    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificat ions or des igns without notice an d withou t inc urring obligations. PC 111 Catalog No . 533-8 0072 Pr inted in U.S .A. Form 3 8-54SI Pg 1 11-0 2 Replaces : 38-52 SI Book 1 4 Ta b 3 a 2 a Installation, Star t-Up and Configur ation Instr uctions P ar t Number ...

  • Carrier 33CSPREMLK - page 2

    2 Carrier ’ s diagnostic standard tier display tools such as Navigator or Scrolling Marquee can be used with t he Premier- Link controller . A cce ss is available via an RJ-11 connection or a 3-wire connection to the communication bus. User interfac es available for use with the CCN system are PC ’ s equipped with Carrier user interface softwar ...

  • Carrier 33CSPREMLK - page 3

    3 PremierLink Contr oller Inputs and Outputs — The PremierLink controller inputs and outputs are shown in T able 1. Contr ol Wiring — The PremierLi nk controller can be connected to either a Carrier-approved therm ostat or CCN compatible tempe rature sensor . 1. T urn of f pow er to the cont rol bo x. 2. Strip the ends of the red, white, and bl ...

  • Carrier 33CSPREMLK - page 4

    4 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AK, AKS, ARZ, ARS T erminal Board (TB) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 CCR 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C W2 R Y ...

  • Carrier 33CSPREMLK - page 5

    5 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38ARD T erminal Board (TB) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C W2 R Y1 Y2 W1 G C X LLSV ...

  • Carrier 33CSPREMLK - page 6

    6 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AH T erminal Board (TB2) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C 4 5 3 2 1 RED RED BRN GR ...

  • Carrier 33CSPREMLK - page 7

    7 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RMQ Connections CR W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C 38AQ007 Control Connections CR R O W BL Y RED R ...

  • Carrier 33CSPREMLK - page 8

    8 Table 1 — PremierLink Controller Inputs and Outputs LEGEND INPU TS PO WER TERMINAL (S) SP ACE TEMPERA TU RE (SPT ) AI (10K Ther mistor) J6-7, J6-6 SET POINT ADJUSTMENT (ST O) AI (10K Ther mistor) J6-5, J6-6 SUPPL Y AIR TEMPERA TURE (S A T) AI (10K Ther mistor) J6-3, J6-4 OUTDOOR AIR TEMPERA TURE (O A T) AI (10K Ther mistor) J6-1, J6-2 IA Q SENS ...

  • Carrier 33CSPREMLK - page 9

    9 Table 2 — Color Code Recommendatio ns Inst all Sens or s ( See Fig. 3-10 ) — The Premi erLink™ controller can be used with ei ther the T 58 Communicating sen- sor or any combination of CO 2 and space tem perature sensors . Refer to the instructions supplied with each sensor for electrical requirements. NOTE: All sensors are f ield-installed ...

  • Carrier 33CSPREMLK - page 10

    10 Table 3 — Thermistor Resista nce vs Temp erature Values for Spa ce Tempera ture Sen sor, Supply Air Temperature Sens or, and Outdoor Air Temperature Sen sor SUPPL Y AIR TEMPE RA T URE (SA T ) SENSOR INST AL- LA T IO N — T he 33ZCSENSA T supply air temperat ure sensor is required for controller operation. The sensor consists of a thermistor e ...

  • Carrier 33CSPREMLK - page 11

    11 Perform the following steps if state or local code requires the use of conduit, or if your installation requires a cable length of more than 8 ft: 1. Secure the probe to the duct with two field-supplie d self- drilling screws. 2. If you are extending cable length beyond 8 ft, use plenum rated, 20 A WG, twisted pair w ire. 3. Connect the sensor l ...

  • Carrier 33CSPREMLK - page 12

    12 J6 6 7 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 J6 6 7 RED BLK RED BLK SENSOR 2 SENSOR 1 RED RED BLK SENSOR 3 SENSOR 4 BLK BLK RED RED RED BLK BLK SENSOR 8 SENSOR 9 SENSOR 5 RED BLK SENSOR 6 SENSOR 7 BLK RED SP A CE TEMPERA TURE A VERA GING — 4 SENSOR APPLICA TION SP AC E TEMPERA TURE A VERAGING — 9 SENSOR ...

  • Carrier 33CSPREMLK - page 13

    13 LE GEND Fig. 7 — Pre mierLink ™ Controller and Sensor Wiring — 33ZCT55S PT, 33ZCT56S PT, 33Z CT58SPT Space Temperature Se nsors; 33ZCSENSAT Supply Air Tempera ture Sensor; 33ZCSENCO2 (Outdoor), and 3 3ZCT55CO2, 33ZCT56CO2 (Indoor) Air Quality Sensors OA T — Outdoor Air T emperature Sensor SA T — Supply Air T emperature Sensor SPT — S ...

  • Carrier 33CSPREMLK - page 14

    14 Fig. 8 — PremierLink ™ Co ntrolle r Wiring — Combination Temperature and CO 2 Sensor — 33ZCT55C O2, 33 ZCT56CO2 NO TE: No wire is connected to c onnector J-5 pin 4. Y ou must relocat e a wire from an unused ter minal. T ypically one of the red wires from c onnector J-4 may be used for this purpos e. This pin on J-5 provided 24 VDC po wer ...

  • Carrier 33CSPREMLK - page 15

    15 NO TE: Remov e all un used red wires from J4 connector to pre v ent 24 v ac shor ting other components or ground. Inputs on J4 are 24 v ac. Red leads are voltage source. Fig. 9 — Pre mierLin k ™ Controller Sensor Wiring — With Programmable or Non-P rogrammable Thermostat ...

  • Carrier 33CSPREMLK - page 16

    16 NO TE: Remov e red wire f rom J4-9 to pre v ent 24 v ac shor ting out other components or ground. Inputs on J4 are 24 v ac. Red leads a re voltage source. Fig. 10 — Premie rLink ™ Field-Installed Controller Sensor Wiring — Discrete Input ...

  • Carrier 33CSPREMLK - page 17

    17 Fig. 11 — Typical Mounting Location for Supply Air Tempera ture (SAT) Sensor On Split Sys tem Units 8 7 6 5 4 32 1 2 1 HG 24 V AC OR 24 VDC NC ALARM RELA Y CONT ACTS COM NO } 0-10VDC SIG COM (J5-3) 4-20mA (J5-2) + + - + - Fig. 12 — Outdoor Air Quality (CO 2 ) Sensor (33ZCSENCO2) — Typical Wiring Dia gram Fig. 13 — Outdoor Air Quality Sen ...

  • Carrier 33CSPREMLK - page 18

    18 Connect to CCN Com m unication Bus — The PremierLink™ controller connects to the bus in a d aisy chain arrangemen t. Negative pins on each component m ust be connected to respective negative p ins and likewise positive p ins on each component must be connected to respective positive pins. Th e contro ller s ignal pins mu st be w ired t o the ...

  • Carrier 33CSPREMLK - page 19

    19 Mounting — Mount the enthalpy switch/receiver in a location where the outdoor air can be sampled (such as the outdoor air intake). The entha lpy switch/receiver is not a NEMA 4 encl o- sure and should be mounted in a location that is not exposed to outdoor elements such a s rain or snow . Use two f ield-supplied no. 8 x 3 / 4 -in. TEK screws. ...

  • Carrier 33CSPREMLK - page 20

    20 Connect the 4-20 mA In terminal on the enthalpy switch/ receive r to the 4 -20 m A Ou t ter minal o n the ret urn air enth alpy sensor . Connect t he 24-36 VDC Out terminal on the enthalpy switch/rece ive r to the 24-36 VD C In t erminal on the return ai r enthalpy sensor . See Fi g. 21. Enthalpy Switch/Reciever Jump er Settings — There are tw ...

  • Carrier 33CSPREMLK - page 21

    21 W iri ng Enthalp y Sensors — T o wire the enthalpy sensor, per- form the following (see Fig. 24 a nd 25): NOTE: T o mount outdoor air sensor remotely , remove it from back of enthalpy control and follow steps 3 and 6. 1. Use a 2-conductor, 18 or 20 A WG, twis t ed pair cable to connect the return air enthalpy sensor to t he differential enthal ...

  • Carrier 33CSPREMLK - page 22

    22 Q7 6 9 B — Be cause the Honeyw ell adapter is de signed for a negative 4 to 20 mA input instead of a positive signal, the Q769B adapter requires a separate transformer a nd a current loop isolator to perform properly . C onnecting th e adapter directly to the PremierLin k controller could caus e the 4 to 20 mA outpu t on the contr oller to be ...

  • Carrier 33CSPREMLK - page 23

    23 NOTE: If Pr em ier Lin k ™ Cont roller is grounded and actuator is grounded on common side , then common wire from PremierLink controller J9-2 is not needed. Fig. 25 — PremierLink Controller Wi ring — Differential Enthalpy Con trol (33AMKITEN T000) ...

  • Carrier 33CSPREMLK - page 24

    24 Economizer wit h Johnson 4 to 20 mA Actua - tor — The PremierLink Controller can be connected to an economizer that us es a Johnso n 4 to 20 mA actuato r . DR I V E DI R E C T I ON — The actua tor drive direction is dependent upon the position of Switch 3 a nd the spring return direction. See T able 5. The actuator i s factory set for Direct ...

  • Carrier 33CSPREMLK - page 25

    25 Output 20 VDC at 25 mA Feedback 0 (2)-10 or 6-9 VDC Input 0 (2)-10 or 6-9 VDC, 0 (4)-20 mA 24 V AC/VDC COM (3) (5) (4) (2) (1) J9-1 TO 24V TRANSFORMER Gray White/Red Red Y ellow White WIRE HARNESS FROM ACTUA TOR ACTUA TOR 50TJ400812 M9206-GGC-2 ECONOMIZER 12-PIN HARNESS RED 24 V AC 1 2 3 4 5 BRN TRANSFORMER GROUND 6 7 8 9 10 11 12 PNK PL6 4-20mA ...

  • Carrier 33CSPREMLK - page 26

    26 ST ART -U P Use the Carri er network communica tion software to start up and configure the Prem ierLink™ controller . Changes can be made using the ComfortWORKS ® soft- ware, ComfortVIEW™ software, or N etwork Service T ool. The Network Se rvice T ool is a port able interface device that allows the user to change system set-up and set point ...

  • Carrier 33CSPREMLK - page 27

    27 keys which are the up arrow ( ), down arrow ( ), and keys. IN S T A L L A T I O N — The Navigator display module is intend- ed to be a mobile device, so the re are no holes in the device for permanent mounting. T he module has a magnetic mount that is strong enough to hold the device in place on any clea n, dry metal surf ace. T o enter LEN (l ...

  • Carrier 33CSPREMLK - page 28

    28 T o access the sub-mode to change the Unocc upied OA T Lockout Setpoint, press the down arrow to scroll down until the Navigator™ module display reads: SETP OA TL >NTLO UHDB T o view an expansion of the sub-mode, press the and keys simultaneously and the Navigator will display: >NTLO UNOCC. OA T LOCKOUT TEMP The Navigator will rema in in ...

  • Carrier 33CSPREMLK - page 29

    29 Tab le 7 — Points Displ ay NO TE: Bold values i ndicate points that can be f orced through communications. SU P P L Y F AN ST A TU S — T his point displa ys the S upply Fan status if controller is configured to receive input from the Supply Fan. Otherwise this point will display the output state of the Supply Fan Relay . This mode ca n only ...

  • Carrier 33CSPREMLK - page 30

    30 HE A T S T A G E 2 — T he Heat Stage 2 point provide s the state of the Heating 2 output. Heating Stage 2: Display Units: Discrete ASCII Default V a lue: Off Display Range: Off/ On Network Ac cess: Read Only HEA T ST AGE 3, EXHAUST F AN , OR REVERSING V A L V E — This point di splays the commanded state of auxi l- iary output. This output ca ...

  • Carrier 33CSPREMLK - page 31

    31 Table 8 — Thermostat Control Input Display AL A R M RE - A L A R M T I M E — This decision i s used to con- figure the number of minutes that will elapse bet ween re-alarms. A re-al arm occurs when the conditi on that caused the initial alarm continues to persist for the number of mi nutes specified. Re-alarming continues to occur a t the sp ...

  • Carrier 33CSPREMLK - page 32

    32 DU R A T I O N — The Duration field indica tes how long the holiday will last (in days). Duration: Range: 0 to 365 Default V a lue: 0 As an example, i f a Holiday is configured for M onth 2, Day 5, Duration 2, then the Holiday will start February 5 and end February 7. Table 11 — Holiday Configuration Occupancy Configurat ion Screen — Th e ...

  • Carrier 33CSPREMLK - page 33

    33 UNOCCUPIED HIGH — The Un oc cu pie d H igh se t po in t d e- scribes the high temperat ure limit of the space during Unoccu- pied mode. Unoccupied High: Units: Degrees F (D egrees C) Range: 45.0 to 99.9 Default V alue: 90.0 HIGH OA T LIMIT FOR IAQ PRE-OCCUP ANC Y PU R G E — The High OA T unit for IAQ Pre-Occupancy Purge function determines t ...

  • Carrier 33CSPREMLK - page 34

    34 Table 14 — Service Configuration Selection ST AG ED C OOLING — The s t a g in g fun c t i on i s us e d f o r D X cooling (1 or 2 stages). The sta ging function uses the cooling submaster reference from the PID and c ompares the value to the supply air temperature to calculate the required number of output stages to energize. T ime Guard del ...

  • Carrier 33CSPREMLK - page 35

    35 The integral gain affects the PID calcula tion; an increa se will ma ke the IAQ submaste r referenc e change greater as t he error in indoor air quality increases. The integral gain should be selected to eliminate proportional droop without over shoot. Enter the desired integral gain for the Indoor Air Qualit y con- trol algorithm. The Derivativ ...

  • Carrier 33CSPREMLK - page 36

    36 The DXCTLO should be turned OFF (to ignore the DXLOCK setpoint) in applications where there is either no OA T sensor (local or broadcast) or t he OA T sensor has failed. For V ersion 1 .3 — If there is a valid OA T sensor reading and DXCTLO is set t o “OFF”, compressor cool ing wi ll NOT be allowed. Please note that t his functionality was ...

  • Carrier 33CSPREMLK - page 37

    37 PremierLink ™ Configurati on Screen — The PremierLink Configuration screen al low s the user to configure all functions. See T a ble 15. OP E R A T I N G M O D E — The Ope rat ing Mode function determines the operating mode of the PremierLink controller . There are two operat ing modes from wh ich to choose: TST A T and CCN Sensor . The TS ...

  • Carrier 33CSPREMLK - page 38

    38 GLOBAL SC HEDULE BROADC AST — The Gl obal Sc hed- ule Broadcast setting confi g ures the controller t o broadcast or receive a global schedule. If se t to Y es, the controller will a ct as a global schedule master and its schedule will be broadcast to the CCN. If set t o No, the c ontroller will not broadcast a global schedule and it wi ll rec ...

  • Carrier 33CSPREMLK - page 39

    39 Low Refere nce spe cif ies Low Poin t of the Out door IAQ Sensor Range in ppm. Low Reference: Uni ts: PPM (parts per million) Range: 0 to 5000 Default V a lue: 0 High Reference specifies High Point of the Outdoor IAQ Sensor Range in ppm. High Reference: Units: PPM (parts per million) Range: 0 to 5000 Default V alue: 2000 OUTDOOR AIR QUALITY LOCK ...

  • Carrier 33CSPREMLK - page 40

    40 NEXT UNOCCUPIED DA Y — Th e N e xt Un o ccu pi e d Da y point displays the day of w eek when the next unoccupied peri- od will begin. This point is used with the Next Unoccupied T ime so the user will know when the next unoccupied period will occur . If the controller is fol lowing a global schedule t his point will remain at defaul t. Next Un ...

  • Carrier 33CSPREMLK - page 41

    41 IAQ PRE-OCCUP ANCY PURGE — Ind i ca tes tha t the pr e- occupancy purge mode is currently act ive. IAQ Pre-occupancy Purge: Display Range: No/Y es Default V a lue: No Netwo rk Ac cess: Read Only UNOCCUPIED FREE COOLING — In d i ca t e s th a t unoccu- pied free cooling is i n effect. Unoccupied Free Cooling: Display Range: No/Y es Default V ...

  • Carrier 33CSPREMLK - page 42

    42 The A verage O ccupied Hea t Set Point displays t he Occupied Heat set point from the Linkage The rmostat. A verage Occupi ed Heat Set Point : Di splay Un its: Degrees F (Degrees C) Display Range: 0.0 to 99.9 Default V alue: 0.0 Network Access: None The A v erage Occupied Cool Set Point displays the Occu- pied Cool set point from the Linkage The ...

  • Carrier 33CSPREMLK - page 43

    ...

  • Carrier 33CSPREMLK - page 44

    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d wit hout inc urring obligations. PC 111 Catalog No . 53 3-80072 Pr inted in U.S .A. Form 3 8-54S I P g 44 1 1-02 Rep laces: 38 -52S I Book 1 4 Ta b 3 a 2 a Copyright 20 02 Car rier Cor po ration ...

メーカー Carrier カテゴリー Air Conditioner

Carrier 33CSPREMLKのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 33CSPREMLKの取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier 33CSPREMLKの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier 33CSPREMLKの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier 33CSPREMLKの取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier 33CSPREMLKのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier 33CSPREMLKの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Carrier 33CSPREMLKデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier 33CSPREMLKを使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier 33CSPREMLKユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier 33CSPREMLKの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier 33CSPREMLKの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier 33CSPREMLKに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier 33CSPREMLKデバイスの基本機能を使うにあたってのヒント。 Carrier 33CSPREMLKのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier 33CSPREMLKに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier 33CSPREMLKのメーカー/サービスへの連絡先に関する情報。

Carrier 33CSPREMLKについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCarrier 33CSPREMLKの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCarrier 33CSPREMLKで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)