Mitsubishi Electronics MSZ-GE18NAの取扱説明書

32ページ 2.49 mb
ダウンロード

ページに移動 of 32

Summary
  • Mitsubishi Electronics MSZ-GE18NA - page 1

    SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ······································· 2 2. P ART NAMES AND FUNCTIONS ····················· 2 3. SPECIFICA TION ················································ 3 4. OUTLINES AND DIMENSIONS ··? ...

  • Mitsubishi Electronics MSZ-GE18NA - page 2

    2 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 1. New model 1 TECHNICAL CHANGES MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA ACCESSORIES Installation plate 1 Installation plate fi xing screw 4 × 25 mm 5 Remote controller holder 1 Fi ...

  • Mitsubishi Electronics MSZ-GE18NA - page 3

    3 Indoor model MSZ-GE06NA MSZ-GE09NA MSY -GE09NA MSZ-GE12NA MSY -GE12NA Power supply V , phase, Hz 208/230, 1, 60 Max. fuse size (time delay)/ Disconnect switch A1 5 Min. circuit ampacity A 1.0 Fan motor F .L.A 0.76 Air fl ow Super High - High - Med. - Low - Quiet COOL Dry (Wet) CFM 399-321-237-170-145 (364-286-201-134-109) HEA T Dry CFM 406-321-2 ...

  • Mitsubishi Electronics MSZ-GE18NA - page 4

    4 3-2. OUTLET AIR SPEED AND COVERAGE ● The air coverage is the figure up to the position where the air speed is 1 ft./s., when air is blown out horizontally from the unit properly at the High speed posi- tion. The coverage should be used only as a general guideline since it varies accord- ing to the size of the room and furniture arranged inside ...

  • Mitsubishi Electronics MSZ-GE18NA - page 5

    5 Unit: inch MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 8-5/16 9-1/8 9-15/16 7/8 6-1/8 6-1/8 3-1/8 3-1/8 8-7/8 8-7/8 1/8 3/4 6 - 1/4 2- 5/16 3/16 9-1/8 2-3/16 2-3/4 31-7/16 30-15/16 1/4 5-1/8 24-3/8 1-15/16 11-5/8 1-15/16 1-5/8 2-3/16 1-11/16 1-5/8 5/16 3-15/16 4/3/16 4-3/8 1-3/4 2-3/16 2- ...

  • Mitsubishi Electronics MSZ-GE18NA - page 6

    6 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 5 WIRING DIAGRAM ...

  • Mitsubishi Electronics MSZ-GE18NA - page 7

    7 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA Unit: inch Indoor heat exchanger Flared connection Room temperature thermistor RT1 1 Flared connection Refrigerant pipe ø3/8 ( MSZ-GE06/09/12NA, MSY -GE09/12NA ) ø1/2 ( MSZ-GE15/18NA, MSY -GE15/18NA ) (with heat insulator) Refrigerant pipe ø1 ...

  • Mitsubishi Electronics MSZ-GE18NA - page 8

    8 7-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P .C. board. The time will be shortened as follows. (Refer to 9-7.) Set time: 1-minute → 1-second Set time: 3-minute → 3-second (It takes 3 minutes for the compressor to start operation. However , the starting time is sho ...

  • Mitsubishi Electronics MSZ-GE18NA - page 9

    9 C N111 CN1 12 CN151 CN10A Indoor electronic control P .C. board JR07 NOTE: • The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller . • If main power is turned OFF or a power failure occurs while AUTO ST ART/STOP timer is active, the timer setting is cancelled. • If the ...

  • Mitsubishi Electronics MSZ-GE18NA - page 10

    10 WIRELESS REMOTE CONTROLLER MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA NOTE: Last setting will be stored after the unit is turned OFF with the remote controller . Indoor unit receives the signal of the remote controller with beeps. Operation Indicator lamp The operation indicator at the ...

  • Mitsubishi Electronics MSZ-GE18NA - page 11

    11 8-1. COOL ( ) OPERA TION (1) Press OPERA TE/ST OP (ON/OFF) button. OPERA TION INDICA TOR lamp of the indoor unit turns ON with a beep tone. (2) Select COOL mode with OPERA TION SELECT button. (3) Press TEMPERA TURE buttons (TOO W ARM or TOO COOL button) to select the desired temperature. The setting range is 61 ~ 88°F (16 ~ 31°C). 1. Coil fros ...

  • Mitsubishi Electronics MSZ-GE18NA - page 12

    12 (4) The initial set temperature is decided by the initial room temperature. Initial room temperature Model Initial set temperature 79°F (26°C) or more COOL mode of "I FEEL CONTROL" 75°F (24°C) 77 to 79°F (25 to 26°C) Initial room temperature minus 4°F (2°C) Less than 79°F (25°C) DRY mode of "I FEEL CONTROL" Initial ...

  • Mitsubishi Electronics MSZ-GE18NA - page 13

    13 8-7. AUTO V ANE OPERA TION 1. Horizontal vane (1) V ane motor drive These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12 V) transmitted from indoor microprocessor . (2) The horizontal vane angle and mode change as follows by pres ...

  • Mitsubishi Electronics MSZ-GE18NA - page 14

    14 ( 10 ) ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 4°F(2°C) higher . Also the horizontal vane swings in various cycle. SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher , the air conditioner can keep ...

  • Mitsubishi Electronics MSZ-GE18NA - page 15

    15 8-9. SMART SET ( ) OPERA TION 1. How to SET SMART SET operation (1) Press OPERA TE/ST OP (ON/OFF) button. (2) Select COOL, HEA T (MSZ) or ECONO COOL mode. (3) Press SMART SET button. (4) Set the temperature, fan speed, and air fl ow direction for SMART SET operation. NOTE: • SMART SET operation cannot be selected during DRY or AUTO mode opera ...

  • Mitsubishi Electronics MSZ-GE18NA - page 16

    16 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA 9-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. T ake care of the following during servicing 1) Before servicing th ...

  • Mitsubishi Electronics MSZ-GE18NA - page 17

    17 9-2. F AILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can be recalled. 1. Flow chart of failure mode recall function for the indoor/outdoor un ...

  • Mitsubishi Electronics MSZ-GE18NA - page 18

    18 2. Indoor unit failure mode table Upper lamp of OP- ERA TION INDICA- TOR lamp Abnormal point (Failure mode) Condition Remedy Not lighted Normal — — 1-time fl ash every 0.5-second Room temperature thermistor The room temperature thermistor short or open circuit is detected every 8 seconds dur- ing operation. Refer to the characteristics of t ...

  • Mitsubishi Electronics MSZ-GE18NA - page 19

    19 9-3. INSTRUCTION OF TROUBLESHOOTING Indoor unit oper- ates. Outdoor unit does not operate. If blinking of OPERA TION INDI- CA T OR lamp cannot be checked, it can be checked with failure mode recall function. Indoor unit operates. Outdoor unit does not operate normally . Indoor unit does not receive the signal from re- mote controller . OPERA TIO ...

  • Mitsubishi Electronics MSZ-GE18NA - page 20

    20 9-4. TROUBLESHOOTING CHECK T ABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after th e power ON), the indoor fan motor turns OFF and OPERA TION INDICA TOR lamp flashes. OPERA TION ...

  • Mitsubishi Electronics MSZ-GE18NA - page 21

    21 OPERA TION INDICA TOR No. Abnormal point Operation indicator lamp Symptom Condition Remedy 1 MXZ type Operation mode setting Upper lamp lights and lower lamp fl ashes. 2.5-second OFF Outdoor unit operates but indoor unit does not operate. The operation mode of the each indoor unit is differently set to COOL (includes DRY) and HEA T at the same ...

  • Mitsubishi Electronics MSZ-GE18NA - page 22

    22 A Check of indoor fan motor 9-6. TROUBLESHOOTING FLOW The indoor fan motor error has occurred, and the indoor fan does not operate. T urn OFF the power supply . Is there any foreign matter that interferes the rotation of the line fl ow fan? Ye s No Remove the foreign matter and adjust the line fl ow fan. Pay enough attention to the high voltag ...

  • Mitsubishi Electronics MSZ-GE18NA - page 23

    23 B Check of remote controller and indoor electronic control P .C. board Check if the remote controller is exclusive for this air conditioner . Does the unit operate with the remote controller? OK Ye s No (Not clear) Replace the batteries. (Refer to 9-1.4.) Press OPERA TE/STOP (ON/OFF) button on the remote controller . Is LCD display on the remote ...

  • Mitsubishi Electronics MSZ-GE18NA - page 24

    24 C Check of indoor P .C. board and indoor fan motor T urn OFF the power supply . Remove indoor fan motor connector CN21 1 from indoor power P .C. board and vane motor connector CN151 from the indoor electronic control P .C. board and turn ON the power supply . Does the unit operate with the remote controller? Does OPERA TION INDICA TOR lamp light ...

  • Mitsubishi Electronics MSZ-GE18NA - page 25

    25 25 D How to check miswiring and serial signal error T urn OFF inverter-controlled lighting equipment. T urn OFF the power supply and then turn ON again. Press EMERGENCY OPERA TION switch. • • • A Is serial signal error indicated 6 minutes later? B Ye s Reinstall either the unit or the light away from each other . Attach a fi lter on remot ...

  • Mitsubishi Electronics MSZ-GE18NA - page 26

    26 E Electromagnetic noise enters into TV sets or radios Ye s Is the unit grounded? No Ground the unit. Ye s Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.? No Extend the distance between the antennas and the indoor unit, and/or the antennas and ...

  • Mitsubishi Electronics MSZ-GE18NA - page 27

    27 1. Indoor power P .C. board, Indoor terminal P .C. board 9-7. T est point diagram and voltage Indoor terminal P .C. board Indoor power P .C. board Please replace the fuse after removing the indoor terminal P .C. board from the electrical box. Fuse (F1 1)( ) V aristor (NR1 1) T erminal block Connector to indoor electronic control P .C. board (CN2 ...

  • Mitsubishi Electronics MSZ-GE18NA - page 28

    28 MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY -GE09NA MSY -GE12NA MSY -GE15NA MSY -GE18NA NOTE: Turn OFF power supply before disassembling. OPERA TING PROCEDURE PHOTOS 1. Removing the panel (1) Remove the horizontal vanes. (2) Remove the screw caps of the panel. Remove the screws of the panel. (3) Unhook the lower part ( ) of the pa ...

  • Mitsubishi Electronics MSZ-GE18NA - page 29

    29 OPERA TING PROCEDURE PHOTOS 2. Removing the indoor electronic control P .C. board and the room temperature thermistor (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the screw of the V .A. clamp and the V .A. clamp. (3) Remove the screw of the electrical cover and the electrical cover . (4) Remove the screw of conduit cover and ...

  • Mitsubishi Electronics MSZ-GE18NA - page 30

    30 OPERA TING PROCEDURE PHOTOS 4. Removing the nozzle assembly (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the indoor/outdoor connecting wire (Refer to 2 (2)-(5).). (3) Remove the indoor electronic control P .C. board hold- er . (4) Pull out the drain hose from the nozzle assembly and remove the nozzle assembly . Photo 4 5. Re ...

  • Mitsubishi Electronics MSZ-GE18NA - page 31

    31 OPERA TING PROCEDURE PHOTOS 6. Removing the indoor fan motor , the indoor coil thermistor , and the line flow fan (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the indoor electronic control P .C. board hold- er , the electrical box and the nozzle assembly . (3) Remove the screws fixing the motor bed. (4) Loosen the screw fixi ...

  • Mitsubishi Electronics MSZ-GE18NA - page 32

    HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2009 MITSUBISHI ELECTRIC CO.,L TD Distributed in Jul. 2009. No. OBH548 5 Made in Japan New publication, effective Jul. 2009 Specifications subject to change without notice. TM ...

メーカー Mitsubishi Electronics カテゴリー Air Conditioner

Mitsubishi Electronics MSZ-GE18NAのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MSZ-GE18NAの取扱説明書
- Mitsubishi Electronicsの製品カード
- パンフレット
- またはMitsubishi Electronics MSZ-GE18NAの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Mitsubishi Electronics MSZ-GE18NAの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Mitsubishi Electronics MSZ-GE18NAの取り付け説明書、サービスマニュアル、簡易説明書、またはMitsubishi Electronics MSZ-GE18NAのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Mitsubishi Electronics MSZ-GE18NAの製品を使用するにあたって最も人気のある説明書を閲覧できます。

Mitsubishi Electronics MSZ-GE18NAデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがMitsubishi Electronics MSZ-GE18NAを使用するのを助ける技術的文書のことです。説明書は通常、全てのMitsubishi Electronics MSZ-GE18NAユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Mitsubishi Electronicsの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Mitsubishi Electronics MSZ-GE18NAの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははMitsubishi Electronics MSZ-GE18NAの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Mitsubishi Electronics MSZ-GE18NAに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Mitsubishi Electronics MSZ-GE18NAデバイスの基本機能を使うにあたってのヒント。 Mitsubishi Electronics MSZ-GE18NAのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Mitsubishi Electronics MSZ-GE18NAに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるMitsubishi Electronics MSZ-GE18NAのメーカー/サービスへの連絡先に関する情報。