    Marathon Sens ors Inc. Oxymit ™ Tran smitter Operators Manua l ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 2

    F200060 Revision: 00 04/18/2001 01 04/23/2001 02 05/08/2001 03 09/19/2001 04 11/01/2001 05 11/21/2001 06 04/19/2002 07 10/30/2002 08 11/13/2002 09 11/06/2003 10 12/03/2003 11 09/30/2004 12 04/04/2005 13 04/11/2005 14 11/14/2006 COPYRIGHT © 2004 MARATHON SENSORS INC. 3100 East Kemper Road, Cincinnati, Ohio 45241 1-800-547-1055 (513) 772-1000 FAX: ( ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 3

    Table of Contents GENERAL DESCRIPTION ................................ ................................ ................................ ............................ 2 SAFETY SUMMARY ................................ ................................ ................................ ................................ ...... 3 CONNECTIONS .............. ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 4

    Page 1 of 23 11/14/200 6 Rev. 14 NOTE: Please specify the following parameters when ordering a transmitter; process type, process range (%, ppm), thermocouple type, temperature scale F/C, analog output 1 process and scale, analog output 2 process and scale. Typical Oxygen Transmitter Calibration (F840030) Calibration Function Measured Value or Inpu ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 5

    Page 2 of 23 11/14/200 6 Rev. 14 General Descr iption The Oxymit ™ Transmitter has been designed to work as an analog or digital interface for any zirconia based oxygen probe used to track dew point, carbon potential, or oxygen. The transmitter connects to the temperature and millivolts outputs of an ox y gen probe and can produce analog outputs ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 6

    Page 3 of 23 11/14/200 6 Rev. 14 Safety Summ ary All cautions and instructions that appear in this manual must be complied with to prevent personnel injury or damage to the Probe T ransmitter or connected equipment. The specified limits of this equipment must not be ex ceeded. I f these limits are exceeded or if this instrument is used in a manner ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 7

    Page 4 of 23 11/14/200 6 Rev. 14 The next figure shows a schematic represent ation of the Probe Transmitter and t ypica l connections required in the field. Figure 3 S chematic Connections Grounding and Shielding To minimize the pick-up of electrical noise, the low vol tage DC connections and the senso r input wiring should be route d awa y fr om h ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 8

    Page 5 of 23 11/14/200 6 Rev. 14 Table 1 Process Pa rameters Parameter Name Selection Default Units or Option s Range PROCESS TYPE %O2 CARBON, DPT, %O2, MV CARB PROC FACT 150 0 to 1000 DEWPT PROC FACT 150 0 to 1000 OXYGEN EXPON 0002 POWER OF TEN 0 to 31 TC TYPE B B, C, E, J, K, N, NNM, R, S, T Process Type Selecting the process t y pe determines wh ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 9

    Page 6 of 23 11/14/200 6 Rev. 14 Oxygen Exponent The range of ox y gen is factor y configured using the oxygen exponent number. Percent oxygen is the standard setting where the oxygen exponent is set to 2 and the output range is 0.00% to 20.9%. For a part per million ( ppm) range the exponent would be set to 6 and the output range of 0.00 X 10 -6 t ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 10

    Page 7 of 23 11/14/200 6 Rev. 14 Table 2 Analog Outputs Parameter Name Oxygen Default Possible Options Possible Ranges OUTPUT 1 MODE O2 0–20.9% 4-20mA O2, CARBON, DEWPT, TEMP, LIN, PROG O2 = 0 – 9999 %C = 0.00 – 2.55 DP = -99.9 – 212.0 Temp = -999 – 3000 LIN = -999 – 9999 PROG = 0 – 4095 OUTPUT 2 MODE TEMP 800-3000°F 4-20mA O2, CARBO ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 11

    Page 8 of 23 11/14/200 6 Rev. 14 Process Variable Calcu lations The transmitter has a selectable process cal culation for percent carbon, percent ox yge n, or dewpoint. The followin g equations are used to derive these values; Percent Oxygen 20.95 %O2 = -------------------- --- e (E/0.0215*Tk) Where: E = probe millivolts, Tk = probe temperature in ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 12

    Page 9 of 23 11/14/200 6 Rev. 14 Communications The Transmitter is capable of digital communications usin g the Modbus protocol. Thi s is possible by connecting to the half duplex RS-485 terminals using a shielded twisted pair. Modbus The MODBUS protocol describes an industrial communications and distributed control system ( DCS) that integrates PL ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 13

    Page 10 of 23 11/14/200 6 Rev. 14 byte received will be an address. The follow command messa ge structure is used, where T is the required character delay. Response from the instrument is based on the command. T1 ,T2,T3 ADDRESS FUNCTION DATA CHECKSUM T1,T2,T3 8-BITS 8-BITS N X 8-BITS 16-BITS Address Field The address field immediatel y f ollows the ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 14

    Page 11 of 23 11/14/200 6 Rev. 14 The following is an example of a fun ction 03 call for dat a at memory location 03. The value returned by the instrument is t he hex value 1E. Transmit from Host or Master Address Cmd Reg HI Reg LO Count HI Count LO CRC HI CRC LO 01 03 00 03 00 01 74 0A Response from Transmitter Address Cmd Byte Count HI Byte Count ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 15

    Page 12 of 23 11/14/200 6 Rev. 14 Memory Map NOTE: Modbus refers to the he xadecimal register location. These parameters are formatted as unsigned 16 bit integers. An y real number suc h as temperature can be evaluated as a signed number , other parameters are bit mapped words that must be evaluated as single bits are bit groups. BLOCK 0 HEX DEC PA ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 16

    Page 13 of 23 11/14/200 6 Rev. 14 BLOCK 0 HEX DEC PARAMETER DESCRIPTION READ/W RITE DEFAULT = 150 05 5 EVENT LDLN LOW BYT E – INPUT EVENT CONFIGURAT ION Bits 0 – 3 0000 = None 0001 = Auto Mode Selected 0010 = Rem ote Setpoint Se lected 0011 = Acknowledge alarms 0100 = Tim er Hold 0101 = Tim er End 0110 = Tim er Start 0111 = Start pr obe test 10 ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 17

    Page 14 of 23 11/14/200 6 Rev. 14 BLOCK 0 HEX DEC PARAMETER DESCRIPTION READ/W RITE BITS 0 - 4 OXYGEN E XPONENT RANGE = 0 to 31, where 2 = % and 6 = ppm DEFAULT = 2 BITS 5 - 6 DISPL A Y DECIM A L PL ACE where: 0 = no decimal point in di spla y 1 = Display X XX.X 2 = Display X X.XX 3 = Display X .XXX DEFAULT = 0 BITS 8 – 12 REDOX M ETAL NUM BER RA ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 18

    Page 15 of 23 11/14/200 6 Rev. 14 BLOCK 0 HEX DEC PARAMETER DESCRIPTION READ/W RITE HIGH BYT E, ANALOG OUTPUT 2 BITS 8 – 12 0000 = N/A 0001 = Tem perature 0010 = Linear I nput A 0011 = Carbon value 0100 = Dewpoint value 0101 = Ox ygen value 0110 = Red ox value 0111 = O utput Power 1000 = Contr ol Output 1 1001 = Contr ol Output 2 1010 = Linear I ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 19

    Page 16 of 23 11/14/200 6 Rev. 14 BLOCK 0 HEX DEC PARAMETER DESCRIPTION READ/W RITE source value is b ased on the s election in ASRC upper b yte where 14 20 SPAR E SPARE READ/W RITE 15 21 SPAR E SPARE READ/W RITE 16 22 SPAR E SPARE READ/W RITE 17 23 T EMPFIL Temperature Inpu t Filter in seco nds Range = 0 t o 3276. The higher the num ber the faster ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 20

    Page 17 of 23 11/14/200 6 Rev. 14 BLOCK 1 HEX DEC PARAMETER DESCRIPTION READ/W RITE 22 20 DACV2 ANALO G OUTPUT 2 0 to 4095 is 4 to 20 m a In dual m ode 4mA = - 100, 12m A = 0, 20mA = +100 READ/W RITE 23 35 SPAR E SPARE 24 36 SPAR E SPARE 25 37 SPAR E SPARE 26 38 SPAR E SPARE 27 39 SPAR E SPARE 28 40 SPAR E SPARE 29 41 SPAR E SPARE 2A 42 SPARE SPAR ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 21

    Page 18 of 23 11/14/200 6 Rev. 14 Operational Spe cifications Power input 21.6 to 26.4 volts DC / 1 30mA Thermocouple input Thermocouple type Zero ºF Span ºF B 800 3000 C 32 3000 E 32 1300 J 32 1300 K 32 2300 N 32 2300 NNM 32 2000 R 300 3000 S 300 3000 T 32 700 Bold shows default Accuracy after linearization +/- 1 deg F Millivolt input -200 to 20 ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 22

    Page 19 of 23 11/14/200 6 Rev. 14 Thermocouple Null Thermocouple Span Cold Junction Trim Communications port RS-485 Half Duplex Only Protocol Modbus RTU Baud rates 1200, 2400, 4800, 9600, 19.2K (19.2K default ) Parity None Address 1 – 254 ( Address 1 is default ) Housing Material Polyamide PA non-reinforced Inflammability Evaluation Class V0 (UL9 ...

  • Marathon OXYMITH TRANSMITTER F200060 - page 23

    Page 20 of 23 11/14/200 6 Rev. 14 Fast Transients EN 61000-4-4 Level 4: 2 kV I/O Level 3: 2 kV power RF conducted interference EN 61000-4-6 Level 3: 10 V/ rms 150 KHz – 80 MHz Emissions as specified by EN 50081-2 RF Interference EN 55011 Enclosure class A Power main class A Note: This i nstrument is designed f or installation insi de a grounde d ...

メーカー Marathon カテゴリー Stereo System

Marathon OXYMITH TRANSMITTER F200060のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- OXYMITH TRANSMITTER F200060の取扱説明書
- Marathonの製品カード
- パンフレット
- またはMarathon OXYMITH TRANSMITTER F200060の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Marathon OXYMITH TRANSMITTER F200060の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Marathon OXYMITH TRANSMITTER F200060の取り付け説明書、サービスマニュアル、簡易説明書、またはMarathon OXYMITH TRANSMITTER F200060のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Marathon OXYMITH TRANSMITTER F200060の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Marathon OXYMITH TRANSMITTER F200060デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがMarathon OXYMITH TRANSMITTER F200060を使用するのを助ける技術的文書のことです。説明書は通常、全てのMarathon OXYMITH TRANSMITTER F200060ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Marathonの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Marathon OXYMITH TRANSMITTER F200060の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははMarathon OXYMITH TRANSMITTER F200060の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Marathon OXYMITH TRANSMITTER F200060に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Marathon OXYMITH TRANSMITTER F200060デバイスの基本機能を使うにあたってのヒント。 Marathon OXYMITH TRANSMITTER F200060のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Marathon OXYMITH TRANSMITTER F200060に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるMarathon OXYMITH TRANSMITTER F200060のメーカー/サービスへの連絡先に関する情報。

Marathon OXYMITH TRANSMITTER F200060についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもMarathon OXYMITH TRANSMITTER F200060の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがMarathon OXYMITH TRANSMITTER F200060で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)