Summary
  • PB Heat Gas Boiler - page 1

    P innacle ® Gas Boilers P eerless ® Stainless Steel Installation, Operation & Maintenance Manual – Do not store or use gasoline or other flammable v apors and liquids in the vicinity of this or any other appliance . – WHA T T O DO IF Y OU SMELL GAS • Do not tr y to light any appliance . • Do not touch any electrical s witch; do not us ...

  • PB Heat Gas Boiler - page 2

    USING THIS MANUAL 1 A . INST ALLA TION SEQUENCE . . . . . . . . . . . . .1 B . SPECIAL A TTENTION BO XES . . . . . . . . . . . .1 1. PREINST ALLA TION 2 A . GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 B . CODES & REGULA TIONS . . . . . . . . . . . . . . .2 C. ACCESSIBILITY CLEARANCES . . . . . . . . . . .2 D . COMBUSTION AN ...

  • PB Heat Gas Boiler - page 3

    1 A. INST ALLA TION SEQUENCE F ollow the installation instructions provided in this manual in the order shown. The order of these instructions has been set in order to provide the installer with a logical sequence of steps that will minimize potential interferences and maximize safety during boiler installation. B. SPECIAL A TTENTION BO XES Through ...

  • PB Heat Gas Boiler - page 4

    2 A. GENERAL 1. Pinnacle boilers ar e supplied completely assembled as packaged boilers. The package should be inspected for damage upon receipt and any damage to the unit should be reported to the shipping company and wholesaler . This boiler should be stored in a clean, dry area. 2. Carefully r ead these instructions and be sure to understand the ...

  • PB Heat Gas Boiler - page 5

    3 PREINST ALLA TION Do not install this boiler where gasoline or other flammable liquids or v apors are stored or are in use . W ARNING This boiler is certified as an indoor appliance . Do not install this boiler outdoors or locate where it will be exposed to freezing temperatures. W ARNING Figure 1.1: Accessibility Clearances – Floor Standing Un ...

  • PB Heat Gas Boiler - page 6

    4 A. GENERAL 1. Pinnacle boilers ar e to be installed in an area with a floor drain or in a suitable drain pan. Do not install any boiler where leaks or r elief valve discharge will cause proper ty damage. 2. This boiler is not intended to suppor t e xter nal piping. All venting and other piping should be suppor ted independently of the boiler . 3. ...

  • PB Heat Gas Boiler - page 7

    A. GENERAL 1. The water supply and return piping of this appliance are to be sized according to system r equirements. Do not use piping smaller than the boiler connections. 2. In hydronic systems where sediment may e xist, install a strainer device in the boiler return piping to prevent large particles and pipe scale from entering the boiler heat e ...

  • PB Heat Gas Boiler - page 8

    6 9. P ressur e Relief V alve: The boiler pressur e relief valve is factory installed into the right side boiler manifold (inside the jacket). Pipe the discharge of the r elief valve to within 12" of the floor and close to a floor drain. Provide piping that is the same size or larger than the relief valve outlet. 10. Circulator: The boiler cir ...

  • PB Heat Gas Boiler - page 9

    7 c. The required flow rate can be calculated based on the design temperature differ ence from the return to the supply of the boiler . F or a PI- T80 with a design temperature differ ence of 20°F the calculation is as follows: d. T able 3.3 shows the pressure drop (in feet of water) for a flow rate which gives a 20°F temperature differ ence for ...

  • PB Heat Gas Boiler - page 10

    8 D . SYSTEM PIPING 1. Figur e 3.3 shows a single boiler with two zones. In this application, the P eerless P artner indirect water heater and the single heating zone requir e similar water temperature. 2. Figur e 3.4 shows an additional zone in which baseboard radiation is the heat load. This zone also requir es water temperatures similar to the i ...

  • PB Heat Gas Boiler - page 11

    9 Figure 3.3: One Boiler , Primary/Secondary with T wo Zones (Zone Circulator) WA TER PIPING AND CONTROLS ...

  • PB Heat Gas Boiler - page 12

    10 Figure 3.4: One Boiler , Primary/Secondary with Three Zones (Zone Circulator) WA TER PIPING AND CONTROLS ...

  • PB Heat Gas Boiler - page 13

    11 Figure 3.5: T wo Boilers, Primary/Secondary with F our Zones (Zone Circulator) WA TER PIPING AND CONTROLS ...

  • PB Heat Gas Boiler - page 14

    12 Figure 3.6: Three Boilers, P rimary/Secondary with Five Zones (Zone Circulator) WA TER PIPING AND CONTROLS ...

  • PB Heat Gas Boiler - page 15

    13 WA TER PIPING AND CONTROLS Figure 3.7: Three Boilers, P rimary/Secondary with Four Zones (Zone V alves) ...

  • PB Heat Gas Boiler - page 16

    14 Antifreeze solutions e xpand more than water . F or example, a 50% by volume solution e xpands 4.8% for a 148°F temperature rise while water e xpands about 3% for the same temperature incr ease. Allowance for this expansion must be considered in sizing e xpansion tanks and related components. 4. The flow rate in systems utilizing glycol solutio ...

  • PB Heat Gas Boiler - page 17

    15 WA TER PIPING AND CONTROLS Figure 3.8: Boiler in conjunction with a Chilled W ater System Figure 3.9: Boiler Connected to a Heating Coil in a F orced Air System ...

  • PB Heat Gas Boiler - page 18

    16 GAS PIPING A . GENERAL 1. All fuel piping to the boiler is to be in accordance with local codes. In the absence of local regulations refer to the National F uel Gas Code, ANSI Z223.1/NFP A 54. 2. Size and install piping to provide a supply of gas sufficient to meet the maximum demand of all appliances supplied by the piping. B. FUEL LINE SIZING ...

  • PB Heat Gas Boiler - page 19

    17 2. Install a sediment trap as shown in Figur e 4.1. Be sure to allow clearance from the floor for r emoval of the pipe cap. 3. Install a ground joint union between the sediment trap and the boiler to allow ser vice of the appliance. 4. Install a ser vice valve as shown in F igure 4.1 to allow the gas supply to be interrupted for ser vice. 5. Mai ...

  • PB Heat Gas Boiler - page 20

    18 3. T o check the gas supply pr essure on the gas valve: a. T urn off the power at the ser vice switch. b. T ur n off the gas shutoff valve. c. Using a flat screwdriver , tur n the screw inside the inlet pressur e tap fitting (see figure 4.4 and 4.5) one turn counterclockwise. d. Attach the manometer tube to the pr essure tap fitting. e. Open the ...

  • PB Heat Gas Boiler - page 21

    19 A. GENERAL 1. Install the boiler venting system in accordance with these instructions and with the National F uel Gas Code, ANSI Z223.1/NFP A 54, CAN/CGA B149, and/or applicable provisions of local building codes. 2. This boiler is a direct vent appliance and is listed as a Category IV appliance with Under writers L aboratories, Inc. B. APPRO VE ...

  • PB Heat Gas Boiler - page 22

    20 VENTING , INLET AIR AND CONDENSA TE D . EXHA UST VENT AND INT AKE AIR PIPE SIZING 1. F or the PI- T50 and PI- T80 Boilers the e xhaust vent and air intake pipes should be 2" Schedule 40 or 80. 2. F or the PI-80, PI-140, PI-199 the exhaust vent and air intake pipes should be 3" Schedule 40 or 80. 3. The total combined equivalent length ...

  • PB Heat Gas Boiler - page 23

    21 4. The minimum combined equivalent length is 16 equivalent feet. 5. The maximum combined equivalent length can be e xtended by increasing the diameter of the vent pipe. However , the transitions should begin a minimum of 15 equivalent feet from the boiler . a. T ransitions should always be made in ver tical sections of pipe to prevent the conden ...

  • PB Heat Gas Boiler - page 24

    22 VENTING , INLET AIR AND CONDENSA TE Figure 5.3: PI-80, PI-140, and PI-199 Sidewall V enting with 3" Pipe (Exhaust T ermination at Higher Elevation than Air Intak e). Figure 5.5: PI-80, PI-140, PI-199 Sidewall V enting with 3" P ipe (Air Intake and Exhaust on the same Elevation). Figure 5.4: PI- T50 & PI- T80 Sidewall V enting with ...

  • PB Heat Gas Boiler - page 25

    23 VENTING , INLET AIR AND CONDENSA TE Figure 5.7: PI-80, PI-140, PI-199 Sidewall V enting with 3" P ipe (3" V ent Kit). Figure 5.9: PI-80, PI-140, PI-199 Sidewall V enting with 3" P ipe (Concentric V ent Kit). Figure 5.10: PI- T50 & PI- T80 Sidewall V enting with 2" P ipe (Concentric V ent Kit). All exhaust vent pipes m ust ...

  • PB Heat Gas Boiler - page 26

    24 VENTING , INLET AIR AND CONDENSA TE Figure 5.11: PI-80, PI-140, PI-199 V ertical V enting with 3" Pipe. Figure 5.13: PI-80, PI-140, PI-199 V ertical V enting with 3" Pipe (Concentric V ent Kit). Figure 5.12: PI- T50 & PI- T80 V ertical V enting with 2" P ipe. Figure 5.14: PI- T50 & PI- T80 V ertical V enting with 2" P ...

  • PB Heat Gas Boiler - page 27

    25 F . EXHAUST T APPING FOR VENT SAMPLE T o obtain a combustion sample a hole must be drilled in the e xhaust vent pipe just above the first elbow at the outlet of the boiler . a. Drill a 21/64" diameter hole in the vent pipe just above the first elbow . b. T ap the hole with a 1/8" NPT P ipe T ap. c. T ake combustion samples through the ...

  • PB Heat Gas Boiler - page 28

    26 ELECTRICAL Install all electrical wiring in accordance with the National Electrical Code, ANSI/NFP A 70, and local requir ements. A. WIRING 1. Refer to Figur es 6.1 for connecting the power supply to the boiler . 2. Connect boiler to a 110 volt, single phase, 60 hertz electrical supply line with a fused disconnect switch. The boiler is fused for ...

  • PB Heat Gas Boiler - page 29

    27 ELECTRICAL e) The main gas valve is then energized to allow gas to mix with the combustion air . f) If the main flame is not detected in 5 seconds, the gas valve closes and the combustion fan goes into post-purge. Other wise, the combustion fan stays at the ignition speed for the length of the flame stabilization period. (10 to 25 seconds). g) A ...

  • PB Heat Gas Boiler - page 30

    28 C. SAFETY INTERL OCKS 1. Low W ater Pr essure Limit Switch: This boiler is intended to operate at pressur es exceeding 10 psig. If the water pressur e drops to below 10 psig, there is a water pressur e limit switch that inter rupts boiler operation and displays the message "PR0" on the interface unit. The combustion air fan completes a ...

  • PB Heat Gas Boiler - page 31

    ELECTRICAL 4. Error Codes: The LED Display will display error codes if the boiler is in a temporary fault condition. T able 8.1 shows Error Codes and descriptions. In some cases, if the temporary fault is not cor rected within 60 seconds the controller will go into a F ault Code. 5. F ault Codes: A F ault Code indicates the controller is locked-out ...

  • PB Heat Gas Boiler - page 32

    30 A. COMPLETING THE INST ALLA TION 1. Confirm that all water , gas and electricity are turned off. 2. V erify that water piping, venting, gas piping and electrical wiring and components are installed properly and where applicable in accordance with manufacturers' instructions. Be sur e that the boiler is installed in accordance with this manu ...

  • PB Heat Gas Boiler - page 33

    31 B. LIGHTING AND OPERA TING PROCEDURES ST ART -UP PROCEDURES FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE A. This appliance does not ha ve a pilot. It is equipped with an ignition de vice which automatically lights the burner . Do not try to light the burner by hand. B. BEFORE OPERA TING smell all arou ...

  • PB Heat Gas Boiler - page 34

    32 C. CHECK - OUT PROCEDURE 1. After star ting the boiler , be cer tain that all controls are working properly . Check to be sure that the boiler will shut down when the water temperature reaches the control board set point. 2. T o check operation of the ignition system safety shut- off features: a) T urn off gas supply . b) Set thermostat or contr ...

  • PB Heat Gas Boiler - page 35

    33 A. BOILER ERROR 1. When an error condition occurs the controller will display an error code on the display module. 2. These error codes and several suggested cor rective actions are included in T able 8.1. 3. In the case of E00, E13, and E14 this error , if uncorrected, will go into a fault condition as described is P aragraph B. B. BOILER F AUL ...

  • PB Heat Gas Boiler - page 36

    34 F ault Code Description Corrective Action F00 High Limit Exceeded. 1. Check circulation pump operation. 2. Assure that ther e is adequate flow through the boiler by accessing the status menu and confirming that there is less than a 50°F rise from the return thermistor to the supply thermistor . 3. If gray thermostat wires are being used, discon ...

  • PB Heat Gas Boiler - page 37

    35 A. GENERAL (WITH BOILER IN USE) General boiler obser vation can be perfor med by the owner . If any potential problems are found, a qualified installer or ser vice technician/agency must be notified. 1. Remove any combustible materials, gasoline and other flammable liquids and substances that generate flammable vapors from the area wher e the bo ...

  • PB Heat Gas Boiler - page 38

    36 d. Disconnect the white, red, blue, and black connection from the Mole x on the combustion blower . (Refer to Control W iring Schematic, Figure 6.3.) This will cause the fan to run at 100% which will then blow out any sediment that has accumulated in the condensate line. (This process should only take a few minutes.) e. The unit should now be re ...

  • PB Heat Gas Boiler - page 39

    37 e. Reset thermostats (IMPORT ANT : MAKE SURE EXHAUST VENT IS NO L ONGER BL OCKED!) f. T urn the Pinnacle back on** and observe condensate flow . g. Reconnect the condensate piping to the outside connection. **NOTE: When firing the boiler the first few times you may experience some fluttering of the gas burner that may result in a flame lockout. ...

  • PB Heat Gas Boiler - page 40

    38 A. BOILER DIMENSIONS 1. Figur e 10.1 shows the dimensions of the PI- T50 and PI- T80. 10. BOILER DIMENSIONS & RA TINGS BOILER DIMENSIONS & RA TINGS Figure 10.1: PI- T50/PI- T80 Dimensions ...

  • PB Heat Gas Boiler - page 41

    39 2. Figur e 10.2 shows the dimensions of the PI-80, PI-140 and PI-199. BOILER DIMENSIONS & RA TINGS Figure 10.2: PI-80/PI-140/PI-199 Dimensions ...

  • PB Heat Gas Boiler - page 42

    40 Boiler Model Input Btu/hr DOE Heating Capacity³ Btu/hr Net I=B=R Rating¹ ’ ² Btu/hr Seasonal Efficiency³ AFUE % Shipping W eight Lbs. PI- T50 18,000 to 50,000 16,000 to 46,000 40,000 92 58 PI- T80 19,000 to 80,000 17,000 to 74,000 64,000 92 58 PI-80 27,000 to 80,000 25,000 to 74,000 64,000 92 75 PI-140 46,000 to 140,000 43,000 to 129,000 1 ...

  • PB Heat Gas Boiler - page 43

    41 REP AIR P ARTS 11. REP AIR P ARTS ...

  • PB Heat Gas Boiler - page 44

    42 REP AIR P ARTS ...

  • PB Heat Gas Boiler - page 45

    43 A. ADV ANT AGES OF THE P125 CONTROL BOARD 1. T emperature displays in F ahrenheit or Celsius. 2. Improved troubleshooting by status display of: a. Actual Supply and Return T emperatures b. Flame Signal c. F an Speed 3. Ser vice Mode allows installers to manually control the firing rate for easy set up. 4. Available Softwar e that allows the inst ...

  • PB Heat Gas Boiler - page 46

    44 C. P125 CONTROL BO ARD VS. WHA CONTROL BOARD COMP ARISON Figure A.2: Comparative Control Board Sequence of Operation WHA T’S NEW WITH THE P125 CONTROL BOARD ...

  • PB Heat Gas Boiler - page 47

    P innacle ® Gas Boilers P eerless ® Stainless Steel Installation, Operation & Maintenance Manual TO THE INST ALLER: This manual is the property of the owner and must be affixed near the boiler for future reference. TO THE OWNER: This boiler should be inspected annually by a Qualified Service Agency. PI8008 R11 (9/06-5M) Printed in U .S.A . © ...

メーカー PB Heat カテゴリー Boiler

PB Heat Gas Boilerのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- Gas Boilerの取扱説明書
- PB Heatの製品カード
- パンフレット
- またはPB Heat Gas Boilerの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、PB Heat Gas Boilerの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、PB Heat Gas Boilerの取り付け説明書、サービスマニュアル、簡易説明書、またはPB Heat Gas Boilerのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、PB Heat Gas Boilerの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

PB Heat Gas Boilerデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがPB Heat Gas Boilerを使用するのを助ける技術的文書のことです。説明書は通常、全てのPB Heat Gas Boilerユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

PB Heatの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. PB Heat Gas Boilerの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははPB Heat Gas Boilerの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。PB Heat Gas Boilerに関してこのドキュメントで見つけることができる全てのヒントの目次
3. PB Heat Gas Boilerデバイスの基本機能を使うにあたってのヒント。 PB Heat Gas Boilerのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。PB Heat Gas Boilerに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるPB Heat Gas Boilerのメーカー/サービスへの連絡先に関する情報。

PB Heat Gas Boilerについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもPB Heat Gas Boilerの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがPB Heat Gas Boilerで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)