    NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property dam ...

  • Bryant 552A - page 2

    can be no deviation. Consult the Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Pu- ron ® Refrigerant to obtain required unit changes for specific applications and for R-22 retrofit. I. CHECK EQUIPMENT AND JOB SITE A. UNPACK UNIT Move to final location. Remove carton taking care not to damage unit. B. INSPECT EQ ...

  • Bryant 552A - page 3

    INSTALLING TXV IN PLACE OF PISTON 1. Pump system down to 2 psig and recover refrigerant. 2. Remove hex nut from piston body. Use backup wrench on fan coils. 3. Remove and discard factory-installed piston. Be sure teflon seal is in place. 4. Reinstall hex nut. Finger tighten nut plus 1/2 turn. NOTE: If the piston is not removed from the body, TXV wi ...

  • Bryant 552A - page 4

    VII. MAKE PIPING CONNECTIONS WARNING: Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves. CAUTION: Do not leave system open to atmosphere any longer than minimum required for installation. POE o ...

  • Bryant 552A - page 5

    2. Braze filter drier between connector tube and liquid tube to indoor coil. Flow arrow must point towards indoor coil. C. REFRIGERANT TUBING Connect vapor tube to fitting on outdoor unit vapor service valves. Connect liquid tube to filter drier. (See Fig. 6 and Table 1.) Use refrigerant grade tubing. D. SWEAT CONNECTION CAUTION: To avoid valve dam ...

  • Bryant 552A - page 6

    NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC. A. ROUTE GROUND AND POWER WIRES Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into ...

  • Bryant 552A - page 7

    To calculate additional charge requried for a 25-ft line set: 25 ft - 15 ft = 10 ft X 0.6 oz/f t=6o zo f additional charge. B. COOLING ONLY PROCEDURE UNITS WITH COOLING MODE PURON ® TXV Units installed with cooling mode TXV require charging by the subcooling method. 1. Operate unit a minimum of 10 minutes before checking charge. 2. Measure liquid ...

  • Bryant 552A - page 8

    TABLE 3 — REQUIRED LIQUID-LINE TEMPERATURE ( ° F) LIQUID PRESSURE AT SERVICE VALVE (PSIG) REQUIRED SUBCOOLING TEMPERATURE ( ° F) 8 1 01 21 41 61 8 189 58 56 54 52 50 48 195 60 58 56 54 52 50 202 62 60 58 56 54 52 208 64 62 60 58 56 54 215 66 64 62 60 58 56 222 68 66 64 62 60 58 229 70 68 66 64 62 60 236 72 70 68 66 64 62 243 74 72 70 68 66 64 2 ...

  • Bryant 552A - page 9

    TABLE 5 — REQUIRED SUCTION-LINE TEMPERATURE SUPERHEAT TEMP ( ° F) SUCTION PRESSURE AT SERVICE PORT (PSIG) 107.8 112.2 116.8 121.2 126.0 130.8 138.8 140.8 145.8 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 ...

  • Bryant 552A - page 10

    PURON ®— QUICK REFERENCE GUIDE • Puron ® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron ® . • Puron ® refrigerant cylinders are rose colored. • Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT 4B ...

  • Bryant 552A - page 11

    24 VAC HOT 24 VAC COM R C G W/W1 Y/Y2 R C C BRYANT NON-PROGRAMMABLE THERMOSTAT MODEL AC SINGLE-STAGE FURNACE AIR CONDITIONER SEE NOTE 2 Y G W HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97359 24 VAC HOT R G W/ W1 Y/ Y 2 O/ W2 R W Y C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL AC SINGLE-STAGE FURNACE AIR CONDITIONER G Y1 / W 2 L INDOOR FAN HEAT STAGE 1 ...

  • Bryant 552A - page 12

    24 VAC HOT R C W/W1 Y/Y2 G R DH W2 W1 Y/Y2 BRYANT NON-PROGRAMMABLE THERMOSTAT MODEL AC FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 24 VAC COM Y1 C SEE NOTE 2 G O J2 JUMPER J1 JUMPER A97363 24 VAC HOT R W Y G R DH W1 W2 Y/ Y2 OTHER NON-PROGRAMMABLE AC THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL ST ...

メーカー Bryant カテゴリー Air Conditioner

Bryant 552Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 552Aの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant 552Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant 552Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant 552Aの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant 552Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant 552Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant 552Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant 552Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant 552Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant 552Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant 552Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant 552Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant 552Aデバイスの基本機能を使うにあたってのヒント。 Bryant 552Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant 552Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant 552Aのメーカー/サービスへの連絡先に関する情報。

Bryant 552Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant 552Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant 552Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)