes have passed with the room temperature 4 °F above the set temperature. In the other cases than t ...

  • Mitsubishi Electronics MSY-ANA - page 12

    12 <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided ...

  • Mitsubishi Electronics MSY-ANA - page 13

    13 MUZ-A24 MUY -A24 MUZ-D MUY -D POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies three-phase AC power to compressor . SMOOTHING CAP ACIT OR It stabilizes the DC voltage and s ...

  • Mitsubishi Electronics MSY-ANA - page 14

    Input current waveform without P AM Input current waveform with P AM Due to the time of no electricity; · Power factor gets worse. · Harmonic gets increased. Input voltage Energized time is short in case L inductance is small. No electricity runs into diode module because the voltage at both sides of smoothing capacitor is higher than input volta ...

  • Mitsubishi Electronics MSY-ANA - page 15

    15 4. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase AC waveform and outputs it. · Drive Circuit : Drives transistors. · Protection circuit : Protects transistors from overcurrent. Since the above components are all integrated in IPM, IPM has a merit to make the control circuit ...

  • Mitsubishi Electronics MSY-ANA - page 16

    16 2-7-3. Sine wave control In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element. In short, the motor is sensorless. However , it's necessary to locate the polar direction of rotor in order to drive brushless DC mo- tor ef fi ciently . The general detection method of the polar direction for such ...

  • Mitsubishi Electronics MSY-ANA - page 17

    17 2-8. OPERA TIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tem- perature. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protectio ...

  • Mitsubishi Electronics MSY-ANA - page 18

    18 2-9. EXP ANSION V AL VE CONTROL (LEV CONTROL) (1) Outline of LEV control The LEV basic control is comprised of setting LEV opening degree to the standard opening °F set for each operational frequency of the compressor . However , when any change in indoor/outdoor temperatures or other factors cause air con- ditioning load fluctuation, the LEV c ...

  • Mitsubishi Electronics MSY-ANA - page 19

    19 (2) T ime chart OFF T ime Ti m e ON Operational frequency of the compressor Commanded to open Standard opening degree Opening degree is corrected according to discharge temperature. Positioning Air conditioner ON Air conditioner OFF (thermostat off) LEV opening degree about 5 minutes <COOL, DRY> about 15 minutes <HEA T> (3) Control d ...

  • Mitsubishi Electronics MSY-ANA - page 20

    20 (b) Reference value of LEV standard opening degree (pulse) Applied model A B C D E F MUZ-A09/12 COOL 130 190 240 260 260 260 HEA T 100 130 170 210 230 230 MUZ-A15/17 MUY -A15/17 COOL 290 300 350 350 370 370 HEA T 130 150 220 250 280 300 MUZ-A24 MUY -A24 COOL 150 166 186 206 230 260 HEA T 130 150 170 196 210 226 MUZ-FD COOL 180 240 300 320 320 32 ...

  • Mitsubishi Electronics MSY-ANA - page 21

    21 MXZ MICROPROCESSOR CONTROL 3 3-1. INVERTER SYSTEM CONTROL MXZ-A•NA POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + 3-1-1. Inverter main power supply circuit Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies three-phase ...

  • Mitsubishi Electronics MSY-ANA - page 22

    22 3. Power factor improvement Booster coil reactor and PFC rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi- lize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Power transistor module IPM consists of ...

  • Mitsubishi Electronics MSY-ANA - page 23

    23 3-2. EXP ANSION V AL VE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit. Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulse in 15 minutes When outdoor unit is operating, some indoor units stop and some operate. COOL : 5 pulse (full closed) ...

  • Mitsubishi Electronics MSY-ANA - page 24

    24 In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger , and when temperature difference have developed, the indoor coil thermistors adjust LEV opening to dimin- ish the super heat. This action is called Evaporation T emperature Protection. Indoor heat exchanger (MXZ ...

  • Mitsubishi Electronics MSY-ANA - page 25

    25 23 54 69 84 100 1 15 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A MXZ-3A/4A 23 Compressor operating frequency (Hz) 4Hz 01 02 03 04 05 06 07 08 09 10 LEV Opening (code) Determination of LEV standard opening in each indoor unit • The standard opening is on the straight line, which connects an each standard point in the section where divided into se ...

  • Mitsubishi Electronics MSY-ANA - page 26

    26 MXZ-3A30NA- 1 MXZ-4A36NA Exclusive LEV Standard opening (pulse) LEV Opening (code) 123456789 1 0 COOL 126 130 134 138 150 160 170 180 190 200 HEA T 248 248 258 266 274 280 286 292 300 306 Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code1 1,12 Code13,14 Code15or above 23 4( MXZ-4A ) COOL 3 6 9 12 15 25 3 ...

  • Mitsubishi Electronics MSY-ANA - page 27

    27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor . <Correction> COOL DRY HEA T Discharge temperature ● 2 ● 2 ● Each correction • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermist ...

  • Mitsubishi Electronics MSY-ANA - page 28

    28 Correct the LEV opening according to the difference between target discharge temperature and discharge temperature. (2) Separate correction (COOL,DR Y) (Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all. Calculate each super ...

  • Mitsubishi Electronics MSY-ANA - page 29

    29 3-3. OPERA TIONAL FREQUENCY RANGE b) Correct the LEV separately by temperature difference “ ∆ RT” between main/sub indoor coil thermistor . ∆ RT LEV opening correction (pulse) 10.8 ∆ RT 2 7.2 ∆ RT < 10.8 1 ∆ RT < 7.2 1 In addition, decrease the target discharge temperature corresponding ∆ RT . ∆ RT T emperature to be decr ...

  • Mitsubishi Electronics MSY-ANA - page 30

    30 3-6. OUTDOOR F AN CONTROL Fan speed is switched according to the number of operating indoor unit and the compressor frequency . 3-5. DISCHARGE TEMPERA TURE PROTECTION CONTROL This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera- ture thermistor . (1) Compressor ON/OFF When tempe ...

  • Mitsubishi Electronics MSY-ANA - page 31

    31 1. Pre-heat control is turned ON for 15 or 30 min, after the breaker is turned ON. 2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min." This is repeated as shown in the graph until the breaker is turned OFF . When outside temperature is 68 °F or below , pre-heat control is ON for ...

  • Mitsubishi Electronics MSY-ANA - page 32

    New publication, effective Feb. 2008 Specifications subject to change without notice. Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Feb. 2008. No. OBT16 REVISED EDITION-B 6 Distributed in May 2007. No. OBT16 REVISED EDITION-A 7 Distributed in Apr . 2006. No. OBT16 7 Made in Japan HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, ...

メーカー Mitsubishi Electronics カテゴリー Air Conditioner

Mitsubishi Electronics MSY-ANAのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MSY-ANAの取扱説明書
- Mitsubishi Electronicsの製品カード
- パンフレット
- またはMitsubishi Electronics MSY-ANAの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Mitsubishi Electronics MSY-ANAの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Mitsubishi Electronics MSY-ANAの取り付け説明書、サービスマニュアル、簡易説明書、またはMitsubishi Electronics MSY-ANAのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Mitsubishi Electronics MSY-ANAの製品を使用するにあたって最も人気のある説明書を閲覧できます。

Mitsubishi Electronics MSY-ANAデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがMitsubishi Electronics MSY-ANAを使用するのを助ける技術的文書のことです。説明書は通常、全てのMitsubishi Electronics MSY-ANAユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Mitsubishi Electronicsの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Mitsubishi Electronics MSY-ANAの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははMitsubishi Electronics MSY-ANAの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Mitsubishi Electronics MSY-ANAに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Mitsubishi Electronics MSY-ANAデバイスの基本機能を使うにあたってのヒント。 Mitsubishi Electronics MSY-ANAのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Mitsubishi Electronics MSY-ANAに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるMitsubishi Electronics MSY-ANAのメーカー/サービスへの連絡先に関する情報。

Mitsubishi Electronics MSY-ANAについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもMitsubishi Electronics MSY-ANAの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがMitsubishi Electronics MSY-ANAで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)