Summary
  • Carrier 38AE016 - page 1

    Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ..............................1 - 8 Step 1 — Complete Pre-Installation Checks ....1 Step 2 — Rig and Mount the Unit .............6 Step 3 — Complete Refrigerant Piping Connections .................................6 Step 4 ? ...

  • Carrier 38AE016 - page 2

    LEGEND A— 1 1 ⁄ 4 -in. (32) diameter knockout for 5 ⁄ 8 -in. (16) ODM liquid line connection B— 1 3 ⁄ 4 -in. (44.5) diameter knockout for suction line connections of 1 1 ⁄ 8 in. (28.6) (38AE012), 1 3 ⁄ 8 in. (35) (38AE014,016), 1 5 ⁄ 8 in. (41) (38AKS024) C— 7 ⁄ 8 -in. (22.2) diameter knockout for control power D— 2-in. (50.8) ...

  • Carrier 38AE016 - page 3

    1 3 2 456 7 8 12 9 10 11 LEGEND 1— Low-V oltage Fuse 5— No. 2 Fan 9— Compressor 2— No. 1 Fan 6— T erminal Block 1 (Unit Power) 1 0— Low-Pressure Switch 3— High-Pressure Switch 7— T erminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 3 ⁄ 8 -in. ODM) 4— Circuit Breakers 8— Wraparound Coil 1 2— Muff ler Fig. 2 ? ...

  • Carrier 38AE016 - page 4

    T able 1A — Physical Data (English, 60 Hz) UNIT 38AE012 38AE014 38AE016 38AKS024 OPERA TING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Speed (Rpm) 1750 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.5 Crankcase Heater W atts 125 125 125 180 Unloader Setting (psig) Load ...

  • Carrier 38AE016 - page 5

    T able 1C — Physical Data (English, 50 Hz) UNIT 38AE012 38AE014 38AE016 38AKS024 OPERA TING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Speed (Rpm) 1460 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.5 Crankcase Heater W atts 125 125 125 180 Unloader Setting (psig) Load ...

  • Carrier 38AE016 - page 6

    T a b l e2—W eight Distribution UNIT WEIGHT — lb (kg) T otal Operating Support Point AB C D 38AE012 732 (333) 142 (65) 138 (63) 225 (102) 227(103) 38AE014 779 (354) 143 (65) 140 (64) 247 (1 12) 249 (1 13) 38AE016 789 (359) 143 (65) 143 (65) 250 (1 14) 253 (1 15) 38AKS024 900 (408) 178 (81) 168 (76) 269 (122) 285 (129) Step 2 — Rig and Mount t ...

  • Carrier 38AE016 - page 7

    INST ALL FIL TER DRIER(S) AND MOISTURE INDICA- TOR(S) — Every unit should have a filter drier and liquid- moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses. One filter drier and sight glass may be installed at A locations in ...

  • Carrier 38AE016 - page 8

    T able 5A — Electrical Data (3 Ph/60 Hz) UNIT UNIT COMPR F AN MOTORS (Single Phase) Model V olts MCA ICF MOCP (Fuse) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 12 38AE012 501 208-230 187 253 62.5 178 100 43.6 170 2 4.3 3.7 1.41 201 380 342 418 35.0 101 50 24.0 93 4.3 3.7 601 460 414 528 29.1 81 40 20.0 77 2.3 1.9 101 575 ...

  • Carrier 38AE016 - page 9

    PRE-ST ART -UP Evacuate and Dehydrate the entire refrigerant sys- tem by either of the methods described in Carrier Standard Service T echniques Manual, Chapter 1. Leak T est the entire refrigerant system by the pres- sure method described in Carrier Standard Service T ech- niques Manual, Chapter 1. Use R-22 at approximately 25 psig (172.4 kPa) bac ...

  • Carrier 38AE016 - page 10

    Fig. 9 — 38AE012 and 38AKS024 Charging Chart 10 ...

  • Carrier 38AE016 - page 11

    Fig. 10 — 38AE014 Charging Chart 11 ...

  • Carrier 38AE016 - page 12

    Fig. 1 1 — 38AE016 Charging Chart 12 ...

  • Carrier 38AE016 - page 13

    Check Operation — V erify operation of all safety con- trols. Replace all service panels. Be sur e that contr ol panel cover is closed tightly . OPERA TING SEQUENCE Cooling — When the first stage (TC1) of the cooling ther- mostat closes, the timer starts. After approximately 3 sec- onds, the timer activates the compressor and fan motor no. 1 c ...

  • Carrier 38AE016 - page 14

    Outdoor Fans — Each fan is supported by a formed- wire mount bolted to the fan deck and covered with a wire guard. The exposed end of the motor shaft is covered with a rubber boot. In case a fan motor must be repaired or re- placed, be sure the rubber boot is put back on when the fan is reinstalled and be sure the fan guard is in place before sta ...

  • Carrier 38AE016 - page 15

    TROUBLESHOOTING PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power . 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power . 3. Check secondary fuse(s); replace with correct type and size. Replace transformer if primary windings receivi ...

  • Carrier 38AE016 - page 16

    TROUBLESHOOTING (cont) PROBLEM SOLUTION COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont) Airflow Restricted 1. Coil iced up. 1. Check refrigerant charge. 2. Coil dirty . 2. Clean coil fins. 3. Air filters dirty . 3. Clean or replace filters. 4. Dampers closed. 4. Check damper operation and position. Indoor-Air Fan Stopped 1. Electrical connectio ...

  • Carrier 38AE016 - page 17

    ...

  • Carrier 38AE016 - page 18

    P ACKAGED SER VICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory , and skills programs is available. A ...

  • Carrier 38AE016 - page 19

    ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y . DOES IT AGREE WITH UNIT? (Y/N) HAS THE GROUND ...

  • Carrier 38AE016 - page 20

    C. Start-Up CHECK EV APORA TOR F AN SPEED AND RECORD. CHECK CONDENSER F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEA VING CONDENSER AIR TEMP EV AP ENTERING-AIR DB (dry bulb) TEMP ...

メーカー Carrier カテゴリー Air Conditioner

Carrier 38AE016のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 38AE016の取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier 38AE016の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier 38AE016の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier 38AE016の取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier 38AE016のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier 38AE016の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Carrier 38AE016デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier 38AE016を使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier 38AE016ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier 38AE016の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier 38AE016の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier 38AE016に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier 38AE016デバイスの基本機能を使うにあたってのヒント。 Carrier 38AE016のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier 38AE016に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier 38AE016のメーカー/サービスへの連絡先に関する情報。

Carrier 38AE016についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCarrier 38AE016の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCarrier 38AE016で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)