  • Goodman Mfg GSC140481A - page 1

    • Refer to Service Manual RS6100004 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. Models listed on page 3. GSH 14 SEER Remote Heat Pump RT6213004 April 2006 This manual is to be used by qualified HV AC technicians only . Goodman does not assume any re ...

  • Goodman Mfg GSC140481A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROP- ERTY DAMAGE, PERSONAL INJURY OR DEA ...

  • Goodman Mfg GSC140481A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING DO NOT CONNECT OR USE ANY DEVICE THAT IS NOT DESIGN CERTI- FIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES. WARNING WARNING TO PREVENT THE RISK OF PROPERTY DAMAGE, PERS ...

  • Goodman Mfg GSC140481A - page 4

    PRODUCT DESIGN 4 GSH14 SEER split system heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications. Air is drawn through the outdoor coil by a propeller fan, and is discharged vertically out the top of the unit. No additional restriction (ductwork) shall be applied. The suction and liq ...

  • Goodman Mfg GSC140481A - page 5

    5 HEA T PUMP SPECIFICA TIONS GSH14[018-060]1A* (1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes . (2) May use fuses or HACR type Circuit Breakers of the same size as noted. NOTE: This data is provided as a guide, it is important to electrically connect the unit and pr ...

  • Goodman Mfg GSC140481A - page 6

    6 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OP ERA TI ON M ODEL: G SH140181A * / C A*F3131B6A *+TXV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid servic e valve, ARI 95 test conditio ns Outdoor A mbient Temperat ure 65 75 85 95 105 115 Entering Indoor W et Bulb Te mperature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg GSC140481A - page 7

    7 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA C OOL IN G OPER AT ION M ODEL: GSH 140181A * / CA* F 3131B6A *+T XV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid service valve, A R I 95 test conditio ns Ou tdo or Amb ie nt Tem per atu r e 65 75 85 95 105 115 Entering Indoor Wet Bulb T emperature I D B * A i r f l o w ...

  • Goodman Mfg GSC140481A - page 8

    8 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DA TA COOLI NG OPER A TION MO DEL: GSH140 241A * / CA *F3636B6A *+TXV / MBR800** 1 Design Subc ooling 9 ±3 °F @ the li qui d servic e valve, A RI 95 test c ondit ions Outdoor A mbient T emperature 65 75 85 95 105 115 Entering I ndoor Wet Bul b Te mperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140481A - page 9

    9 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DATA COOLING OPER A TION MO DEL: GSH140 241A * / CA *F3636B 6A *+TXV / MBR800 **1 Desi gn Subc ooling 9 ±3 °F @ the liqui d se rvice valve, A RI 95 test c onditions Outdoor A m bien t Temperature 65 75 85 95 105 115 Entering I ndoor Wet B ulb T emperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140481A - page 10

    10 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service valve, A RI 95 test conditi on s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140481A - page 11

    11 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service valve, A RI 95 test conditi on s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140481A - page 12

    12 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service valve, A RI 95 test condi tions Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140481A - page 13

    13 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service valve, A RI 95 test condi tions Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140481A - page 14

    14 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DATA COOLING OPERA TION M ODEL: GSH140421A* / CA *F4860D6A*+TXV / M BR2000**-1 Design Subcooling, 9 ± 3 °F @ the liquid service valv e, A RI 95 test condit i ons Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb T emperature I D B * A i r f l o w 5 96 36 77 1 ...

  • Goodman Mfg GSC140481A - page 15

    15 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140421A * / CA*F4860D6A *+TXV / M BR2000**-1 D esign Subcoolin g, 9 ±3 °F @ th e liquid serv ice valve, AR I 95 te st conditi ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng I nd oor W et Bulb Temp eratur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140481A - page 16

    16 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / MBR2000**-1 Design Subcooling 9 ±3 °F @ th e liquid servi ce valve, AR I 95 test condit io ns Outdoor Ambient Temper ature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Tempe ratur e I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140481A - page 17

    17 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / M BR2000**-1 Design Su bcooling 9 ±3 °F @ th e liquid serv ice valve, ARI 95 te st conditio ns Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng I nd oor W et Bulb Temp eratur e I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg GSC140481A - page 18

    18 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service valv e, ARI 95 te st con diti ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140481A - page 19

    19 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service valv e, ARI 95 te st con diti ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140481A - page 20

    20 PERFORMANCE DA T A Outdo or Temp. ° F. Total Btuh Sensib le Btuh Latent Btuh Total Watts 75° 18,900 13,282 5,618 1,367 80° 18,675 13,290 5,385 1,410 85° 18,450 13,295 5,155 1,452 90° 18,225 13,344 4,881 1,489 95° 18,000 13,389 4,611 1,526 100° 17 ,550 13,301 4,249 1,558 105° 17 ,100 13,201 3,899 1,589 110° 16 ,470 12,768 3,702 1,616 115 ...

  • Goodman Mfg GSC140481A - page 21

    21 EXPA NDED PERFO RMANC E DA TA MO DEL: G SH140181A* / CA*F3131B6A*+TXV / M BR800** -1 HEA TING OPERA TION Outdoor A mbient Temperature 65 60 55 50 47 45 40 35 30 25 20 17 1 5 10 5 0 -5 -10 MBh 22.6 21.4 20.2 18.8 18.0 17.4 16.2 14.9 13.6 12.5 11.5 10.9 10.5 9.4 8.3 7. 3 6.2 5.1 Delta T 34.9 33.1 31.1 29.1 27.8 26.9 25.0 23.1 20.9 19.3 17.8 16.8 1 ...

  • Goodman Mfg GSC140481A - page 22

    22 SPLIT SYSTEM HEA TING PERFORMANCE EXPA NDED PE RFO RMA NCE DA TA MODEL: GS H140421A * / CA *F4860D6A *+TXV / MB R2000**-1 HE AT I N G OP E R AT I O N Outdoor A mbient T emperat ure 65 60 55 50 47 45 40 35 30 2 5 20 1 7 15 10 5 - 5 -10 MBh 49.8 47.1 44.4 41. 5 39 .6 3 8 . 43 5 . 63 2 . 93 1 . 22 8 . 82 6 . 62 5 . 12 4 . 12 1 . 71 9 . 21 6 . 81 4 ...

  • Goodman Mfg GSC140481A - page 23

    23 HEA TING SPECIFICA TIONS capacity btuh c.o.p. 4.8 9.6 14.4 19.2 65 22.63 4.23 39.008 55.391 71.7732 88. 156 60 21.42 4.09 37.802 54.185 70.5672 86. 950 55 20.16 3.93 36.542 52.925 69.3072 85. 690 50 18.85 3.75 35.228 51.611 67.9932 84. 376 45 17.44 3.54 33.824 50.207 66.5892 82. 972 40 16.20 3.36 32.582 48.965 65.3472 81. 730 35 14.94 3.16 31.32 ...

  • Goodman Mfg GSC140481A - page 24

    24 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a s ...

  • Goodman Mfg GSC140481A - page 25

    WIRING DIAGRAMS 25 TO AVOID POSSI BLE ELECTRI CAL SHOCK, PERSONAL I NJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI C ING. WARNING ! GSH140[18-60]1A* US E N .E .C. CL AS S 2 WI R E NOTES : 1) TO INDOOR U NIT LOW VOL T AGE TER MINAL BLO CK & INDO OR TH ER M O ST A T . 2) STA RT AS SI ST FAC TO R Y E QUI P PED WH EN REQ U I RE D. 3) C RA NKC ...

メーカー Goodman Mfg カテゴリー Heat Pump

Goodman Mfg GSC140481Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- GSC140481Aの取扱説明書
- Goodman Mfgの製品カード
- パンフレット
- またはGoodman Mfg GSC140481Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Goodman Mfg GSC140481Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Goodman Mfg GSC140481Aの取り付け説明書、サービスマニュアル、簡易説明書、またはGoodman Mfg GSC140481Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Goodman Mfg GSC140481Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Goodman Mfg GSC140481Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがGoodman Mfg GSC140481Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのGoodman Mfg GSC140481Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Goodman Mfgの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Goodman Mfg GSC140481Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははGoodman Mfg GSC140481Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Goodman Mfg GSC140481Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Goodman Mfg GSC140481Aデバイスの基本機能を使うにあたってのヒント。 Goodman Mfg GSC140481Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Goodman Mfg GSC140481Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるGoodman Mfg GSC140481Aのメーカー/サービスへの連絡先に関する情報。

Goodman Mfg GSC140481Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもGoodman Mfg GSC140481Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがGoodman Mfg GSC140481Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)