    A THENA CONTROLS, INC. 5145 Campus Drive Plymouth Meeting P A 19462 U.S.A. T el: (610) 828-2490 Fax: (610) 828-7084 AthenaControls.com Contr oller Indicator T ransmitter 1 / 32 DIN - 48 x 24 C10 line c c User manual • M.I.U.C10-1/02.06 • Cod. J30-478-1AC1 SEA U L C US LISTED ...

  • Athena Technologies C10 - page 2

    Contr oller Indicator T ransmitter 1 / 32 DIN - 48 x 24 C10 line c c 274.8 U L C US LISTED ...

  • Athena Technologies C10 - page 3

    2 information c c N OTES ON ELECTRIC SAFETY AND ELECTROMAGNETIC COMP A TIBILITY . Please, read car efully these instructions befor e proceeding with the installation of the controller . Class II instrument, rear panel mounting. This controller has been designed with compliance to: Regulations on electrical apparatus (appliance, systems and installa ...

  • Athena Technologies C10 - page 4

    3 T able of contents T ABLE OF C ONTENTS 1 I NST ALLA TION ........................................................................................................................... Page 4 2 E LECTRICAL CONNECTIONS ..................................................................................... Page 8 3 P RODUCT CODING ....................... ...

  • Athena Technologies C10 - page 5

    4 1 - Installation 1 INST ALLA TION Installation must only be carried out by qualified personnel. Before pr oceeding with the instal- lation of this controller , follow the instructions illustrated in this man- ual and, particularly the installation precautions marked with the B symbol, related to the Eur opean Community directive on electrical pro ...

  • Athena Technologies C10 - page 6

    5 1 - Installation 1.2 DIMENSIONAL DET AILS 48 mm 1.89 in 25 mm 0.99 in 120 mm 4.72 in 20 mm max 0.79 in max 1.3 P ANEL CUT -OUT 65 mm min 2.56 in min 42 mm min. 1.65 in min. 22.2 +0.3 mm 0.87 +0.01 in 45 +0.6 mm 1.78 +0.023 in ...

  • Athena Technologies C10 - page 7

    6 1 - Installation Special conditions M Altitude > 2000 m T T emperatur e >50°C %Rh Humidity > 95 % P Conducting atmosphere Use filter W arm up Use forced air ventilation Use 24V ~ supply version Suggestions Forbidden Conditions D C Corrosive atmospher e E Explosive atmosphere Operating conditions M Altitude up to 2000 m T T emperatur e 0 ...

  • Athena Technologies C10 - page 8

    7 1 - Installation 1.5.1 INSERT THE INSTRUMENT 1 Prepar e panel cut-out 2 Check front panel gasket posi- tion 3 Insert the instrument through the cut-out 1.5 P ANEL MOUNTING 1.5.2 INST ALLA TION SECURING 1 Position the mounting clamps 2 Push the mounting clamps towards the panel surface to secure the instrument 1 3 2 1.5.3 CLAMPS REMOVING 1 Insert ...

  • Athena Technologies C10 - page 9

    8 2 - Electrical connections 2 ELECTRICAL CONNECTIONS 2.1 TERMINA TION UNIT B 12 screw terminals Option terminals Holding screw 0.5 Nm Positive screw driver PH1 Negative screw driver 0,8 x 4 mm Recommended wire terminal leads Pin connector q 1.4 mm - 0.055 in max Ø Fork-shape AMP 165004 Ø 5.5 mm - 0.21 in L Stripped wire L 5.5 mm - 0.21 in 1234 5 ...

  • Athena Technologies C10 - page 10

    9 2 - Electrical connections PRECAUTIONS B Despite the fact that the instrument has been designed to work in an harsh and noisy environmental (level IV of the industrial standard IEC 801-4), it is strongly r ecom- mended to follow the following suggestions. A All the wiring must comply with the local regulations. The supply wiring should be rout- e ...

  • Athena Technologies C10 - page 11

    10 2 - Electrical connections 2.3 TYPICAL INSTRUMENT WIRING B 6 V ~ Supervisory Supply V ~ V ~ Retransmission 4…20mA L N DC voltage Thermocouple Current 2.5 Ω external shunt resistor Coil of the load contactor Fuse Power supply switch OP2 OP1 V ~ Fuse 0.2 A T 18V Pt100 2 wire transmitter Load Solid state relays PV 5 4 3 2 1 12 11 10 9 8 7 A B B ...

  • Athena Technologies C10 - page 12

    11 2 - Electrical connections 2.3.1 POWER SUPPL Y B Switching power supply with mul- tiple isolation and internal fuse • Standard version: nominal voltage: 100 - 240V ~ (- 15% + 10%) Frequency 50/60Hz • Low V oltage version: Nominal voltage: 24V ~ (- 25% + 12%) Frequency 50/60Hz or 24V– (- 15% + 25%) • Power consumption 1.6W max 0.2A includ ...

  • Athena Technologies C10 - page 13

    12 2 - Electrical connections 2.3.4 PV CONTROL INPUT B • Connect the wires with the polarity as shown • Use always compensation cable of the correct type for the ther- mocouple used • The shield, if present, must be connected to a proper earth. • If a 3 wires system is used, use always cables of the same diameter (1mm 2 min.) (line 20 Ω / ...

  • Athena Technologies C10 - page 14

    13 2 - Electrical connections 2.3.5 OP4 OUTPUT (option) B 2.3.6 SERIAL COMMUNICA TIONS (option) B PV retransmission • Galvanic isolation 500V ~ /1 min. • 0/4...20mA, 750 Ω / 15V– max • Galvanic isolation 500V ~ /1 min • Compliance to the EIA RS485 standard for Modbus/Jbus A Please, read the user instructions on the “C10 controller MOD ...

  • Athena Technologies C10 - page 15

    14 3 - Product coding 3 PRODUCT CODING The complete code is shown on the instrument label. The informa- tions about product coding ar e accessible from the fr ont panel by mean of a particular procedur e described at section 4.2.2 page 19 3000 L C D M N B P/N S/N V ~ (L-N) : 100 ÷ 240V 50/60 Hz - 1.6W ; C10-3000-0300 : A0A-9809/0013 Made in Italy ...

  • Athena Technologies C10 - page 16

    15 3 - Product coding Option 1 D Option 2 Not provided 0 Not provided 6 T ransmitter Power Supply (PS) RS485 Modbus/Jbus protocol 0 Not provided 6 T ransmitter Power Supply C 0 0 5 5 Option 3 E Not provided 0 Front Bezel Color [2] G Dark Grey (standar d) 0 Beige 1 Output 1 [1] B Relay 0 T riac 3 Power supply A 100 - 240V ~ (-15% + 10%) 3 24V ~ (-25 ...

  • Athena Technologies C10 - page 17

    16 3 - Product coding 3.2 CONFIGURA TION CODING The configuration code consists of 4 digits that identify the operat- ing characteristic of the controller , as chosen by the user . Section 4.5 at pag. 26 reports the instructions how to set a new con- figuration code. The configuration code can be dis- played on the front panel, follow- ing the inst ...

  • Athena Technologies C10 - page 18

    17 3 - Product coding A If, when the controller is pow- ered up for the first time, the dis- play shows the following mes- sage it means that the controller has not been configured yet. The controller r emains in stand-by until the configuration code is set correctly (see chapter 4.6 pag 26). Alarm 2 type and function N Not active 0 Sensor break al ...

  • Athena Technologies C10 - page 19

    18 4 - Operations 4 OPERA TIONS 4.1 KEYP AD COMMANDS AND DISPLA Y V alues modification Enter key for selection and value setting confirmation Menu access OP1 output ON (red) OP2 output ON (red) T uning in progr ess (green) • PV contr ol input (operator mode) (in engineering units) when the measured value is greater than sensor high range when the ...

  • Athena Technologies C10 - page 20

    19 4 - Operations 4.2 DISPLA Y When the display operation is selected, the controller pr esents automatically all the most impor- tant parameters and configuration information. During the operation, the para- meters values cannot be modi- fied by the user After 2 sec from the end of the operation, the controller flashes the display and returns to t ...

  • Athena Technologies C10 - page 21

    20 4 - Operations Operator mode Current setpoint display Setpoint modification Setpoint entry . The operation is acknowledged by one flash of the display . 274.8 275.0 230.0 240.0 240.0 4.3 P ARAMETER SETTING Press S or G momentarily to change the value of 1 unit every push Continued pressing of S or G changes the value, at rate that doubles every ...

  • Athena Technologies C10 - page 22

    21 4 - Operations Engineering Units Degree Centigrade Degree Fahrenheit no units defined Degree Fahrenheit Ph Unit °C °f none °f ph 4.3.2 MNEMONIC CODES SETTING (e.g. configuration see pages 26, 27) Press the S or G to display the next or previous mnemonic for the selected parameter . Continued pressing of S or G will display further mnemonics a ...

  • Athena Technologies C10 - page 23

    22 4 - Operations 4.4 P ARAMETER SETTING A The parameter setting procedur e has a timeout. If no keys are pressed for , at least, 30 seconds, the controller switches back, auto- matically , to the operator mode. After having selected the parame- ter or the code, press S and G to display or modify the value (see pag. 20) The value is entered when th ...

  • Athena Technologies C10 - page 24

    23 4 - Operations rt.Hi hy. O.C. Op. H sl. u sl. d s.p. l s.p. H AIhy tune t.fil In.sh Addr rt.lo pass A2hy P 1:00 P 100:0 P 0:5 P 0:5 P 0:5 P Off P Off P In.s P cala P Off P 0 P 1 P In.s P cala P F. s P cala P F. s P cala P L. r P ange P L. r P ange P H. r P ange P H. r P ange Overshoot control (PID algorithm only) 0.01…1.00 Control output high ...

  • Athena Technologies C10 - page 25

    24 4 - Operations 4.5 P ARAMETER 1st GROUP The controller parameters have been or ganized in group, accor d- ing to their functionality area. AL1 alarm threshold The threshold is pr esented only if the controller have been configur ed with 2 alarms. ( Digit L of the con- figuration code assigned to 4 or 5) AL2 alarm threshold The alarm occurrences ...

  • Athena Technologies C10 - page 26

    25 4 - Operations effectiveness of the PID algorithm. Setting 1, the overshoot control is disabled. Control output high limit It specifies the maximum value the control output can be set Control output hysteresis Control output hyster esis span, set in % of the full scale. 2nd GROUP Setpoint ramp up Setpoint ramp down This parameter specifies the m ...

  • Athena Technologies C10 - page 27

    26 4 - Operations 4.6 CONFIGURA TION The configuration of the controller is specified through a 4 digit code that defines the type of input, of control output and of the alarms. (sect. 3.2 pag16) Other parameters specifie the type of auxiliary functions. Press S or G to display the next parameter or the next code and change its value. The new value ...

  • Athena Technologies C10 - page 28

    27 4 - Operations Note Pressing the Q the next gr oup of parameters is displayed. [1] T able of the supported Engineering Units. * For inputs from thermocouple or r esistance thermometer , the choice is between °C and °F only . [2] Range of min 100 digits. [3] If password is 0000 to 4999, parameter set- ting will be available to the operator with ...

  • Athena Technologies C10 - page 29

    28 5 - Automatic tune 5 AUTOMA TIC TUNE Start/stop of the Fuzzy T uning The T uning operation can be started or stopped any time. The green led 3 goes on when the Fuzzy T uning is in progr ess. At the end of this operation, the calculat- ed PID terms parameter are stor ed and used by the control algorithm and the controller goes back to the operato ...

  • Athena Technologies C10 - page 30

    29 6 - T echnical specification 6 TECHNICAL SPECIFICA TIONS Common characteristics A/D converter with resolution of 50.000 points Update measurement time: 0.2 seconds Sampling time: 0.5 seconds Input bias: - 60…+ 60 digit Input filter with enable/disable: 1…30 seconds Accurac y 0.25% ± 1 digits for temperature sensors 0.1% ±1 digits (for mV) ...

  • Athena Technologies C10 - page 31

    30 6 - T echnical specification Features (at 25°C enviromental temp.) Operating mode and Outputs Control Mode OP1 output OP2 output AL1 alarm (indicator with 2 alarms) AL2 alarm Description 1 PID loop or 1 ON-OFF loop with 1 Alarm Indicator with 2 alarms Algorithm PID with overshoot control or ON OFF Hysteresis 0.1…10,0% c.s. Proportional band ( ...

  • Athena Technologies C10 - page 32

    Approvals 31 6 - T echnical specification Features (at 25°C enviromental temp.) Setpoint OP4 PV retransmission (option) One shot Fuzzy-T uning with automatic selection Serial comm. (option) Auxiliary Supply Operational safety General characteristics Description Ramp up and down Low limit High limit Galvanic isolation : 500 V ~ /1 min Resolution 12 ...

  • Athena Technologies C10 - page 33

    32 warranty 1 W ARRANTY W e warrant that the pr od- ucts will be fr ee from defects in material and workmanship for 3 years fr om the date of delivery . The warranty above shall not apply for any failur e caused by the use of the pr oduct not in line with the instructions r eported on this manual. CSG srl • New Media Communications • www.csg-ne ...

  • Athena Technologies C10 - page 34

    33 Main universal input Digital input Thermocouple Isolated contact RTD (Pt100) NPN open collector Delta T emp (2x RTD) TTL open collector mA and mV Setpoint Custom Local Frequency Stand-by Auxiliary input Keypad lock Current transformer Outputs lock mA Remote setpoint Start-up function V olt Remote setpoint Timer function Feedback potentiometer Me ...

メーカー Athena Technologies カテゴリー Satellite Radio

Athena Technologies C10のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- C10の取扱説明書
- Athena Technologiesの製品カード
- パンフレット
- またはAthena Technologies C10の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Athena Technologies C10の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Athena Technologies C10の取り付け説明書、サービスマニュアル、簡易説明書、またはAthena Technologies C10のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Athena Technologies C10の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Athena Technologies C10デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAthena Technologies C10を使用するのを助ける技術的文書のことです。説明書は通常、全てのAthena Technologies C10ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Athena Technologiesの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Athena Technologies C10の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAthena Technologies C10の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Athena Technologies C10に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Athena Technologies C10デバイスの基本機能を使うにあたってのヒント。 Athena Technologies C10のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Athena Technologies C10に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAthena Technologies C10のメーカー/サービスへの連絡先に関する情報。

Athena Technologies C10についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAthena Technologies C10の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAthena Technologies C10で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)