    © Copyright, 1999, all rights reserved • Securitron Magnalock Corp., 550 Vista Blvd., Sparks NV 89434, USA Tel: (775) 355-5625 • (800) MAGLOCK • Fax: (775) 355-5636 • Website: www.securitron.com An ASSA ABLOY Group company PN# 500-13200 Rev. A.1, 10/99 SECURITRON MODEL LCP SERIES ELECTRIC LOCK CONTROL PANEL TABLE OF CONTENTS AND GUIDE TO T ...

  • Assa Abloy ELECTRIC LOCK - page 2

    Rev. A.1, 10/99 SECTION 4.3 FAIL SECURE LOCKS --------------------------------------------------------Page 10 If the locks you will be using are fail secure (sec ure when not powered), this section should be carefully read to determine the proper hook up. Figure 4 (Page 12) shows the several different ways that fail secure locks may be connected to ...

  • Assa Abloy ELECTRIC LOCK - page 3

    Rev. A.1, 10/99 Page- 1 SECURITRON LCP SERIES ELECTRIC LOCK CONTROL PANEL INSTALLATION AND OPERATING INSTRUCTIONS 1. DESCRIPTION 1.1 GENERAL The LCP series is a circuit board based family of control panels suitable for hard wired control and monitoring of electric locks. The unit can al so be used for door monitoring only (no electric locks). See s ...

  • Assa Abloy ELECTRIC LOCK - page 4

    Rev. A.1, 10/99 Page- 2 requirements vary with the monitoring scheme and the voltage but figur e a worst case of 60 mA per control zone for panel current draw. Since power supply cost is always a small percentage of the installation cost, we always recommend to not skimp on power supply capacity. We advise that the power supply be capable of drivin ...

  • Assa Abloy ELECTRIC LOCK - page 5

    Rev. A.1, 10/99 Page- 3 1.5 AUDIBLE ALARM AND ALARM RESET The red indicator is always accompanied by a Sonalert sounding on the panel. The panel operator hears the alarm, and then consults the panel face to determine the zone that has gone into violation. The violation condition is latching . Once a red indicator goes on and the Sonalert sounds, it ...

  • Assa Abloy ELECTRIC LOCK - page 6

    Rev. A.1, 10/99 Page- 4 BICOLOR ORANGE : ZONE THAT HAD BEEN IN VIOLATION HAS RESECURED. PRESSING RESET TOGGLE WILL CLEAR CONDI TION, CHANGING LAMP TO GREEN AND EXTINGUISHING SONALERT 2. OPTIONS If the panel has been supplied with any of the options listed in secti on 1.1, explanations of the options' functions are provided in the following sec ...

  • Assa Abloy ELECTRIC LOCK - page 7

    Rev. A.1, 10/99 Page- 5 It is, of course, possible to assi gn a different function to the additi onal lights. They can be made to illuminate when any sort of external switch closes. Examples could include an installation where lock status and door status are separately monitored. If it is desired that the pulsing Sonalert not accompany the illumina ...

  • Assa Abloy ELECTRIC LOCK - page 8

    Rev. A.1, 10/99 Page- 6 3. BOARD TERMINAL DESCRIPTIONS Refer to Figure 1 (Panel Board Over view) to see the terminal layout. This section describes the function of each terminal and is int ended for reference or to allow the installer to use the panel in a novel way. FIG. 1: PANEL BOARD OVERVIEW E1 E2 E3 E4 L1 L3 L4 S1 S2 S3 S4 AY Y4 Y3 Y2 Y1 A R - ...

  • Assa Abloy ELECTRIC LOCK - page 9

    Rev. A.1, 10/99 Page- 7 TERMINALS "Y1, Y2, Y3, Y4": These input terminals are only active if the AM option has been supplied. With the option, a second (yellow) LED will be mounted adjacent to the standard bicolor. When the respective "Y" terminal receives +V, the yellow LED will illuminate. This is used to annunciate any condit ...

  • Assa Abloy ELECTRIC LOCK - page 10

    Rev. A.1, 10/99 Page- 8 board. The CCS board provides multiple, current limited two Amp outputs on terminals marked P1, P2 etc. The advantage of us ing these individual outputs as s hown on the right of Figure 2 is that any short circuit in the downstream wiring will take out only one of the breakers on the CCS board and the rest of the installatio ...

  • Assa Abloy ELECTRIC LOCK - page 11

    Rev. A.1, 10/99 Page- 9 controlled by the panel zone. Not also that Securitron can supply additional breakered output boards for the power supply (part #CCB-8). If the “PB” option is supplied, (see Sections 2.2 and 5.2) power supply DC neg does not connect to the “-” terminals on the boards but rather to a flying black lead coming from the ...

  • Assa Abloy ELECTRIC LOCK - page 12

    Rev. A.1, 10/99 Page- 10 FIG. 3: FAIL SAFE LOCK CONNECTIONS MA GNA LOC K RED WHI TE BLACK TO D C NE G TO D C NE G C O M NC NO TO D C NE G "S" SEN STAT S E L S E L S E L + - FA IL S AFE LOCK SIMPLE LOCK HOO KUP WITH NO STAT US MONITO RIN G. S AN D L TER MINALS JU MPERED TOGET HER T O AVOID VIOLAT ION ALARM. TO D C NE G S E L + - FA IL S AF ...

  • Assa Abloy ELECTRIC LOCK - page 13

    Rev. A.1, 10/99 Page- 11 TYPE 3 FAIL SAFE This is the most common conf iguration. The status s witch is still present but a remote release switch such as a card reader, digital key pad, keyswitch, switch equipped panic bar, or Securitron's Touch Sense Bar is present at t he door. The lock can be released from the panel toggle or from this remo ...

  • Assa Abloy ELECTRIC LOCK - page 14

    Rev. A.1, 10/99 Page- 12 FIG. 4: FAIL SECURE LOCK CONNECTIONS TO D C NE G TO D C NE G S E L S E L + - LOCK SIMPLE LOCK HOO KUP WITH NO STAT US MONITORIN G. S AN D L T ERMINAL S JUMPER ED TOGET HER T O AVOID VIOLAT ION ALAR M. TO D C NE G S E L + CLOS ED WHEN SECURE LOCK OR DO OR STATUS SWITCH A L OCK OR DOO R STATUS SWI TCH I S ADDE D TO PRO VIDE M ...

  • Assa Abloy ELECTRIC LOCK - page 15

    Rev. A.1, 10/99 Page- 13 TYPE 1 FAIL SECURE The type 1 drawing is the simplest. It utilizes a fail secure lock controlled directly by the panel with no other release devices employed. No lock or door status monitoring switch is used. As the drawing shows, lock power comes from the E terminal and the S terminal and L terminal are jumpered together. ...

  • Assa Abloy ELECTRIC LOCK - page 16

    Rev. A.1, 10/99 Page- 14 TYPE 4 FAIL SECURE This is the same as Type 3 except that 2 remote switches are used. An example would be an entry card reader and an exit pus h button. The SPDT contacts of each remote switch are connected in NC series as shown so that the use of either switch cuts power to the status switch common extinguishing the green ...

  • Assa Abloy ELECTRIC LOCK - page 17

    Rev. A.1, 10/99 Page- 15 There are a number of things to c onsider about this drawing. The main point is to show that a powered switching device at the door should pref erably draw constant power from the LCP board power terminals (assuming the device isn’ t receiving separate power). It would be possible as an alternate method to provide power t ...

  • Assa Abloy ELECTRIC LOCK - page 18

    Rev. A.1, 10/99 Page- 16 FIG. 6: FAIL SAFE/FAIL SECURE TIMER CONNECTIONS TO D C NE G S E L LOCK + CLOSED WHEN SECURE LO C K O R D O OR STA T U S S W IT C H FAIL SE CUR E REMOTE RELEASE SWITCH C O M NO TO D C NE G C O M NC NO S E L FAIL SAF E LOCK + CLOSED WHEN SECURE LO C K O R D O OR STA T U S S W IT CH TIMEMATE TIMEMATE RED BLACK YELLO W WHI TE B ...

  • Assa Abloy ELECTRIC LOCK - page 19

    Rev. A.1, 10/99 Page- 17 "the system is working". When the release switch is used, the indicato r will go out which will prompt the individual to go through the door. If two indicators are present, one should be wir ed to the zone S terminal and the other to the zone E terminal. This creates a lamp switching effect which provides more pos ...

  • Assa Abloy ELECTRIC LOCK - page 20

    Rev. A.1, 10/99 Page- 18 The silence latch is entirely prewired. However, if the panel t hat has been supplied was ordered without a silence latch, one can be added comparatively easily in the field. The components required are an SPDT relay of the panel voltage and an illuminated normally open momentary switch with an indicator t hat also operates ...

  • Assa Abloy ELECTRIC LOCK - page 21

    Rev. A.1, 10/99 Page- 19 The locks may be immediately released by the a ssociated panel toggle. Optionally, a remote release switch may be provided at the door such as a card reader, keyswitch etc. An exit device is provided for delayed egress. Pressing the exit device starts a 15 or 30 second irrevocable delay after which the lock releases . The l ...

  • Assa Abloy ELECTRIC LOCK - page 22

    Rev. A.1, 10/99 Page- 20 Most installations do not require use of the bypa ss function. Even if t here is a local authorized entry or exit device at the door, it will often have its own timed re lay output. We believe that the LCP/XDT combination works more clearly when the bypass function is not used and therefore recommend employing the first con ...

  • Assa Abloy ELECTRIC LOCK - page 23

    Rev. A.1, 10/99 Page- 21 used. An "S" Senstat Magnalock, Touch Sense Bar and MK keyswitch are employed in place of the generic fail safe lock, initiate device and reset device. FIG. 10: LCP/XDT CONNECTION USIN G SECURITRON MAGNALOCK, TOUCH SENSE BAR, AND MK KEYSWITCH WITHOUT USE OF BYPASS FUNCTION NO NC C1 C2 C3 + LS BP FE IN RS NC NC NO ...

  • Assa Abloy ELECTRIC LOCK - page 24

    Rev. A.1, 10/99 Page- 22 FIG. 11: GENERAL LCP/XDT CONNECTIONS WITH USE OF BYPASS NO NC C1 C2 C3 + LS BP FE IN RS NC NC NO NO 0V (NE G) +V RESET (NC) INI TIAT E (N C) FA IL SA FE LOCK LOCAL ALARM MOV LCP "Y" TERMINAL DO OR /L OCK S TA T U S SWIT CH. CLO SED WHEN SEC URE. COM NC NO LCP "L " TERMIN AL LCP "E" TERMINAL LOC ...

  • Assa Abloy ELECTRIC LOCK - page 25

    Rev. A.1, 10/99 Page- 23 NO NC C1 C2 C3 + LS BP FE IN RS NC NC NO NO 0V (NE G) +V MA GN A LOC K SONA- LERT RED BLACK + TOU CH SENSE BAR RED WHT MK KEY- SWITCH WHI TE RED LED RED GREEN BLACK XDT BOARD LCP "S" TERMINAL "S" SENSTAT LCP "Y" TERMINAL COM NC NO LCP "L " TERMINAL LCP "E" TERMINAL LOCAL REL ...

  • Assa Abloy ELECTRIC LOCK - page 26

    Rev. A.1, 10/99 Page- 24 keyswitch is in the NO position. Be sure that the keyswitch contacts are of adequate capacity to switch all the power of the panel. FIG. 13: FIELD INSTALLATION OF BYPASS KEYSWITCH (FAIL SAFE LOCKS) ALTE R N ATE A C TIO N INDI CATO R SPDT KEYSWITCH C NC NO TO DC NEG E4 L4 L1 S1 L4 E4 L1 S1 OPEN PAD OPEN PAD NEXT BOARD ETC TH ...

  • Assa Abloy ELECTRIC LOCK - page 27

    Rev. A.1, 10/99 Page- 25 the bypass switch. The remote switch’s NO terminal then connects to the DC negative lock return wire so that the remote switch will release the lock by connecting the negative side even when the panel is bypassed. If there is a lock stat us sensing switch, it connects as in type 2, Figure 4. FIG. 14: FIELD INSTALLATION OF ...

  • Assa Abloy ELECTRIC LOCK - page 28

    Rev. A.1, 10/99 Page- 26 If other options are used in a master/slave insta llation, they would wire as follows: If the AM option is present, terminals Y1-Y4 would connec t together between the boards just as the S terminals do. The emergency release option (PB) would only be install ed on the master panel. The button would act to break pow er to th ...

  • Assa Abloy ELECTRIC LOCK - page 29

    Rev. A.1, 10/99 Page- 27 6.2 MULTIPLE PANEL FAIL SECURE WIRING If fail secure locks are employed and more t han one panel is needed to c ontrol them, the panel terminals are simply wired in parallel (S to S; L to L; and E to E). Eit her panel can release the lock but the same panel that released it must be used to resecure it . Both panels monitor ...

  • Assa Abloy ELECTRIC LOCK - page 30

    Rev. A.1, 10/99 Page- 28 FIGURE 16: ALTERNATELY ENABLED PANEL WIRING COM NC NO DPDT KEYSWITCH ON PANEL #1 ALTER NATE ACT ION +V FRO M POWE R SUPPLY + + + COM CONNECTS TO + T E RM INA LS ON ALL BOARDS COM NC NO DPDT KEYSWITCH ON PANEL #2 ALTER NATE ACT ION COM NC NO COM NC NO + + + COM CONNECTS TO + T E RM INA LS ON ALL BOARDS PANE L #1 PANE L #2 WI ...

  • Assa Abloy ELECTRIC LOCK - page 31

    Rev. A.1, 10/99 Page- 29 7. DOOR MONITORING (NO ELECTRIC LOCKS) The panel may also be used to monitor doors wher e no electric locks are installed. The zone toggle switch serves to arm and disarm the zone and when the zone is armed, the panel will provide a latching alarm signal when the door is opened. Often, on the same panel, some doors are used ...

  • Assa Abloy ELECTRIC LOCK - page 32

    Rev. A.1, 10/99 Page- 30 MAGNACARE ® LIMITED LIFETIME WARRANTY SECURITRON MAGNALOCK CORPORATION wa rrants that it will replace at cu stomer’s request, at any time for any reason, products manufac tured and branded by SECURITRON. SECURITRON will use its best efforts to ship a replacem ent product by next day air fr eight at no cost to the custome ...

メーカー Assa Abloy カテゴリー Door

Assa Abloy ELECTRIC LOCKのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- ELECTRIC LOCKの取扱説明書
- Assa Abloyの製品カード
- パンフレット
- またはAssa Abloy ELECTRIC LOCKの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Assa Abloy ELECTRIC LOCKの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Assa Abloy ELECTRIC LOCKの取り付け説明書、サービスマニュアル、簡易説明書、またはAssa Abloy ELECTRIC LOCKのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Assa Abloy ELECTRIC LOCKの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Assa Abloy ELECTRIC LOCKデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAssa Abloy ELECTRIC LOCKを使用するのを助ける技術的文書のことです。説明書は通常、全てのAssa Abloy ELECTRIC LOCKユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Assa Abloyの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Assa Abloy ELECTRIC LOCKの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAssa Abloy ELECTRIC LOCKの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Assa Abloy ELECTRIC LOCKに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Assa Abloy ELECTRIC LOCKデバイスの基本機能を使うにあたってのヒント。 Assa Abloy ELECTRIC LOCKのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Assa Abloy ELECTRIC LOCKに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAssa Abloy ELECTRIC LOCKのメーカー/サービスへの連絡先に関する情報。

Assa Abloy ELECTRIC LOCKについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAssa Abloy ELECTRIC LOCKの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAssa Abloy ELECTRIC LOCKで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)