Summary
  • Lennox International Inc. CBWMV - page 1

    09/06 505,047M *2P0906* *P505047M* Page 1 E 2006 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE W ARNING Due to higher operating pressures, CBWMV units must not be applied to steam boiler systems. CAUTION Unit is designed to be used with non−potable boiler systems only . CAUTION Physical contact with me ...

  • Lennox International Inc. CBWMV - page 2

    Page 2 505047 09/06 CBWMV Unit Dimensions − inches (mm) *Bottom Return Air Opening *Bottom Return Air Opening ELECTRICAL INLET (Either Side) SUPPL Y AIR OPENING AIR FLOW FRONT VIEW SIDE VIEW TOP VIEW A B 9/16 (14) C 3/4 (19) 3/4 (19) 28−1/2 (724) 19−7/16 (494) 23−1/2 (597) 4−1/4 (108) 40 (1016) 4 (102) 1−15/16 (49) 23 (584) 14 (356) 9/1 ...

  • Lennox International Inc. CBWMV - page 3

    Page 3 CBWMV SERIES General These instructions are intended as a general guide and do not supersede local codes in any way . Consult authorities having jurisdiction before inst allation. Only qualified ser- vice technicians or installers may install and service this unit. CBWMV Unit Part s Arrangement CBWMV Unit HOT W A TER COPPER TUBE COIL CBWMV C ...

  • Lennox International Inc. CBWMV - page 4

    Page 4 505047 09/06 Requirements W ARNING Improper installation, adjustment, alteration, ser- vice or maintenance can cause personal injury , loss of life, or damage to property . Installation and service must be performed by a qualified inst aller or service agency . Installation of Lennox CBWMV unit must conform with lo - cal building codes. Refe ...

  • Lennox International Inc. CBWMV - page 5

    Page 5 CBWMV SERIES tions with add−on cooling coils require field−fabricated tran- sitions that provide at least 6 inches of clearance for the CBWMV unit’s inlet/outlet water lines. See figure 2 for ex- amples. AIR FLOW AIR FLOW Figure 2 UPFLOW RIGHT HAND DISCHARGE* LEFT HAND DISCHARGE* DOWNFLOW CBWMV Multi−Positional Unit DOWNFLOW BASE * C ...

  • Lennox International Inc. CBWMV - page 6

    Page 6 505047 09/06 Return Air Opening Guidelines NOTE − Do not bring in air from the back of the unit. Return air can be brought in from the sides or bottom only . Bottom Return If the air handler is inst alled on a platform with bottom re- turn, make an airtight seal between the bottom of the air handler and the plat form to ensure that the air ...

  • Lennox International Inc. CBWMV - page 7

    Page 7 CBWMV SERIES Removing the Bottom Panel (bottom return or return air base configurations) Remove the two screws that secure the bottom cap to the air handler . Pivot the bottom cap down to release the bottom panel. Once the bottom p anel has been removed, reinstall the bottom cap. See fig- ure 5. Removing the Bottom Panel Figure 5 SCREW BO ...

  • Lennox International Inc. CBWMV - page 8

    Page 8 505047 09/06 Filter Assembly & Filters This unit is not equipped with a filter or rack. A field−pro- vided high−velocity filter is required for the unit to operate properly . T able 2 list s recommended filter sizes. A filter must be in place any time the unit is operating. T able 2 Recommended Filter Sizes Air Handler Filter Size Ai ...

  • Lennox International Inc. CBWMV - page 9

    Page 9 CBWMV SERIES Electrostatic Discharge (ESD) - Precautions And Procedures CAUTION Elect rostatic d ischarg e c an affect e lect roni c com- ponent s. T ak e p r ecautio ns d u rin g a ir h an dler i n st al- lati on a nd s er vic e to pr otec t t he a ir ha ndler ’s e lec - tron ic c o ntrol s. P recaut ion s w i ll help t o a voi d con- tr ...

  • Lennox International Inc. CBWMV - page 10

    Page 10 505047 09/06 Indoor Blower Speeds 1. When the thermost at is set to F AN ON," the indoor blower will run continuously at approximately 38% of the second−st age cooling speed when there is no cool- ing or heating demand. 2. When the CBWMV is in the heating mode, the indoor blower will run on the heating speed designated by the posi ...

  • Lennox International Inc. CBWMV - page 11

    Page 1 1 CBWMV SERIES Figure 12 T ypical CBWMV Wiring Diagram ...

  • Lennox International Inc. CBWMV - page 12

    Page 12 505047 09/06 Freezestat Operation IMPORT ANT Use of the freezest at feature is required in all instal- lations using CBWMV unit s. Th e CBWMV unit is equipped with a field-wired freezestat. The freezestat protect s the CBWMV system from freezing temperatures when the unit is installed in unconditioned areas. The factory-provided freezestat ...

  • Lennox International Inc. CBWMV - page 13

    Page 13 CBWMV SERIES Jumper Settings IMPORT ANT Before changing jumper setting, make sure the mo- tor has completely stopped. Any jumper setting change will not t ake place while the motor is run- ning. T able 4 shows the factory blower speed tap settings for CBWMV series unit s. These settings are for nominal ton- nage match−ups with the CBWMV . ...

  • Lennox International Inc. CBWMV - page 14

    Page 14 505047 09/06 T able 5 CBWMV−24B−040 Blower Performance 0 through 0.80 in. w.g. (0 Through 200 Pa) External S t atic Pressure Range ; Factory Settings: Heating S peed − 2, Cooling Speed − 1, S peed Adjust − NORM; Applications with single sided inlet s will reduce CFM by approximately 4%. ADJUST" BDC3 Jumper Speed Positions ...

  • Lennox International Inc. CBWMV - page 15

    Page 15 CBWMV SERIES T able 7 CBWMV−36C−090 Blower Performance 0 through 0.80 in. w.g. (0 Through 200 Pa) External S t atic Pressure Range ; Factory Settings: Heating S peed − 4, Cooling Speed − 3, S peed Adjust − NORM; Applications with single sided inlet s will reduce CFM by approximately 5%. ADJUST" BDC3 Jumpe r S pe ed Positio ...

  • Lennox International Inc. CBWMV - page 16

    Page 16 505047 09/06 T able 9 CBWMV−60C−120 Blower Performance 0 through 0.80 in. w.g. (0 Through 200 Pa) External S t atic Pressure Range ; Factory Settings: Heating S peed − 4, Cooling Speed − 4, S peed Adjust − NORM; Applications with single sided inlet s will reduce CFM by approximately 5%. ADJUST" BDC3 Jumpe r S pe ed Positio ...

  • Lennox International Inc. CBWMV - page 17

    Page 17 CBWMV SERIES System Adjustments Timed−ON and Timed−OFF Delays The 45−second timed−ON delay and the 30−second timed− OFF delay for heating (time that the blower operates after the heat demand has been satisfied) is not adjustable. Blower Speeds Select the blower speed by moving the pins on the variable speed control board. See fi ...

  • Lennox International Inc. CBWMV - page 18

    Page 18 505047 09/06 W ARNING W ARNING T O SER VICE PERSONS! Electric shock hazard. When electrical power to the internal control box component s must be available for troubleshooting, a common practice is to construct a by−pass" of the door interlock switch. When such a by−p ass is in place, a potential shock hazard is present which ca ...

  • Lennox International Inc. CBWMV - page 19

    Page 19 CBWMV SERIES W ARNING W ARNING T O SER VICE PERSONS! Electric shock hazard. When electrical power to the internal control box component s must be available for troubleshooting, a common practice is to construct a by−pass" of the door interlock switch. When such a by−p ass is in place, a potential shock hazard is present which ca ...

  • Lennox International Inc. CBWMV - page 20

    Page 20 505047 09/06 W ARNING W ARNING T O SER VICE PERSONS! Electric shock hazard. When electrical power to the internal control box component s must be available for troubleshooting, a common practice is to construct a by−pass" of the door interlock switch. When such a by−p ass is in place, a potential shock hazard is present which ca ...

メーカー Lennox International Inc. カテゴリー Water Heater

Lennox International Inc. CBWMVのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- CBWMVの取扱説明書
- Lennox International Inc.の製品カード
- パンフレット
- またはLennox International Inc. CBWMVの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Lennox International Inc. CBWMVの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Lennox International Inc. CBWMVの取り付け説明書、サービスマニュアル、簡易説明書、またはLennox International Inc. CBWMVのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Lennox International Inc. CBWMVの製品を使用するにあたって最も人気のある説明書を閲覧できます。

Lennox International Inc. CBWMVデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがLennox International Inc. CBWMVを使用するのを助ける技術的文書のことです。説明書は通常、全てのLennox International Inc. CBWMVユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Lennox International Inc.の取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Lennox International Inc. CBWMVの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははLennox International Inc. CBWMVの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Lennox International Inc. CBWMVに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Lennox International Inc. CBWMVデバイスの基本機能を使うにあたってのヒント。 Lennox International Inc. CBWMVのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Lennox International Inc. CBWMVに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるLennox International Inc. CBWMVのメーカー/サービスへの連絡先に関する情報。