Mitsubishi FX-485ADP - page 1
USER'S GUIDE JY992D53201C This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX and FX 0N , 485 communication adapters. It should be read and understood before attempt- ing to install or use these units. Further information can be found in the FX PROGRAMMING MANUAL, ...
-
Mitsubishi FX-485ADP - page 2
1 INTRODUCTION ①⑥ LINK SG SDB SDA RDB RDA FG 24+ 24G 〈 FX-485ADP 〉 MITSUBISHI FX-485ADP ① Direct mounting hole ② Power LED · · · ③ R D L E D ······· ④ S D L E D ······· ⑤ Terminal screws (M3 (0.12)) ⑥ Extension cable ⑦ Terminal cover ⑧ Groove for mounting DIN rail (DIN rail width : 35 (1.38)) ⑨ Hook for mo ...
-
Mitsubishi FX-485ADP - page 3
Station No.15 ↑ FX series PC Max. 16 stations including A series PCs (total extension distance 500m) (2) Computer and PC by 1 : n configuration In this case, the number of link stations is 16 PCs at maximum for one computer, including the FX series PCs and A series PCs. Such system of data exchange with plural PCs with one computer is called the ...
-
Mitsubishi FX-485ADP - page 4
For setting up the system, the 485ADP can be connected to the following PCs. PC series FX 0N FX , FX 2C PC version Ver. 1.20 or later Ver. 3.30 or later Remarks Exclusive protocol format 1 and format 4 are supported. Exclusive protocol format 1 and format 4 are supported. FX 0N -485ADP FX-485ADP As for exclusive protocol formats (1, 4) , see the 48 ...
-
Mitsubishi FX-485ADP - page 5
*1 R is the terminating resistance. Connect the terminating resistance (330 Ω ) between terminals SDA and SDB , and terminals RDA and RDB . For details see section 2.3. *2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100 Ω or less. However, as for the computer link unit of the A series PC, see the manual ...
-
Mitsubishi FX-485ADP - page 6
*1 R is the terminating resistance. Connect the terminating resistance (110 Ω ) between terminals RDA and RDB . For details see section 2.3. *2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100 Ω or less. However, as for the computer link unit of the A series PC, see the manual of the computer link unit. ...
-
Mitsubishi FX-485ADP - page 7
Classification of terminating resistances In this product, two sets of terminal end resistances (330 Ω ✕ 2, 110 Ω ✕ 1) are packaged, and the terminating resistances to be connected differ as shown below depending on the circuit being used. ● When communicating with the RS-422 circuit, connect the resistances of “330 Ω 1/4W ” as the ...
-
Mitsubishi FX-485ADP - page 8
FX 0N FX, FX 2C The communication format of the PC is set using special D8120. Operating ambient temperature Humidity no condensation Shock resistance Noise immunity Dielectric withstand voltage Insulation resistance Ground Operating ambience 3 Environmental specifications Vibration resistance 0 to 55°C, storage temperature -20 to 70°C 35 to 85% ...
-
Mitsubishi FX-485ADP - page 9
X0000 ~ X0177 Y0000 ~ Y0177 M0000 ~ M0511 S0000 ~ S0127 M0000 ~ M8254 TS000 ~ TS063 CS000 ~ CS031 CS235 ~ CS254 TN000 ~ TN063 CN000 ~ CN031 CN235 ~ CN254 D0000 ~ D0255 D1000 ~ D2499 D8000 ~ D8255 ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) X,Y,M,S T,C , D 4 Symbol ASCII code Command Function Objective device symbol Number of processing poin ...
-
Mitsubishi FX-485ADP - page 10
In case of trouble, check the following points, and remedy according to the troubleshooting guide in the 485PC- IF manual. (1) Power LED Lit Otherwise (2) As for SD LED, RD LED, check and remedy according to the troubleshooting guide in the 485PC-IF manual. 5 DIAGNOSTICS : The extension cable is normally connected to the PC. : The extension cable i ...
-
Mitsubishi FX-485ADP - page 11
Prior to start of operation, follow the procedure below. As for detail of procedure, see the 485PC-IF manual. 6 Determine system configuration Setting of transfer specification (D8120) Setting of station number (D8120) Setting of time-out check time (D8129) (1) (2) (3) Specification of data length Specification of parity Specification of stop bit S ...
-
Mitsubishi FX-485ADP - page 12
Guidelines for the safety of the user and protection of the FX-485ADP, FX 0N -485ADP communication adapter JY992D53201C Effective AUG. 1997 Specifications are subject to change without notice. HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUCH TOKYO 100 TELEX : J24532 CABLE MELCO TOKYO HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN ● This manual has b ...