    INST ALLA TION INSTRUCTIONS 69-2076-01 S9360A, S9361A, S9370A, S9371A Integrated Boiler Controllers APPLICATION These integra ted boiler cont rol modules prov ide ignition sequence , flame monitorin g and safet y shutof f for either intermittent pilo t spark ignition or direct hot surface ignition heating systems. They a lso provide limit r ated wa ...

  • Honeywell S9360A - page 2

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 2 Fig. 1. S936X In tegrated Boiler Controller , dimensions in in. (mm). Electrical Ratin gs: Line V oltag e: 120 V ac, 60 Hz (220 V ac, 50 Hz on speci fic model numb ers). T ransformer: Nominal 24 V ac (maximum 30 V ac, minimum 18 V ac). 5.0 V A plus external loads (gas valv ...

  • Honeywell S9360A - page 3

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 3 69-2076—01 T able 1. Recom mended Igniti on Cables. T ransformer Requireme nt: Add curren t ratings of module, pil ot valve, main valve , vent da mper and any othe r compone nts o f the con trol system to deter mine transfor mer size require ment. Approvals: V aries with cont rol mode ...

  • Honeywell S9360A - page 4

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 4 WARNING Fire or Explosi on Hazard. Can cause seve re injury , death or property damage. 1. The modu le can malfun ction if it gets wet, leading to ac cumulation of explo sive gas. • Never ins tall wh ere water ca n flood, drip or condense on module. • Never try to use ...

  • Honeywell S9360A - page 5

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 5 69-2076—01 Fig. 3. Align module with slo ts in control box. Wire the Syst em WARNING Electrical Shock Hazard. Can cause seve re injury , death or property damage. Disconnect the power su pply before making wir ing connections to preve nt electrical shock or equipment dama ge. Check th ...

  • Honeywell S9360A - page 6

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 6 NOTE: Cable length must be 36 in. (0.9 m) or less. The cable mus t not be in co ntinuous c ontact with a metal surface or spark voltage w ill be greatly reduced. Use c eramic or plastic standoff insulators as re quired. 1. Connect on e end of the cable to the male quick-co ...

  • Honeywell S9360A - page 7

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 7 69-2076—01 Fig. 4. S park Ignition W iring (S936X). M24216 CIRCULA TOR SP ARK IGNITER FLAME SENSE INDUCER L1 L2 GND GND 24 V AC TRANSFORMER DAMPER ENVIRACOM DIAGNOSTIC SENSOR 1 SENSOR 2 ENVIRACOM DISPLA Y GAS CONTROL MV PV PV/ MV PRESSURE SWITCH LIMIT SWITCH OPTIONAL DEPENDING ON CONF ...

  • Honeywell S9360A - page 8

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 8 Fig. 5. Hot Surf ace Ignition W iring (S937X). Common Connectors SENSOR 1 SENSOR 2 GAS CONTROL MV MV PRESSURE SWITCH LIMIT SWITCH M24218 ENVIRACOM DISPLA Y ENVIRACOM DIAGNOSTIC 24 V AC TRANSFORMER L2 L1 GND FLAME SENSE HOT SURF ACE IGNITER CIRCULA TOR INDUCER GND T able 3. ...

  • Honeywell S9360A - page 9

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 9 69-2076—01 a Indicates optio nal connection b ased on configura tion. HSI Model Specific Co nnectors In addit ion to the com mon connectors lis ted above, T able 4 identi fies conn ectors avai lable on th e HSI model board assemblies. a Indicates optio nal connection b ased on configu ...

  • Honeywell S9360A - page 10

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 10 T able 5. Spark Model Specif ic Connec tors. a Indicates optio nal connections bas ed on configur ation. T able 6. Pin Confi guration. T emperature Control T emperatur e control s etpoint on t he module can be adjusted as de scribed in the fo llowing sections. Som e modul ...

  • Honeywell S9360A - page 11

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 1 1 69-207 6—01 “SP_” Setpoint. “Df_” Setpoint Differential (se lect models). “°F_” Degrees Fahrenheit Then press th e UP or DOW N button unt il the parameter has reached t he desired valu e. After 60 seconds wit hout any button inputs, the control will autom atically retur ...

  • Honeywell S9360A - page 12

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 12 Mounting Sensor and Thermowell The remote upper temperature senso r is installed in an immersion well (Fig. 8) that extends int o the supply w ater side of the boiler. Immersion Well Fitting The immersion well must snugly f it the sensing bu lb for good thermal re sponse. ...

  • Honeywell S9360A - page 13

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 13 69-2076 —01 Fig. 10. Operat ing Sequence. IGNITION SEQUENCE IDLE ALL OUTPUTS OFF CHECK LEAKA GE/ SET FLAME BIAS WAIT LIMIT SWITCH CLOSE CHECK DAMPER/ PRESSURE SWITCH OPEN DRIVE DAMPER/ INDUCER WAIT FOR SWITCH CLOSE PREPURGE SPARK TURN PILOT VALVE ON CHECK FLAME PRE-TRIAL SOFT LOCKOUT ...

  • Honeywell S9360A - page 14

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 14 T ROUBLESHOOTING IMPORT ANT 1. The following service procedures a re provided as a general g uide. Follow ap pliance manufac - turer ’s service instruction s if available. 2. On lockout and re try models, m eter reading s between gas cont rol and ignitio n module must b ...

  • Honeywell S9360A - page 15

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 15 69-2076 —01 T able 7. Error Codes. Segment Display Definitio n Pressure Switch failed to open (contacts stuck clo sed). Flame sens ed out of nor mal sequenc e (before ope ning gas va lve or after closing gas valve). Flame sens ed during pre purge (befor e gas valve sig naled opened ) ...

  • Honeywell S9360A - page 16

    S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS Automation and Cont rol Solution s Honeywell Internatio nal Inc. Honeywell Limited-H oneywell Limitée 1985 Douglas Dr ive North 35 Dynamic Drive Golden Valley, MN 55 422 Toronto, Ontario M1V 4Z9 customer.hone ywell.com ® U.S. Regi stered T rademark © 2007 Hone ywell Internat ional Inc. ...

メーカー Honeywell カテゴリー Boiler

Honeywell S9360Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- S9360Aの取扱説明書
- Honeywellの製品カード
- パンフレット
- またはHoneywell S9360Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Honeywell S9360Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Honeywell S9360Aの取り付け説明書、サービスマニュアル、簡易説明書、またはHoneywell S9360Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Honeywell S9360Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Honeywell S9360Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがHoneywell S9360Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのHoneywell S9360Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Honeywellの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Honeywell S9360Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははHoneywell S9360Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Honeywell S9360Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Honeywell S9360Aデバイスの基本機能を使うにあたってのヒント。 Honeywell S9360Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Honeywell S9360Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるHoneywell S9360Aのメーカー/サービスへの連絡先に関する情報。

Honeywell S9360Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもHoneywell S9360Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがHoneywell S9360Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)