    SEALED COMBUSTION DOWNFLOW GAS FURNACE MODELS: DGAA, DGAH, DGPA, AND DGPH For Installation In: 1, Manufactured (Mobile) Homes 2. RecreationaIVehicles & Park Models 3. Modular Homes & Buildings IMPORTANT - Only individuals having proven expedence with this type of equipment should attempt to perform set-up. Proper furnace set-up and adjustme ...

  • York DGAA056BDTA - page 2

    035-16328-002 Rev. C (0902) FURNACE SPECIFICATIONS DGAA -- AUTOMATIC IGNITION -- WITH BUILT-IN COIL CABINET -- 4 TON - AIC READY MODEL NO, Factor'/Equipped for use with Input/BTUH OutputJBTUH DGAA056BDTA NATURAL GAS 56,000 45,000 DGAA07OBDTA NATURAL GAS 70,000 56,000 DGAAO77BDTA NATURAL GAS 77,000 62,000 DGAAO9OBDTA NATURAL GAS 90,000 72,000 D ...

  • York DGAA056BDTA - page 3

    GENERAL INFORMATION NOTE: The words "Shall" or "Must" indicate a requirement which is essential to satisfactory and safe product perfor- mance. The words "Should" or "May" indicate a recommendation or advice which is not essential and not required but which may be useful or helpful. IMPORTANT - These instruct ...

  • York DGAA056BDTA - page 4

    035-16328-002 Rev. C (0902) RETURN AIR REQUIREMENTS CLOSET INSTALLATIONS Additional Requirements Additional requirements for floor and ceiling return system for closet installed sealed combustion heating appliance are given in the next paragraph. Floor or Ceiling Return Air System Listed in the next paragraph are the conditions to be met by Manufac ...

  • York DGAA056BDTA - page 5

    035-16328-002 Rev. C (0902) Return Air Grille Part No. 7900-287P/A * White 250 SQ. IN MINIMUM FREE AREA B 250 SQ. IN. MINIMUM 50 SQ LN FREE AREA _ MINIMUM FREE AREA Furnace to Closet Door Clearance -- 5 Inches or more The closet door MUST have a minimum o1250 Square Inches of free area in the upper half of the door. If opening for return air is loc ...

  • York DGAA056BDTA - page 6

    035-16328-002 Rev. C (0902) ROOF JACK AWARNING Failure to follow aft venting instructions can result in fire, asphyxiation, or explosion. [ Ak CAUTION Only use the appropriate roof jack. See Figures 6 & 7 for correct application. Do not exceed the maximum height as deter- mined from Figures 6 & 7. Installer should allow an additional 1-1/2& ...

  • York DGAA056BDTA - page 7

    035-16328-002 Rev. C (0902) SWIVEL FLASHING ADJUSTS FROM 0/12 TO 5/12 PITCH SLANT FLASHING 3/12 PITCH 4000-7101/C 4000-6101/A 4000-7121/C 4000-61211A 4900-7141/C 4000-6141/A 4900-7151/C 4000-6151/A 4900-7171/C 4009-6171/A DGAH FURNACES INSTALLATION DIMENSIONS "A" ADJUSTABLE HEIGHT 7O" _ 79" 75" _ 86" 83"to 104&quo ...

  • York DGAA056BDTA - page 8

    035-16328-002 Rev. C (0902) I SWIVEL FLASHING ADJUSTS FROM 0/12 TO 5/12 PITCH SLANT FLASHING 3/12 PITCH 4000-8161/C I 4000-9161/A 4000-8181/C 4000-9181/A DGAH FURNACES INSTALLATION DIMENSIONS =A = ADJUSTABLE HEIGHT 85" to 101" 99" to 129" DGPH, DGPA, & DGAA FURNACES INSTALLATION DIMENSIONS "B" ADJUSTABLE HEIGHT 101 ...

  • York DGAA056BDTA - page 9

    035-16328-002 Rev. C (0902) DUCT CONNECTORS I .. - = I , , T. _ DUCT CONNECTOR DIMENSIONS DUCT CONNECTOR DIMENSIONS DUCT CONNECTOR PART NUMBER 7990-6011 7990-6021 7990-6041 7990-6061 7990-6071 7990-6081 7990_I01 7990-6121 I DUCT CONNECTOR DEPTH 1" 2" 4-I/2" 6-1-2" 7-1/2" 8-1/2" 10-1/4" 12-!/4" DUCT CONNECTOR ...

  • York DGAA056BDTA - page 10

    035-16328-002 Rev. C (0902) SUPPLY DUCT LOCATOR BRACKET _ NAI L_,AFL EATH EAD S C R EWS FLOOR SUPPLY DUCT NAILS, FLAT HEAD SCREWS OR STAPLES BEND TABS UNDER OPENING TO SECURE TO THE SUPPLY DUCT FIGURE tl : Duct Connector Screw Attachment INSTALLATION OF SCREW A'B'ACHMENT DUCT CONNECTOR 1, 2. 3. 4. 5. Make floor cut out as shown in Figure ...

  • York DGAA056BDTA - page 11

    035-16328-002 Ray. C (0902) FURNACE SEATED AGAINST THE LOCATOR BRACKET SECUREFURNACE TO FLOOR WITH TWO NAILS OR SCREWS. FIGURE 13 : Installation of Furnace INSTALLATION OF THE FURNACE 2. 3. Remove the front panels and set the fumaca onto the duct connector. Slide it back until the rear of the unit engages the Iocator bracket. Secure the front of ...

  • York DGAA056BDTA - page 12

    035-16328-092 Rev. C (0902) CEILING RINGS The coiling ring is to meet fire stop requirements. Accessory Ceiling Ring (PIN 7660-2841) may be used, (See Figure 15) or the manufactured home manufacturer or the installer may use other approved methods to stop fire. CONNECT THERMOSTAT WIRES 1. Insert 24 volt wires through the small plastic bushing just ...

  • York DGAA056BDTA - page 13

    035-16328-002 Rev. C (0902) WALL THERMOSTAT Avoid locations where the thermostat could be subject to drafts from outside, or exposed to direct light from lamps, sun, fireplaces, etc., or affected by air from a duct register blowing directly on the thermostat. The wall thermostat should be located 52 to 66 inches above the floor. The preferred locat ...

  • York DGAA056BDTA - page 14

    035-16328-002 Rev. C (0902) WIRING DIAGRAMS If" B!OWER MOTOR LN BLK MANUAL RESET LIMIT SWITCH _c_ w W R WALL "lit .... L THERMOSTAT °11 02 03 -c 4 05 06 07 4 8 GND. SCREW ORG ____ __Z WHT 3 AMP FUSE 24V SEC. 120V PRI. I INE TRANSFORMER FAN SWITCH ORG (_ GRY o AUTO RESET ORG LIMIT SWITCH SYSTEM GAS SWITCH CONTROL E NEU. ., WHT ..... . LI ...

  • York DGAA056BDTA - page 15

    035-16328-002 Rev. C (0902) WHT MANUAL RESET LIMIT SWITCI [_ WHT i :{_]_ RED I, W' i O 1 o2 o3 -o 4 o5 o6 o7 _8 ORG WHT BLU BRN 3 AMP FUSE COMBUSTION BLOWER RELAY GND. SCREW TRANSFORMER LOAD 24V SEC. 120V PRI. WHT ORG SYSTEM NEU, WHT SWITCH iv. BLK _3 _/ o 1 LI BLK WALL qt @ GNO. THERMOSTAT TO EARTH GND. SCREW FAN SWITCH AUTO RESET LIMITSWITCH ...

  • York DGAA056BDTA - page 16

    035-16328-002 Rev. C (0902) t I BLEND-AIR I CONTROL BOX [ (IF EQUIPPED i , , . i i i i , i ! I BLOWER MOTOR I_ K BLK MANUAL RESET i { LIMIT ] SWITCH I GRN WHT RED [_]i BLK b r • 1 AIC i CONDENSING I UNIT • J CONTACTORI , L ...... J i' LUl {_i 2°_w _ .,vAc WALL "lit THERMOSTAT ORG 4 I s :_g 6 7 9 WHT 3 AMP FUSE NEU. _ WHT i'_ LI ...

  • York DGAA056BDTA - page 17

    035-16328-002 Rev. C (0902) BLOWER MOTOR WHT MANUAL BLEND AIR ! RESET CONTROL BOX I LIMIT I (IF EQUIPPED) I SWITCH Z _}_ GRN i_ WriT i_ RED ' I_ BLK , F -I AJC l I CONDENSING I I UNIT I CONTACTOR I W, -J' L ....... G°°°:]w R ,,,VAt WA,, "lit L THERMOSTAT ORG '1 _2 _, _5 )6 81 2N RED 3 AMP FUSE NEU. WHT LI BLK :J TO EARTH GND, ...

  • York DGAA056BDTA - page 18

    035-16328-002 Rev. C (0902) RED WALL THERMOSTAT TO A]C __,J CONDENSING UNIT (if equipped) ............ ERL_ WHT BLK BLOW RED MOTOR I TO EARTH GROUND II I NEUTRAL 115 VAC L1 INCOMING POWER MUST BE POLARIZED. OBSERVE COLOR CODING. UPPER I LIMIT SWITCH BLU CRY m O o o BLK I RED WHT o ca L o; WHT GROUND SCRI .... _A D-_ ORG BRN BRN X o BLK BLK WHT WHT ...

  • York DGAA056BDTA - page 19

    GAS PIPING INSTALLATION AND CHECKING OF GAS LINE Gas Supply piping must be sized in accordance with the rec- ommendations contained in National Fuel Gas Code (ANSI- Z223.1, NFPA-54) unless local codes or regulations state oth- erwise. Matedals used and pipe sizing for U.S. manufactured homes must comply with requirements contained in Manufactured H ...

  • York DGAA056BDTA - page 20

    035-16328-002 Rev. C (0902) FINAL PROCEDURE INSTALL FURNACE DOORS Install the lower door first by sliding the bottom of the door down until the tabs on the casing base engage the slots in the bottom door end cap. Then push the top of the lower door in until the door clips snap into place. Install the upper door in a similar manner, first engaging t ...

  • York DGAA056BDTA - page 21

    035-16328-002 Rev. C (0902) HIGH ALTITUDE DERATION CHART Elevation Sea Level 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 56,000--lnput Odfice Drill Pa_ # Dia. Size 0.136 29 9951-1361 0.136 29 9981--1361 0.128 30 9981--1281 0.128 30 9951--1281 0.128 30 9951-1281 0.128 30 9951-1281 0.129 31 9951--1291 0.120 31 9951-1201 0.120 31 9951_-1201 ...

  • York DGAA056BDTA - page 22

    035-16328-002 Rev. C (0902) REPAIR PARTS LIST _ _HEAT/COOLHEAT ONLY __'_ DGAA056BDTA DGPA056ABTA DGAA070BDTA DGPA070ABTA DGAA077BDTA DGPA077ABTA DGAA090BDTA DGPA090ABTA DGAH056BBSA DGPH056ABTA DGAH077BBSA DGPH070ABTA DGPH077ABTA DGPH09OABTA i DGAA,DGAH ® L DGP_ DGPH [] / 3--" "4 DGAA, DGAH DGPA, DGPH I CONTROL BOX DETAIL 22 Unitary ...

  • York DGAA056BDTA - page 23

    035-16328-002 Rev. C (0902) DGAA ITEM DESCRIPTION DGAA056BDTA DGAA070BDTA DGAA077BDTA DGAA09OBDTA Switch, Pressure 024-27666-000 024-27666-000 024-27666-000 024-27666-000 2 Tubing Silicone (2' Req'd) 028-11957-000 028-11957-000 028-11957-000 028-11957-000 Limit Switch, Manual(Upper) 025-35358-000 026-35358-000 025-35356-000 025-35358-009 ...

  • York DGAA056BDTA - page 24

    035-16328-002 Rev. C (0902) DGAH ITEM DESCRIPTION Switch, Pressure 2 Tubing Silicone (2' Req'd) Limit Switch, Manual (Upper) 4 Assembly, Booster (w/Motor) Control Board, Integrated 6 Valve, Gas 7 Bracket, Valve 8 Thermostat (Heat/Cool) 9 Exchanger, Heat (w/Gasketa) 19 Sensor, Flame _ Switch, System Transformer (115-24V, 40 VA) Switch, Lim ...

  • York DGAA056BDTA - page 25

    035-16328-002 Rev. C (0902) DGPA ITEM DESCRIPTION DGPA086ABTA DGPA070ABTA DGPA077ABTA DGPA090ABTA Switch, Pressure ....... 024-27666-000 2 Tubing Silicone (2' Req'd) ........ 028-11957-000 Limit Switch, Manual(Upper) 025-35358-000 025-35358-000 025-35358_000 025-35358-000 4 Assembly, Booster (w/Motor) ........ 373-19601-820 Control Board, ...

  • York DGAA056BDTA - page 26

    035-16328-002 Rev. C (0902) DGPH ITEM DESCRIPTION Switch, Pressure 2 Tubing Silicone (2' Req'd} Limit Switch, Manual (Upper) 4 Assembly, Booster (w/Motor) Control Board, Integrated 6 Valve, Gas 7 Bracket, Valve 8 Thermostat (Heat Only) 9 Exchanger, Heat (w/Gaskets) 10 !Sensor, Flame Switch, System Transformer (115-24V, 40 VA) Switch, Limi ...

  • York DGAA056BDTA - page 27

    035-16328-002 Rev. C (0902) BURNER ORIFICE CHART (Normal Altitude Only 4) MODEL 056 070 077 090 NATURAL GAS 9951-1361 9951-1541 9951-1611 9951-1801 LP GAS 9951-0821 9951-0931 9951-0981 9951-1061 NOTES 4, Contact Customer Service for installations at altitudes over 2000 feet above sea level. =<= Across from row indicates a change in that row. ACC ...

  • York DGAA056BDTA - page 28

    NOTES Subject to change without notice. Printed in U.S.A. Copyright © by York Intemational Corp. 2002. All rights reserved. 035-16328-002 Rev. C (0902) Supersedes: 0035-16328-002 Rev. B (1001) Unitary P.O. Wichita Products Box KS Group 19014 67204-9014 ...

メーカー York カテゴリー Furnace

York DGAA056BDTAのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- DGAA056BDTAの取扱説明書
- Yorkの製品カード
- パンフレット
- またはYork DGAA056BDTAの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、York DGAA056BDTAの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、York DGAA056BDTAの取り付け説明書、サービスマニュアル、簡易説明書、またはYork DGAA056BDTAのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、York DGAA056BDTAの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

York DGAA056BDTAデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがYork DGAA056BDTAを使用するのを助ける技術的文書のことです。説明書は通常、全てのYork DGAA056BDTAユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Yorkの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. York DGAA056BDTAの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははYork DGAA056BDTAの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。York DGAA056BDTAに関してこのドキュメントで見つけることができる全てのヒントの目次
3. York DGAA056BDTAデバイスの基本機能を使うにあたってのヒント。 York DGAA056BDTAのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。York DGAA056BDTAに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるYork DGAA056BDTAのメーカー/サービスへの連絡先に関する情報。

York DGAA056BDTAについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもYork DGAA056BDTAの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがYork DGAA056BDTAで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)