    1 CA T ALOG NO.: 5000.59B Effective Date: 4-09-08 Replaces: 3-15-99 T-3 Raypak B6000 Modbus System Protocol Interface T-3 Communications Interface Raypak B6000 Boiler Controller to Modbus Interface Card Installation and Operating Manual P/N 240729 Rev . 3 ...

  • Raypak B6000 - page 2

    2 T ABLE OF CONTENTS 1.0 Contents (as shipped) ----------------------------------------------------------------------------------- 3 2.0 Forward ----------------------------------------------------------------------------------------------------- 3 3.0 Installation and Mounting ---- ------------------------------------------------------------------ ...

  • Raypak B6000 - page 3

    3 T -3 (Rayp ak B6000 System Protocol Interface) Content s Quantity COMP ACT DISC (CD) 1 T- 3 1 EPROM (CPX.XNMn) in small black ESD box 1 Check packaging for damage or missing components. I MPORT ANT NOTICE: These instructions are intended for the use by qualified personnel only , specifically trained and experienced in the installation of this typ ...

  • Raypak B6000 - page 4

    4 T -3 INST ALLA TION AND MOUNTING The T -3 Module should be mounted on a permanent base not subject to vibrations, moisture or dust. It should be readily accessible, for serviceability . DIMENSIONS AND WEIGHT 15 3/4” H 14 LBS 8 ” W 5 3/4” D MECHANICAL INST ALLA TION Mount the System Protocol Interface within five (5) feet of B6000 System Con ...

  • Raypak B6000 - page 5

    5 WIRING T -3 1. T urn of f power to the B6000 System Control Box. 2. Open front door of System Protocol Interface Gateway Enclosure. 3. Remove four screws and the lower cover , revealing the field wiring blocks. 4 . Attach wires from interface card to the field wiring side of left terminal block (N+, N-, GND, NC). Refer to diagram in this user man ...

  • Raypak B6000 - page 6

    6 B6000 SYSTEM CONTROL BOARD CHECK YOUR POWER SOURCE AC = 108 V olts AC Minimum, 132 V olts MAX AB = 108 V olts AC Minimum, 132 V olts MAX BC = Must be less than 1.0 V olts AC ...

  • Raypak B6000 - page 7

    7 ...

  • Raypak B6000 - page 8

    8 1 1.0. T-3 Revision 1.0 Raypak B6000 Modbus ™ Protocol Interface Please Read this Notice Successful application of the T- 3 card requires a reasonable work- ing knowledge of the Raypak B6000 Boiler Control, and the applica- tion in which the combination is to be used. For this reason, it is important that those responsible for implementing the ...

  • Raypak B6000 - page 9

    9 1 1.1. Product S pecifications The T -3 card is a hardware product designed to be the communications front end for the Raypak B6000 Boiler Control and a modbus Master Host. The product includes the following functionality: Modbus Slave Specifications • Protocol Modes: RTU mode with CRC-16 error checking • Supported Modbus Function codes: 2 Re ...

  • Raypak B6000 - page 10

    10 1 1.2.0 Slave Port Functionality 1 1.2.1 Modbus Communications The T -3 Modbus Slave card runs the RTU version of the Modbus protocol. This capability allows the module to communicate data from a Raypak B6000 Boiler Control to a Modbus Master host, and vice-versa. The module supports both point-to-point implementation as well as multi-drop imple ...

  • Raypak B6000 - page 11

    11 1 1.2.1.4 Data Integrity As in all good protocols, there must exist a level of data integrity checking to verify , with some degree of assurance, the quality of the transmitted data. The Modbus protocol supports two types of error checking: • RTU Mode: 16 bit cyclic redundancy check (CRC-16) • One bit parity check CRC-16: When the master gen ...

  • Raypak B6000 - page 12

    12 1 1.3.0 Hardware Setup 1 1.3.1.1 1500 Interface Card Setup 1 1.3.1.1 Connecting Power to the T -3 Card The T -3 Card requires an external source of DC voltage. The DC source voltage should be between 9V and 30V . The power is connected to TB1, located near the two 9 pin serial port connec- tions. The connection to TB1 is as follows: TB1-1 9-30 V ...

  • Raypak B6000 - page 13

    13 Example Addresses = 0 to 33 Example Addresses = 34 to 63 8 7 6 5 4 3 2 1 Address 8 7 6 5 4 3 2 1 Address 0 0 0 0 0 0 0 0 Invalid 0 0 1 0 0 0 1 0 34 0000000 1 1 * 0010001 1 3 5 0000001 0 2 0010010 0 3 6 0000001 1 3 0010010 1 3 7 0000010 0 4 0010011 0 3 8 0000010 1 5 0010011 1 3 9 0000011 0 6 0010100 0 4 0 0000011 1 7 0010100 1 4 1 0000100 0 8 001 ...

  • Raypak B6000 - page 14

    14 The parameters are defined as follows: Modbus Slave Address: Each of the separate drop offs of a Modbus host must have a different slave address. The slave address is selected by encoding the slave address in a binary form using the dip switches. 1 1.3.1.3 T-3 Jumper Configurations The T -3 card has five sets of jumpers on the board. Generally , ...

  • Raypak B6000 - page 15

    15 1 1.4.0 Modbus Protocol Support 1 1.4.1 Modbus Commands The T -3 card support s a command subset of the Modbus S pecification consisting primarily of the Function Codes required to read and write data. The following sections detail the different commands supported by the card. Function Address Slave Driver Code Command Range Comments 2 Read Inpu ...

  • Raypak B6000 - page 16

    16 1 1.5.0 Diagnostics Several hardware diagnostics capabilities have been implemented using the LED indicator lights on the front of the T-3 card. The possible conditions as indicated by the lights are: 1 1.5.1 LED Indicators Several hardware diagnostics capabilities have been implemented using the LED indicator lights on the front of the module. ...

  • Raypak B6000 - page 17

    17 1 1.6.0 ProSoft Support, Service and Warranty 1 1.6.1 T echnical Support ProSoft T echnology survives on its ability to provide meaningful support to its customers. Should any questions or problems arise, please feel free to contact us at: ProSoft T echnology , Inc. 9801 Camino Media Suite 105 Bakersfield, CA 9331 1 (805) 664-7208 (805) 664-7233 ...

  • Raypak B6000 - page 18

    18 LIMITED W ARRANTY T- 3 SCOPE OF W ARRANTY : Raypak, Inc. (“Raypak”) warrants to the original owner the T -3 to be free from defects in materials and workmanship under nor mal use and service for the applicable warranty period. In accordance with the terms of this Limited W arranty , RA YP AK will furnish a replacement or repair , at our opti ...

  • Raypak B6000 - page 19

    19 APPENDIX A Modbus Register Map A-1 ...

  • Raypak B6000 - page 20

    20 A-2 Raypak Modbus Register Assignments Function Function Function T ype 2 4 3,6 Description R /W 30001 40001 Setpoint Day Setpoint (Desired water temp @70F) R / W 30002 40002 Nitesetback Night Setback (Desired water temp @ 70F) R /W 30003 40003 Ratio Out 1-200 = 0.1 - 20.0 in 0.1 increments R /W 30004 40004 Throttling Delta T of all boilers in s ...

  • Raypak B6000 - page 21

    21 R 10215 6 High Limit (0 = Normal, 1 = Alarm) R 10216 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat) R 10217 8 Manual Override (0 = Normal, 1 = Alarm) R 10218 9 Flow Switch (0 = Normal, 1 = Alarm) R 10219 10 No Pilot (0 = Normal, 1 = Alarm) 30045 40045 bit Boiler #2 S tatus Word Boiler #2 R 10225 0 Boiler Not On Line (0 ...

  • Raypak B6000 - page 22

    22 30049 40049 bit Boiler #6 S tatus Word Boiler #6 R 10289 0 Boiler Not On Line (0 = Normal, 1 = Alarm) R 10290 1 Boiler Operation (0 = Firing, 1 = Ready) R 10291 2 Low W ater Cutoff (0 = Normal, 1 = Alarm) R 10292 3 Low Pressure W ater (0 = Normal, 1 = Alarm) R 10293 4 Low Pressure Gas (0 = Normal, 1 = Alarm) R 10294 5 High Pressure Gas (0 = Norm ...

  • Raypak B6000 - page 23

    23 R 30070 40070 TS - Boiler S t art T imes (Sec) Boiler #1 R 30071 40071 TS - Boiler S t art T imes (Sec) Boiler #2 R 30072 40072 TS - Boiler S t art T imes (Sec) Boiler #3 R 30073 40073 TS - Boiler S t art T imes (Sec) Boiler #4 R 30074 40074 TS - Boiler S t art T imes (Sec) Boiler #5 R 30075 40075 TS - Boiler S t art T imes (Sec) Boiler #6 R 300 ...

  • Raypak B6000 - page 24

    24 Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 • F AX (805) 278-5489 Litho in U.S.A. www .rayp ak.com ...

メーカー Raypak カテゴリー Network Card

Raypak B6000のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- B6000の取扱説明書
- Raypakの製品カード
- パンフレット
- またはRaypak B6000の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Raypak B6000の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Raypak B6000の取り付け説明書、サービスマニュアル、簡易説明書、またはRaypak B6000のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Raypak B6000の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Raypak B6000デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがRaypak B6000を使用するのを助ける技術的文書のことです。説明書は通常、全てのRaypak B6000ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Raypakの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Raypak B6000の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははRaypak B6000の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Raypak B6000に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Raypak B6000デバイスの基本機能を使うにあたってのヒント。 Raypak B6000のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Raypak B6000に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるRaypak B6000のメーカー/サービスへの連絡先に関する情報。

Raypak B6000についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもRaypak B6000の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがRaypak B6000で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)