    Room Air Conditioner Service and P ar ts Man ual CP 06 - CP 08 S vc P ar ts 2010 ( 05 / 10) C P 06F1 0 CP08F1 0 0 F Power Mode Timer 0 n / 0ff Fan Speed Temp Cool Money Saver ® Fan Only Dry hr Auto Swing 115Volts ...

  • Friedrich CP08F10 - page 2

    Air Conditioner Ser vice Man ual T ABLE OF CONTENTS Safety Precautions ............................................................................................................................... ...........3 Dimensions ............................................................................................................................... ...

  • Friedrich CP08F10 - page 3

    Ser vice Man ual 3 Saf ety Precautions Safety Precautions T o pre vent injury to the user or other people and proper ty damage, the f ollowing instructions must be f ollow ed. Incorrect operation due to ignoring instr uctions will cause harm or damage. The seriousness is classified b y the f ollowing indications. Meanings of symbols used in this ma ...

  • Friedrich CP08F10 - page 4

    4 Room Air Conditioner Saf ety Precautions Plug in the power plug properl y . • Otherwise , it will cause electric shock or fire. Do not operate or stop the unit b y inserting or pulling out the power plug. • It will cause electric shock or fire. Do not damage or use an unspecified power cor d. • It will cause electric shock or fire. Do not u ...

  • Friedrich CP08F10 - page 5

    Ser vice Man ual 5 Saf ety Precautions CAUTION • • • • • If water enters the pr oduct, turn off the the power s witch of the main body of appliance. Contact service center after taking the power - plug out from the soc ket. • It will cause electric shock or f ailure of machine. Do not clean the air conditioner with water . • W ater ma ...

  • Friedrich CP08F10 - page 6

    6 Room Air Conditioner Dimensions Dimensions Outside Dimensions This symbol alerts you to the risk of electric shoc k. This symbol alerts you to hazar ds that could cause harm to the air conditioner . This symbol indicates special notes. NOTICE Symbols Used in this Manual 353(13 7 / 8 ") 470(18 1 / 2 ") 525(20 11 / 16 ") ...

  • Friedrich CP08F10 - page 7

    1Ø, 115, 60Hz * * ) B W ( 7 6 * ) B D ( 80 ) 。 ( R O O D N I F 。 F ) ( R O O D T U O 345g(12.2 oz) Ø7 .0, 2ROW 14 STA CKS Ø5 .0, 2ROW 16STA CKS TU RBO FAN PROPELLER TY PE FAN WITH SLINGER RING 3/3 6 POLES REMOTE CONTROLLER THERMISTOR HORIZONTAL LO UVER (UP & DOWN), VER TICAL LOUVER (RIGHT &LEFT) SLIDE IN-OUT CH AS SIS R O T C E T O R ...

  • Friedrich CP08F10 - page 8

    Ai r Pu r i f i e r Pow er Temp Mod e Ti me r A Sw i n g Fan Spe ed 1 2 4 3 5 Auto Swing 6 0 F P ower Mode Timer 0n / 0f f Fa n Speed T emp Cool Money Saver ® Fan Only Dry hr Auto Swing 1 3 2 4 6 5 7 6. A UT O SWING This button can automatically control the air flo w direction. 7 T o receive the signal from remote controller. dry operation. (dehum ...

  • Friedrich CP08F10 - page 9

    Disassembly Disassembl y Mechanical Parts — Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord. 1. FRONT GRILLE 1. Open the lnlet grille upward or downward. 2. Remove the screw which fastens the front grille. 3. Pull the front grille from the right side. 4. Remove the front grille. 5. Re-install the component ...

  • Friedrich CP08F10 - page 10

    1 0 Room Air Conditioner Disassembly Air Handling P ar ts 1 . AIR GUIDE AND BLO WER 1. Remove the front grille. 2. Remove the cabinet. 3. Remove the control box. 4. Remove the 3 screws which fasten the brace. 5. Remove the brace. 6. Remove the 2 screws which fasten the evaporator. 7. Move the evaporator forward and pulling it upward slightly. (See ...

  • Friedrich CP08F10 - page 11

    Se r vice Ma n ual 1 1 Electrical P ar ts 1. Remove the cabinet. 2. Remove the evaporator. 3. Remove the orifice. 4. Remove the blower. 5. Remove the fan. 6. Remove the control box cover and housing of the motor in the control box. 7. Remove the 2 screws which fasten the motor from th e moun t motor . (Se e Figur e 7 ) 8. Remove the motor. 9. Re-in ...

  • Friedrich CP08F10 - page 12

    3. CA P A CI T OR 1 2 Room Air Conditioner 1. Remove the control box. 2. Remove the screw which fasten control panel from control box. 3. Remove the screw which located in the front. 4. Open the bottom side of control box. 5. Remove the screw and the clamp which fastens the capacitor. 6. Disconnect all the leads of capacitor terminals. 7. Re-instal ...

  • Friedrich CP08F10 - page 13

    13 Room Air Conditioner Disassembly — Replacement of the refrigeration cycle. 1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a Freon TM recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon TM . Leave the valve in place after se ...

  • Friedrich CP08F10 - page 14

    Se r vice Ma n ual 14 Disassembly Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve. A COMPOUND GAUGE EVAPORATOR (LOW PRESSURE SIDE) COMPRESSOR CAPILLARY TUBE CONDENSER (HIGH PRESSURE SID ...

  • Friedrich CP08F10 - page 15

    Schematic Diagr am Cir cuit Diagram LOCATION NO. 1 2 3 4 5 6 7 8 Q'TY PER SET 1 1 1 1 1 1 1 1 DESCRIPTION POWER CORD ASSEMBLY FAN MOTOR COMPRESSOR DISPLAY P.W.B ASSEMBLY MAIN P.W.B ASSEMBLY THERMISTOR CAPACITOR OWERLOAD PROTECTOR (SMPS) 250V/T2A (250V/T3.15A) MEZ62420707 WH (BL) 15 Room Air Conditioner ...

  • Friedrich CP08F10 - page 16

    Electr onic Control De vice Schematic Diagram Se r vice Ma n ua l 16 ...

  • Friedrich CP08F10 - page 17

    T roubleshooting Guide T r oubleshooting Guide Piping System Figure 1 6 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle. MOTOR COMPRESSOR OIL (LIQUID REFRIGERANT) CAPILLARY T ...

  • Friedrich CP08F10 - page 18

    T roubleshooting Guide T roub leshooting Guide In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but poor cooling. Ineffective Cooling ...

  • Friedrich CP08F10 - page 19

    T roubleshooting Guide Fails to Start Improper thermistor setting Loose terminal connection Improper wiring Check of power source. Drop of power voltage. Capacitor check. Replacement. Check of control panel setting. Compressor fails only to start. Defect of compressor capacitor. Replacement of compressor (Motor damaged). Irregular motor insulation ...

  • Friedrich CP08F10 - page 20

    T roubleshooting Guide ELECTRIC P AR TS TR OUBLESHOO TING GUIDE: P ossible T rouble 1 • The unit does not operate. Is the Trans input power AC 115V? Is the Trans output power about AC 14V? Is shorted the Trans. output? Is output Voltage of IC01D DC 12V? Is output Voltage of IC02D DC 5V? Is the voltage No.18 of Micom DC 5V? Exchange Main P.W.B Ass ...

  • Friedrich CP08F10 - page 21

    T roubleshooting Guide Is Temp. setting set lower than Room Temp.-0.5 ° C? Is the voltage No.10 of IC01M 0V? • Exchange IC01M. • Set the Temp. setting to lower Temp. • Wait 3 Minutes Is the Unit for 3 minutes delay? • Exchange MAIN P.W.B Ass'y. Is the voltage N0.7 of IC01M DC 5V? • Check the RY-COMP. • Check the wiring Diagram. NO ...

  • Friedrich CP08F10 - page 22

    T roubleshooting Guide Is the voltage of Battery about over 2.3V? • Exchange Receiver Ass'y. Is the connection of CN-DISP1 all right? Is the voltage No.16 of CN-DISP1 on Main P.W.B Ass'y DC 5V? • Exchange the battery. • Check the P.W.B pattern. • Connect connector to CN-DISP1 exactly. NO NO NO YES YES YES P ossible T rouble 5 • ...

  • Friedrich CP08F10 - page 23

    T roubleshooting Guide ROOM AIR CONDITIONER VOLTAGE LIMITS NAME PLATE RATING MINIMUM MAXIMUM 115V ± 10% 103.5V 126.5V Y D E M E R E S U A C T N I A L P M O C Fan motor will not run. No power Check voltage at outlet. Correct if none. Wire disconnected or Connect wire. Refer to wiring diagram for connection loose terminal identification. Repair or r ...

  • Friedrich CP08F10 - page 24

    T roubleshooting Guide Y D E M E R E S U A C T N I A L P M O C , g n i s s i m y l l a i t r a p r o , e c n a l a b f o t u o , d e k c a r c f I n a F . e s i o n r o t o m n a F replace it. , g n i s s i m y l l a i t r a p r o , e c n a l a b f o t u o , d e k c a r c f I r e w o l B replace it. Loose set screw Tighten it. Worn bearings If knoc ...

  • Friedrich CP08F10 - page 25

    COMPLAINT CAUSE REMEDY Compressor cycles on Voltage Check the voltage. See the limits on the overload. preceding page. If voltage is not within these limits, call an electrician. Overload Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.) Compressor cycles on Fan m ...

  • Friedrich CP08F10 - page 26

    Exploded Vie w Exploded Vie w 249950 268711-1 264110 238310 237200 268711-2 135500 146812 W0CZZ 359011 731273 267110 135303 749740 352380 152302 148000 130910 34681 1 349600 W48602 149980 359012 349480 147581 135312 130410 567502 550140 349001 147582 567480 552113 Se r vice Ma n ua l 26 ...

  • Friedrich CP08F10 - page 27

    LocNo DESCRIPT ION CP06F10 130410 Base Ass embly,Single 67302912 130910 Cabinet Assem bly ,Single 67303714 135303 Grille,Inlet 67306114 135312 Grille As sembly,Front(Indoor) 67306017 135500 Cover 67400148 146812 Motor,AC 67300902 147581 Louver,Horizontal 67306208 147582 Louver,Vertical 67306264 148000 Supporter 67303901 149980 Shroud 67303108 15230 ...

  • Friedrich CP08F10 - page 28

    Replacement Parts list LocNo DESCRIPTIO N CP08F10 130410 Base Ass e mbly ,Single 67302917 130910 Cabinet Assem bly ,Single 67303714 135303 Grille,Inlet 67306114 135312 Grille Ass embly,Front(Indoor) 67306017 135500 Cover 67400148 146812 Motor,AC 67300902 147581 Louver,Horizontal 67306208 147582 Louver,Vertical 67306264 148000 Supporter 67303901 149 ...

  • Friedrich CP08F10 - page 29

    Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540 • (210) 357-4400 • FAX (210) 357-4490 FRIEDRICH AIR CONDITIONING CO. Visit our web site at www.friedrich.com Use F actor y Cer tified P ar ts... CP 06 - CP 08 S vc P ar ts 2010 ( 05 / 10) ...

メーカー Friedrich カテゴリー Air Conditioner

Friedrich CP08F10のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- CP08F10の取扱説明書
- Friedrichの製品カード
- パンフレット
- またはFriedrich CP08F10の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Friedrich CP08F10の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Friedrich CP08F10の取り付け説明書、サービスマニュアル、簡易説明書、またはFriedrich CP08F10のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Friedrich CP08F10の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Friedrich CP08F10デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがFriedrich CP08F10を使用するのを助ける技術的文書のことです。説明書は通常、全てのFriedrich CP08F10ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Friedrichの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Friedrich CP08F10の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははFriedrich CP08F10の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Friedrich CP08F10に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Friedrich CP08F10デバイスの基本機能を使うにあたってのヒント。 Friedrich CP08F10のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Friedrich CP08F10に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるFriedrich CP08F10のメーカー/サービスへの連絡先に関する情報。

Friedrich CP08F10についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもFriedrich CP08F10の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがFriedrich CP08F10で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)