    F20470I EN (082012) Viking Installation Guide Pr ofessional & Outdoor Hoods Viking Range Corporation 111 Front Street Greenwood, Mississippi 38930 USA (662) 455-1200 For product infor mation, call 1-888-VIKING1 (845-4641) or visit the Viking Web site at vikingrange.com ...

  • Viking F20470I EN - page 2

    T able of Contents 3 IMPORT ANT– Please Read and Follow! NOTE: If installing hood with warming shelf panel, install war ming shelf panel first. IMPORT ANT – PLEASE READ AND FOLLOW • Before beginning, please read these instructions completely and carefully . • Do not remove permanently affixed labels, war nings, or plates from the product. T ...

  • Viking F20470I EN - page 3

    5 IMPORT ANT– Please Read and Follow! 4 W A R N I N G TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS Rangehoods must be installed with the ventilators that are specified on their carton indicating suitability with this model. Other ventilators cannot be substituted. C A U T I O N For general ventilating use only . Do not use t ...

  • Viking F20470I EN - page 4

    6 Clearance Dimensions 7 Interior V entilator Dimensions 460 CFM Interior V entilator Installation T op View (VWH 10”H. W all Hoods w/Standard V entilator) (VWH 10”H. W all Hoods w/Standard V entilator) ...

  • Viking F20470I EN - page 5

    9 Dimensions & Specifications 8 ( VW H 18 ” H . 2 4 ” De e p W al l Ho o ds 3 0 ”, 3 6” , 42 ” , 48 ” , 54 ” , & 6 0” ) ( VW H 18 ” H . 2 7 ” De e p W al l Ho o ds 3 6 ”, 4 8” , & 6 0 ”) * A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill. M ...

  • Viking F20470I EN - page 6

    Exterior V entilator Dimensions 11 Interior V entilator Dimensions 10 900 or 1200 CFM Exterior or In-Line V entilator Installation for all W all Hoods 1200 or 1500 CFM Exterior or In-Line V entilator Installation for all W all Hoods 300 or 600 CFM Interior V entilator Installation for all W all Hoods 1200 CFM Interior V entilator Installation for a ...

  • Viking F20470I EN - page 7

    13 12 Dimensions & Specifications ( VW H O 18 ” H. O u td o o r W al l Ho o ds 3 6” , 4 8” , & 6 0 ”) * A 1,200 CFM interior- or exterior-power ventilator should be used with all T -Series models and when i ndoor models are installed over range/rangetop with gas char -grill. Max duct run is 50 ft. ** It is recommended that the 1,500 ...

  • Viking F20470I EN - page 8

    15 Dimensions & Specifications 14 (VCWH Chimney W all Hoods 30”, 36”, 42”, 48”, 54”, 60”, & 66”) * A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill. Max duct run is 50 ft. ** It is recommended that the 1,500 CFM ventilator be used with longer duct runs. Ma ...

  • Viking F20470I EN - page 9

    Interior V entilator Dimensions 16 Exterior V entilator Dimensions 17 900 or 1200 CFM Exterior or In-Line V entilator Installation for 30”, 36”, & 42” models 900, 1200 or 1500 CFM Exterior or In-Line V entilator Installation for 48”, 54”, 60”, & 66” models 300 or 600 CFM Interior V entilator Installation for 30”, 36”, & ...

  • Viking F20470I EN - page 10

    19 Dimensions & Specifications 18 (DCWH Classic Chimney Hoods 30”, 36”, 42”, & 48”) * A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill. Max duct run is 50 ft. ** It is recommended that the 1,500 CFM ventilator be used with longer duct runs. Max duct run is 75 ft ...

  • Viking F20470I EN - page 11

    21 20 Exterior V entilator Dimensions Interior V entilator Dimensions 300 or 600 CFM Interior V entilator Installation for 30”, 36”, & 42”Hoods 900 or 1200 CFM Exterior or In-Line V entilator Installation for 30”, 36”, & 42” Hoods T op View T op View T op View T op View 900, 1200 or 1500 CFM Exteri or or In-Lin e V entil ator In ...

  • Viking F20470I EN - page 12

    23 22 * A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill. Max duct run is 50 ft. ** It is recommended that the 1,500 CFM ventilator be used with longer duct runs. Max duct run is 75 ft. NOTE: Maximum amp rating for hoods includes recommended ventilator kit rating; All products ...

  • Viking F20470I EN - page 13

    Exterior V entilator Dimensions 25 Interior V entilator Dimensions 24 900 or 1200 CFM Exterior or In-Li ne V entilator Installation for all Chimney Island Hoods 900, 1200 or 1500 CFM Exterior or In-Lin e V entilator Installation for all Chimney Island Hoods 600 CFM Interior V entilator Installation for all Chimney Island Hoods 1200 CFM Interior V e ...

  • Viking F20470I EN - page 14

    27 26 Dimensions & Specifications (VBCV W all Custom V entilator System 30”, 36”, 42”, 48”, 54”, 60” & 66”) * A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill. Max duct run is 50 ft. ** It is recommended that the 1,500 CFM ventilator be used with longer du ...

  • Viking F20470I EN - page 15

    29 Built-In W all Custom V entilator System Dimensions (VBCV Models ) For 900, 1200 or 1500 CFM Exterior or In-Line V entilator Installation For 300, 600 or 1200 CFM Interior V entilator Installation 900 or 1200 CFM Exterior or In-Line V entilator Installation 30”, 36”, 42” W . Models 300 or 600 CFM Interior V entilator Installation 30”, 36 ...

  • Viking F20470I EN - page 16

    31 30 1200 or 1500 CFM Exterior or In-Line V entilator Installation 48”, 54”, 60”, 66” W . Models 1200 CFM Interior V entilator Installation 30”, 36”, 42”, 48”, 54”, 60”, 66” W . Models Built-In W all Custom V entilator System Dimensions (VBCV Models ) C 30” W . 28-1/4” (71.8 cm) 36” W . 34-1/4” (87.0 cm) 42” W . 40- ...

  • Viking F20470I EN - page 17

    33 CAUTION: If not using a duct cover , using screws provided, make sure top mounting screws are secured into soffit or cabinet framing. Use additional mounting screws, if necessary . Connect black to black, white to white, and the green/bar e wire under the green screw . NOTE: Housing wiring must be properly installed for wiring to be correct when ...

  • Viking F20470I EN - page 18

    35 CAUTION: Secure vent hood. Make sure mounting screws are secured into framing. Use additional mounting screws and wall anchors, if necessary . Remove electrical box cover . Flip hood over . Insert 6” of electrical wiring through the top of vent hood and secure. Refer to local codes. Attach with screws and lock washers provided. Attach with scr ...

  • Viking F20470I EN - page 19

    37 Measure down 1-13/16 (4.6 cm) from desired height of hood and secure 1-1/2” x 3/4” wood strip (provided locally) to wall using screws provided. Use additional mounting screws to secure hood to wood strip. Installation (VWH 18”H. W all & VCWH Chimney W all Hoods) CAUTION: Secure vent hood to wall using screws provided. Use additional mo ...

  • Viking F20470I EN - page 20

    39 Pl ac e du ct co ve r t op i ns id e d uc t c ov e r b as e a nd lo we r un ti l de si r ed h ei gh t i s f ou nd . Ma rk he ig ht . U s e t he r et ai ni ng nu ts a nd bo lt s t o f as t en in pl ac e a nd r em o ve ta pe . Slide the duct cover in place and fasten from inside canopy using the sheet metal screws provided. Measure distance from c ...

  • Viking F20470I EN - page 21

    41 Attach canopy to duct cover/soffit. Seal top of hood to duct with aluminum tape. Run duct work down to bottom edge of duct cover/soffit and secure in place. Make sure the duct does not stick down past the cover . Slide filter front over front lip. Push filter rear up, then slide back over rear lip. Slide spacer front over front lip. Push spacer ...

  • Viking F20470I EN - page 22

    43 42 Measure down 1-13/16 (4.6 cm) from desired height of hood and secure 1-1/2” x 3/4” wood strip (not included) to wall using screws provided. Use additional mounting screws to secure hood to wood strip. I n s t a l l a t i o n ( D C W H C l a s s i c C h i m n e y W a l l H o o d s ) C AU T I O N: Se c u r e ve n t h oo d t o wa l l u si n ...

  • Viking F20470I EN - page 23

    44 Service & Registration Service & Parts Only authorized replacement parts may be used in performing service on the appliance. Do not repair or replace any part of the appliance unless specifically recommended in the manual. All other servicing should be referr ed to a qualified technician. Rec or d the follo wing info rmatio n indic ated ...

  • Viking F20470I EN - page 24

    47 46 ...

メーカー Viking カテゴリー Ventilation Hood

Viking F20470I ENのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- F20470I ENの取扱説明書
- Vikingの製品カード
- パンフレット
- またはViking F20470I ENの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Viking F20470I ENの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Viking F20470I ENの取り付け説明書、サービスマニュアル、簡易説明書、またはViking F20470I ENのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Viking F20470I ENの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Viking F20470I ENデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがViking F20470I ENを使用するのを助ける技術的文書のことです。説明書は通常、全てのViking F20470I ENユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Vikingの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Viking F20470I ENの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははViking F20470I ENの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Viking F20470I ENに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Viking F20470I ENデバイスの基本機能を使うにあたってのヒント。 Viking F20470I ENのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Viking F20470I ENに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるViking F20470I ENのメーカー/サービスへの連絡先に関する情報。

Viking F20470I ENについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもViking F20470I ENの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがViking F20470I ENで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)