    1 BMC and BMC-6X Installation and Operation Manual BMC SYSTEM A B C D Full Modulation Sequencing Control 1 2 RUN PROGRAM FOR ALL CIRCUITS 120VAC, 6A RESISTIVE OUTPUT RATINGS: 1A PILOT DUTY, 15A TOTAL 115VAC 60Hz , 30VA MAX INPUT RATINGS: USE COPPER WIRE, DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS 3 4 5 6 7 8 9 10 11 12 13 15 14 17 16 18 22 20 19 2 ...

  • Weil-McLain BMC-6X - page 2

    2 BMC and BMC-6X Installation and Operation Manual BMC LA YOUT . . . . . . . . . . . . . . . . 3 BMC OVERVIEW . . . . . . . . . . . . . . 4 Reset Ratio/Outdoor Reset . . . . . . . . . . 5 Make Sure Y ou Have the Right Control . . 6 INITIAL SETUP . . . . . . . . . . . . . . . 6 Selecting the System Features . . . . . . . 6 INST ALLA TION . . . . . . ...

  • Weil-McLain BMC-6X - page 3

    3 BMC and BMC-6X Installation and Operation Manual BMC SYSTEM A B C D Full Modulation Sequencing Control 1 2 RUN PROGRAM FOR ALL CIRCUITS 120VAC, 6A RESISTIVE OUTPUT RATINGS: 1A PILOT DUTY, 15A TOTAL 115VAC 60Hz , 30VA MAX INPUT RATINGS: USE COPPER WIRE, DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS 3 4 5 6 7 8 9 10 11 12 13 15 14 17 16 18 22 20 19 2 ...

  • Weil-McLain BMC-6X - page 4

    4 BMC and BMC-6X Installation and Operation Manual BMC OVER VIEW SEQUENCES UP T O 4 FULL Y MODULA TING ST AGES. The BMC is the perfect control whenever multiple fully modulating stages are required for hydronic heating applications. The BM C controls the on/off and the modulation of each stage to maintain precise system set point control. PID TYPE ...

  • Weil-McLain BMC-6X - page 5

    5 BMC and BMC-6X Installation and Operation Manual UNDERST ANDING OPERA TION CONCEPT The BMC has multiple operating modes that satisfy most hydronic systems. It can change the System Set Point based on outdoor temperature (Outdoor Reset) or it can modulate its stages to achieve an adjustable fixed Set Point. In Outdoor Reset, the BMC controls a ho ...

  • Weil-McLain BMC-6X - page 6

    6 BMC and BMC-6X Installation and Operation Manual MAKE SURE YOU HA VE THE RIGHT CONTROL If you need the BCP-8W to do additional tasks that either are not listed or do not know how to set them, contact W eil McLain. INITIAL SETUP Setting an Initial Program will ease the configuration of the BMC and will give the opportunity to utilize many of the ...

  • Weil-McLain BMC-6X - page 7

    7 BMC and BMC-6X Installation and Operation Manual System Run-On • This feature lets the BMC run the SYS relay for a longer period after the boilers have been turned off. When this relay is used to control a pump, it helps in dissipating the excess heat from the boilers combustion chamber . INST ALLA TION Each of the BMC or BMC-6X consists of thr ...

  • Weil-McLain BMC-6X - page 8

    8 BMC and BMC-6X Installation and Operation Manual INST ALL THE SENSORS HEA TING SYSTEM SENSOR (HSS) INST ALLA TION LOCA TING HSS • Put the Heating System sensor approximately 10' feet past the last boiler on the common supply header but before any major takeoffs. • The sensor must be located where it sees the output of all the boiler stag ...

  • Weil-McLain BMC-6X - page 9

    9 BMC and BMC-6X Installation and Operation Manual WIRING WIRING THE POWER (TERMINALS 1, 2) • Bring the 120V AC 60Hz power wires through the bottom Knockout of the enclosure. • Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring. • Connect the hot line to terminal marked L. • Connect the neu ...

  • Weil-McLain BMC-6X - page 10

    10 BMC and BMC-6X Installation and Operation Manual WIRING THE PROVE (TERMINALS 29, 30) • The Prove feature is provided to check system component operation and must be selected in the Startup Menu. See page 15. • A typical use of this feature is to check for pump flow before firing any boiler . • If the PROVE input is open on a call, the BM ...

  • Weil-McLain BMC-6X - page 11

    11 BMC and BMC-6X Installation and Operation Manual WIRING TO MODULA TING MOTORS The BMC can modulate any combination of the following motors. The Output T ype must be selected properly before connecting any output wires to avoid damage components. See Output T ype on page 1 1. WIRING THE 4-20MA MODULA TING MOTORS (A TERMINALS 13, 14), (B TERMINALS ...

  • Weil-McLain BMC-6X - page 12

    12 BMC and BMC-6X Installation and Operation Manual ----------- SETTINGS ------------ Season Winter Set Point 70 F <System Settings> <Maintenance> <Histories> <System Startup> BACK SELECT BACK SAVE ------------- SEASON -------------- Winter Summer BACK SAVE ------------ SET POINT ---------- 70 F [] --------- RESET RATIO ---- ...

  • Weil-McLain BMC-6X - page 13

    13 BMC and BMC-6X Installation and Operation Manual ----------- SETTINGS ------------ Season Winter Set Point 70 F <System Settings> <Maintenance> <Histories> <System Startup> BACK SELECT BACK SAVE ---------------- GAIN -------------- +0 F [] BACK SELECT ---------- SETTINGS 1 ---------- Gain +0 Lead Rotation Time Purge Delay ...

  • Weil-McLain BMC-6X - page 14

    14 BMC and BMC-6X Installation and Operation Manual ST ARTUP SETTINGS PROGRAM CHANGE SETTINGS T o be able to change the BMC settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure W iring Cover for security . The Enclosure W iring Cover can be securely closed using a lock. RUN PROGRAM ST ARTUP SEQUENCE Butt ...

  • Weil-McLain BMC-6X - page 15

    15 BMC and BMC-6X Installation and Operation Manual SELECTING THE MODULA TING MODE Normal, Parallel Default: Normal Button: MENU/<System Startup>/..../Modulating Mode • Some modulating boilers perform better as their modulation increases. For these units, it is advantageous to run one unit at high modulation than several units at lower modu ...

  • Weil-McLain BMC-6X - page 16

    16 BMC and BMC-6X Installation and Operation Manual SENSOR F AUL T All Off, All On Default: All On Button: MENU/<System Startup>/..../Sensor Fault The Sensor Fault will determine the operating status of all output stages that are set to Auto when a sensor reads Short or Open. BACK SAVE --------- SENSOR FAULT -------- All Off All On RESET MODE ...

  • Weil-McLain BMC-6X - page 17

    17 BMC and BMC-6X Installation and Operation Manual OPERA TING SETTINGS PROGRAM CHANGE SETTINGS T o be able to change the BMC settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure W iring Cover for security . The Enclosure W iring Cover can be securely closed using a lock. RUN PROGRAM BACK SAVE ---------- ...

  • Weil-McLain BMC-6X - page 18

    18 BMC and BMC-6X Installation and Operation Manual OUTDOOR CUTOFF TEMPERA TURE Adjustable Off, from 20 º F/ to70 º C - 100 º F , On Default: 60ºF/ 16 º C Button: MENU/Set Point/Outdoor Cutoff in Set Point Button: MENU/Set Point/Offset/Outdoor Cutoff in Reset • If the outdoor sensor is installed, the Outdoor Cutoff screen will automatically ...

  • Weil-McLain BMC-6X - page 19

    19 BMC and BMC-6X Installation and Operation Manual SYSTEM SETTINGS Button: MENU/<System Settings> The Settings 1 and Settings 2 menus provide access to adjusting and fine-tuning the system for enhanced comfort and more fuel savings. The BMC behaves dif ferently based on the selected Control Modes (see Startup Settings). BACK SELECT -------- ...

  • Weil-McLain BMC-6X - page 20

    20 BMC and BMC-6X Installation and Operation Manual LAG DELA Y Adjustable from 0min to 60min Default: 0min Button: MENU/<System Settings>/Lag Delay • The Lag Delay requires the previous stage to remain at 100% modulation for the full period of the Lag Delay before another Stage can be activated. For example, if the Lag Delay was set to 10 m ...

  • Weil-McLain BMC-6X - page 21

    21 BMC and BMC-6X Installation and Operation Manual • If Setback Input is selected as a Shutdown/T stat/Setback Mode (See page 15), the Setback will not be activated unless a Short dry contact signal is received on the Shutdown/T stat/Setback terminals ( 31 and 32 ) as a signal. • If Shutdown Input or T stat Input is selected as a Shutdown/T st ...

  • Weil-McLain BMC-6X - page 22

    22 BMC and BMC-6X Installation and Operation Manual SET TIME Button: MENU/<System Settings>/<Mor e Settings>/Set T ime Button: MENU/<System Settings>/<Mor e Settings>/<Day/Night Schedules>/Set T ime • Adjust the time by selecting T ime from the menu and then scrolling through the hours then select Save. Then, scroll ...

  • Weil-McLain BMC-6X - page 23

    23 BMC and BMC-6X Installation and Operation Manual MAINTENANCE Button: MENU/<Maintenance> The Maintenance menu gives access to sensor and outputs trimming and Soft-Off. In addition, you'll have access to view the Startup configuration settings. ALERT T o be able to change the BMC settings the Program/Run Switch must be set to Program. ...

  • Weil-McLain BMC-6X - page 24

    24 BMC and BMC-6X Installation and Operation Manual CONFIGURA TION Button: MENU/<Maintenance>/<Configuration> • This menu option provides a consolidated view of the BMC's Startup and Stage settings. BACK NEXT ------ CONFIGURATION 1 ------ v1.00c Reset F Normal Day/Night Schedules All Off BACK EXIT ------ CONFIGURATION 2 ------ A ...

  • Weil-McLain BMC-6X - page 25

    25 BMC and BMC-6X Installation and Operation Manual DISPLA Y MESSAGES The BMC normal display layout reserved the second line for message indications. The following is a list of the most common Message Display Line information: • Summer The control is set to Summer . No heat is active. See Season on page 17. • Shutdown Active The Shutdown T ermi ...

  • Weil-McLain BMC-6X - page 26

    26 BMC and BMC-6X Installation and Operation Manual Auto - The BMC will control the boiler ’ s operation to maintain the desired Set Point. Only boilers set to Auto can be Lead boilers. Standby Standby boilers can only be activated when all boilers in Auto have been at 100% modulation for a selectable period of time. Standby is generally used whe ...

  • Weil-McLain BMC-6X - page 27

    27 BMC and BMC-6X Installation and Operation Manual TROUBLESHOOTING SENSOR INPUTS Display shows Sensor OPEN or SHORT When OPEN, Check the sensor is connected and the wires are continuous to the BMC. Finally follow the procedure for Incorrect T emperature or Pressure Display . When SHOR T Remove the wires from the sensor terminals. The display shoul ...

  • Weil-McLain BMC-6X - page 28

    28 BMC and BMC-6X Installation and Operation Manual • Boiler Mode Settings - The BMC will only modulate boilers their mode is set to Auto or Standby . Check if any boiler stage is set to Manual, Off, or Standby . See Mode on page 25. Boilers are Short-Cycling • Lag Delay - Increase the Lag Delay only if all boilers tend to short-cycle. • Last ...

  • Weil-McLain BMC-6X - page 29

    29 BMC and BMC-6X Installation and Operation Manual MUL TIPLE MODULA TING BOILERS DIRECT HEA TING PIPING DIAGRAM Outdoor Sensor System Sensor 120V AC Boiler 1 Boiler 2 Boiler 3 Boiler 4 Building Heating Loop BMC SYSTEM A B C D Full Modulation Sequencing Control 1 2 RUN PROGRAM DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS 3 4 5 6 7 8 9 10 11 12 13 15 ...

  • Weil-McLain BMC-6X - page 30

    30 BMC and BMC-6X Installation and Operation Manual MUL TIPLE MODULA TING BOILERS DIRECT HEA TING WIRING DIAGRAM Boiler 1 Boiler 2 Boiler 3 Boiler 4 Boiler 1 Boiler 2 Boiler 3 Boiler 4 4 - 20 mA Signal Outputs Outdoor Sensor System Sensor Prov e Jumper Do Not remove BMC SYSTEM A B C D Full Modulation Sequencing Control 1 2 RUN PROGRAM DO NOT APPLY ...

  • Weil-McLain BMC-6X - page 31

    31 BMC and BMC-6X Installation and Operation Manual MUL TIPLE MODULA TING BOILERS EXTERNAL 4-20MA SET POINT USING 4-20MA EMS INTERF ACE Boiler 1 Boiler 2 Boiler 3 Boiler 4 Boiler 1 Boiler 2 Boiler 3 Boiler 4 4 - 20 mA Signal Outputs System Sensor Prov e Jumper Do Not remove BMC SYSTEM A B C D Full Modulation Sequencing Control 1 2 RUN PROGRAM DO NO ...

  • Weil-McLain BMC-6X - page 32

    32 BMC and BMC-6X Installation and Operation Manual SPECIFICA TIONS V oltage Input: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 V AC 60 Hz Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 V A M a x Operating T empe ...

メーカー Weil-McLain カテゴリー Boiler

Weil-McLain BMC-6Xのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- BMC-6Xの取扱説明書
- Weil-McLainの製品カード
- パンフレット
- またはWeil-McLain BMC-6Xの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Weil-McLain BMC-6Xの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Weil-McLain BMC-6Xの取り付け説明書、サービスマニュアル、簡易説明書、またはWeil-McLain BMC-6Xのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Weil-McLain BMC-6Xの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Weil-McLain BMC-6Xデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがWeil-McLain BMC-6Xを使用するのを助ける技術的文書のことです。説明書は通常、全てのWeil-McLain BMC-6Xユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Weil-McLainの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Weil-McLain BMC-6Xの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははWeil-McLain BMC-6Xの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Weil-McLain BMC-6Xに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Weil-McLain BMC-6Xデバイスの基本機能を使うにあたってのヒント。 Weil-McLain BMC-6Xのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Weil-McLain BMC-6Xに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるWeil-McLain BMC-6Xのメーカー/サービスへの連絡先に関する情報。

Weil-McLain BMC-6Xについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもWeil-McLain BMC-6Xの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがWeil-McLain BMC-6Xで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)