  • Carrier AQUAZONE 50RLP - page 1

    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificat ions or des igns without notice an d withou t inc urring obligations. PC 111 Catalo g No. 535-00077 Prin ted in U.S.A. F or m 50RLP -1SI Pg 1 1-03 Replaces: New Book 1 4 Ta b 5 a 5 a Installation Instr uctions CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . ...

  • Carrier AQUAZONE 50RLP - page 2

    2 The Aquazone™ System Control Panel is a single packaged system control panel for use with Aquazone water source heat pumps (WSHPs ) in stand-alone or di rect digital control applications using the Carrier Comfort Network (CCN). The Aquazone system control panel controls and monitors the operation of the water source heat pumps, the ancillary he ...

  • Carrier AQUAZONE 50RLP - page 3

    3 If variable frequency d r ives are utilized for system pumps, no pump control relays are spec ified. Each relay contains a r ed light-emitting diode (LED), which indicates the relay coi l is energized. The pump control relays are located in the upper left hand corner of the system control panel. See Fig. 4. W iring is shown in Fig. 5A-5C. Specifi ...

  • Carrier AQUAZONE 50RLP - page 4

    4 WSHP 2 WSHP 1 D.C. L.S. CC6400 T .B. M T R MCP LCP CARRIER COMFORT NETWORK BLDG. PREMIERLINK WSHP CONTROLLER PREMIERLINK WSHP CONTROLLER AQUAZONE SYSTEM LOOP CONTROL P ANEL (CARRIER COMFORT CONTROLLER) MASTER CONTROL P ANEL (CARRIER COMFORT CONTROLLER) REPEA TER: INTERF ACE PC TO NETWORK TELINK WITH MODEM CONTROLLER DA T A COLLECTION LOADSHED COM ...

  • Carrier AQUAZONE 50RLP - page 5

    5 Pum p 1 Pum p 2 Cool Sta g es 1 Cool Sta g es 2 Heat Sta g es 1 Heat Sta g es 2 T ransfo rm e r 1 Transf orm er 2 Tr an s fo r me r 3 Processor Input/Outpu t 1 Input/Outpu t 2 Low Volta g e Zo ne T he rm ostat Control R ela y s HOA INPUT TYPE UCS-421 MODE FLT SEQ MODE FLT SEQ A B C D MA V CH H3 H4 H5 A B C D 24V POWER COMMON SIGNAL INPUT CHAIN OU ...

  • Carrier AQUAZONE 50RLP - page 6

    6 ZONE THERMOST A T CONTROL RELA YS — A u ni qu e featur e of the Aquazone system contr ol panel is the capabi lity to add z one th ermost at cont rol re lays. T his fe ature is used when the Aquazon e system co ntrol pa nel is ut ilized i n a stand-a lone type of instal lation. Either a set of 10 or 18 rel ays can be sele cted from the 50RL P mo ...

  • Carrier AQUAZONE 50RLP - page 7

    7 PO W E R R E C E P T AC L E — A power rece ptac le is provi ded in the Aquazone™ system control panel and is located in the bottom left corner . Spec ifications for the power rece ptacle are as follows: Power: 120 vac Rating: 15A @ 120 vac for receptacles 15A @ 120 vac for switch 250 V for fuse W A TER TEMPERA TURE SENSORS — T wo wat er te ...

  • Carrier AQUAZONE 50RLP - page 8

    8 Carrier ’ s diagnostic standard tier display tools such as Navigator™ or Scrolling Marquee can be used wi th the PremierLi nk™ controller . Access is available via an RJ-11 connection or a 3-wire connec tion to the communication bus. Computers equipped with Carri er user inter face software such as Service T ool, ComfortVIEW™, or ComfortW ...

  • Carrier AQUAZONE 50RLP - page 9

    9 Table 1 — Aquazone ™ Thermostats Field-Suppl ied Har dware For CCN Applica- tions — The factory-installed PremierLink™ controller for the water source heat pump unit is configurable with a va riety of Carrier space t emperature sens ors. SP ACE TEMPERA TURE SENSOR (SP T) — A field-supplied Carrier space temperat ure sensor is required t ...

  • Carrier AQUAZONE 50RLP - page 10

    10 INST ALLA TION Inspection — Inspect the package cont ents for visual de- fects that may have occurred during shipping. If there is any damage, contact your l ocal representa tive before proceeding. Moun ting Loc ation — The Aquazone™ system control panel should be l ocated indoors. Be sure the locat ion prevents moisture and rain from comi ...

  • Carrier AQUAZONE 50RLP - page 11

    11 PREMIERLINK™ CONTROLLER INPUTS AND OUT- PU T S — When PremierLi nk controllers are factory mounted with water source heat pump equipment to impl ement a CCN system install a tion, the inputs and outputs are shown in T a ble 3. CO N N E CT PO W E R — The Aquazone™ system control panel requires an uninterrupted 1 10-v , single-phase, 60 Hz ...

  • Carrier AQUAZONE 50RLP - page 12

    12 SYSZ 18 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1 2 3 2 3 4 5 1 6 7 8 2 3 4 5 1 6 7 8 Loop Pane l LOW VOLTAGE CONTROL WIRING PCB1 T1 CB1 RED BLK GRN TBP GRN J3 J4 J2 BLK BLU 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1 2 3 PCB2 GRN J3 J4 J2 T2 CB2 BRN BLU 24 V Y ...

  • Carrier AQUAZONE 50RLP - page 13

    13 LEGEND FOR FIG. 8 Install The rmostat, S ensors and Switche s — In all installations, the loop supply w ater temperature sensor and water flow switch must be installed in the field. The water pressure sensor is used to sense water system pressure to operate in conjunction with pump variable frequency drives. A therm o st at is use d in stand-a ...

  • Carrier AQUAZONE 50RLP - page 14

    14 Table 5 — Water Flow Switch Tr oubleshooting Connect to CCN Com m unication Bus — The Aquazone™ sy stem control p anel primary co ntroller connec ts to the bus in a dais y chain arran gement. Negative pi ns on each component mu st be c onnected to r espective neg ative pins an d likewise positive pins on each component must be connected to ...

  • Carrier AQUAZONE 50RLP - page 15

    15 Change the Default Pass wor d — T o change the default password, per form the following procedure: NOTE: The password must have a l ready been entered to pe r- form this procedure. 1. Pres s 3 and then . The LID display will show: Controller Password 2. Pre ss . The LID di splay will show: Log in to Controller Enter Password 3. Pres s . The LI ...

  • Carrier AQUAZONE 50RLP - page 16

    16 Configure Sc hedules — T o configure the schedules, perform the following procedure: 1. Pres s 1 and then . The LID display will show: Occupancy Algorithm 2. Pres s . The LID display will show: Occupancy 01 OCCPC01 3. There are 18 occupancy algorithms: OCCPC01 to OCCPC18. There is one algorithm for each of the 18 zone relay outputs. Use the up ...

  • Carrier AQUAZONE 50RLP - page 17

    17 Set the Aquazone ™ System Contr ol Pan el Contr oller Ad dress — T o set the addre ss of the Aquazone System Control panel controller, perform the following procedure: 1. Pre ss 7 and then . Press and then . 2. T ype in the CCN element number and press . 3. Pre ss the button. T ype in the CCN bus number and press . Log Off fr om Contr oller ...

  • Carrier AQUAZONE 50RLP - page 18

    18 Access Items in the Status Mod e — The user can ac cess maintenance data in t he Status mode in two ways: • Pressing the appropri ate funct ion key (i. e., ) once to access a category (i.e., alarms) and then continu- ing to press that key ( ) to scroll through all the items in that cat egory (i.e., Limit Alarm , Setpoint Alarm, Discrete Alar ...

  • Carrier AQUAZONE 50RLP - page 19

    19 Table 10 — Quick Acce ss Cha rt LEGEND NOT ES: 1. If in the Edit m ode an d wish t o switch to the St atus mo de, press or press again. 2. Not all availab le selections will have items to select in suble v els. LID NUM. KEY LID FUNCTION KEYS Algori thms (ALGO ) Status (ST A T ) History (HIST ) Service (SR VC) Alarm (ALRM ) Setup (SET) Sche dul ...

  • Carrier AQUAZONE 50RLP - page 20

    20 Sequence of Oper ation HE A T R E J E C T IO N — When the system pumps are operat - ing and there is flow to the sys tem, heat rejection control compares the system supply water temperature to the hi gh set point in the system loop temperature set points. If the system supply water temperature approaches the high set point, the controller comm ...

  • Carrier AQUAZONE 50RLP - page 21

    21 CONFIGURA TION The Aquazone™ System Control Panel contains a Comfort Controller 6400 programmed using the standard algorithms and enhanced by BEST++™ custom programming. The BEST++ T emplates for some of the programs have been removed to prevent field alterations. For other programs, the templates are included to allow for jobsite customizat ...

  • Carrier AQUAZONE 50RLP - page 22

    22 RE M O T E O C C U P A N C Y — This input is used to provide an external clock input to enable all 18 of the local sche dules, start the loop pumps, and enable loop tempera ture control. Remote Occupancy: Displ ay Un its Discret e ASCI I Defau lt V alue Disable Dis play Range Enable/Dis abl e Network Ac cess Read/Write SY S TE M / S H UT DO W ...

  • Carrier AQUAZONE 50RLP - page 23

    23 HEA T SOURCE 2 SPEED/LEVEL — When the Aquaz one™ system control panel is configured for modulating heat source, this point displays the percent open or percent heat capa city requested. When the Aquazone system cont rol panel is equipped for staged output, this point displays the percent of stages commanded. The act ual number of stages a ct ...

  • Carrier AQUAZONE 50RLP - page 24

    24 PU M P 2 RU N T I ME — This point displays the number of hours that the pump has run. When the maximum number of hours is exceeded (9999 hours), both pumps run time hours will r eset to 0. Pump 2 Run T ime Displ ay Un its Num eric Default V alue 0 Display Range 0 to 9999 Network Ac cess Read/Write Loop Supply W at er Set P oint — The low set ...

  • Carrier AQUAZONE 50RLP - page 25

    25 BOILER/H EA T SOURCE CONTROL TYPE — Th is co n - figuration determines how the tower outputs will be controlled. If panels were ordered w i th the stage output transducers, t hen tower control type should be set to 0. If the tower outputs will control variable speed tower fans, then the configuration should be set to 1. V ari able speed config ...

  • Carrier AQUAZONE 50RLP - page 26

    26 The loop co ntrolle r comes pre-con figured with local schedules 1 through 18. It is also pre-configu red with network schedules 65 through 82 in order to receive global schedules broadcast from PremierLink™ controlle rs or other networked cont rollers. See Network T ime Schedule sec tion. This is the recom mended method for using glob al sche ...

  • Carrier AQUAZONE 50RLP - page 27

    27 OC C U PI E D F R O M — This field is used t o c onfigure the hour and minute, in military time, th at the mode for t he PremierLink™ controller will switc h to occupied. Occupied From: Units Hours:Minutes Range 00:00 to 24:00 (Minutes 00 to 59) Default V alue 00:00 OC C U PI E D TO — This field is us ed to configure the hour and minute, i ...

  • Carrier AQUAZONE 50RLP - page 28

    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d wit hout inc urring obligations. PC 111 Catalo g No. 535-00077 Prin ted in U.S.A. F or m 50RLP -1SI Pg 28 1-03 Repla ces: New Copyright 20 03 Car rier Cor po ration Book 1 4 Ta b 5 a 5 a ...

メーカー Carrier カテゴリー Heat Pump

Carrier AQUAZONE 50RLPのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- AQUAZONE 50RLPの取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier AQUAZONE 50RLPの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier AQUAZONE 50RLPの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier AQUAZONE 50RLPの取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier AQUAZONE 50RLPのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier AQUAZONE 50RLPの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Carrier AQUAZONE 50RLPデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier AQUAZONE 50RLPを使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier AQUAZONE 50RLPユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier AQUAZONE 50RLPの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier AQUAZONE 50RLPの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier AQUAZONE 50RLPに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier AQUAZONE 50RLPデバイスの基本機能を使うにあたってのヒント。 Carrier AQUAZONE 50RLPのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier AQUAZONE 50RLPに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier AQUAZONE 50RLPのメーカー/サービスへの連絡先に関する情報。

Carrier AQUAZONE 50RLPについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCarrier AQUAZONE 50RLPの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCarrier AQUAZONE 50RLPで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)