    1 18004 04/03/2007 Rev. C CG2 & MA2 Series Clean Agent FE-241 & HF C-227ea Owner’s Manual & Installation Instructions For all sizes 25 cubic feet to 1500 cubic feet Read and comply with all instructions, warnings and limitations before installing, servicing or removing this device. ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 2

    2 This owner’s manual and i nstallation instru ctions pamphlet is provided in English. Additional copies in English are availabl e at no charge by contacting the manufacturer, distributor or dealer. Co pies in the language of desti nation are available upon request for an additio nal fee. Fireboy-Xintex reserves the right to change features witho ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 3

    3 General Information Fireboy Automatic (CG series) and Manual/Automatic (MA) se ries Fire Extinguishing Systems are manufactured for a broad range of ap plications, including marine, industrial, and comm ercial uses. This booklet is intended to outline the proper installation of the sy stem for mari ne applications; most applications are similar. ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 4

    4 WARNING: • Never install a Fireboy system on the underside of a h atch cover or on an access door that may open or separate in an expl osion • Never install the actuator of a Fireboy sy stem in close proximity to exhaust manifolds or turbocha rgers. Radiated heat may cause premature actuation • Never install the actuator of a Fireboy system ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 5

    5 Volume Approximate Protected Diameter Total Height Age nt Weight Shipping Weight Model Number ft^3 m^3 in cm in cm lbs kgs lbs kgs U.S.C.G. # CG2-550-FE241 550 15.6 7.2 18 24.7 63 18.6 8.5 49 22.1 162.029/185/0 CG2-600-FE241 600 17 7.2 18 24.7 63 20.3 9.2 50 22.9 162.029/185/0 CG2-650-FE241 650 18.4 7.2 18 24.7 63 22 10 52 23.6 162.029/185/0 CG2- ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 6

    6 Volume Approximate Protected Diameter Total Height Age nt Weight Shipping Weight Model Number ft^3 m^3 in cm in cm lbs kgs lbs kgs U.S.C.G. # CG2-300-227 300 8.5 7.2 18 15.1 38 13 5.9 35 15.9 162.029/210/0 CG2-325-227 325 9.2 7.2 18 15.1 38 14 6.4 36 16.4 162.029/210/0 CG2-350-227 350 10 7.2 18 15.1 38 15.1 6.9 37 16.9 162.029/210/ 0 CG2-375-227 ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 7

    7 Marine Installation Instructions Before Installation 1. Check the system for damage during sh ipment. 2. Check the pressure gauge to be sure the gauge pointer lies within the green zone at 70°F (2 1°C). The correct weig ht is shown on the nameplate for the appropriate model. 3. Select an interior location not directly subject to weather or seaw ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 8

    8 Accommodating Diesel Engines 1. Failure to install an Automa tic Engine Shutdown in any compartment containing a diesel engine and a Fir eboy system impedes the fire extinguisher and may prevent fire extinguishment. 2. Automatic Engine Shutdown units are available through your Fireboy- Xintex distributor, dealer or retailer in three, five and eig ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 9

    9 WARNING: • An electrical short may result in electrical burn, injury or fire • Before attempting to wire the indicato r lamp, turn off all electrical current to the ignition switch • All Fireboy wiring must comply with the American Boat and Yacht Council Standard E9-9, titled Direct Cu rrent Electrical Systems for Boats, available from ABYC ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 10

    10 If the engine compartment is equipped with a powe red ventilation system, U.S. Coast Guard Rule 162.029 requires that the ground conne ction of the ventilation system be connected to the Fireboy system. Failure to connect a po wered ventilation system in the manner described belo w impedes fire extinguisher and may prev ent fire extinguishment. ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 11

    11 NOTE: Never push the cable at the T-handle end. Cable m ay jam and become inoperable. Fixing a jammed cable: 1. Turn the T-handle and threaded metal rod counter clo ckwise ½ turn until the jam releases . 2. If necessary, use a pair of pliers to carefully twist the threaded metal rod until the jam releases. 3. Pull the cable from the “S” hoo ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 12

    12 6. Pull cable to full extension. 7. Screw ferrule on to cable (approximately 4-5 turns maximum). 8. Slide o-ring onto c able shaft. 9. Screw red T-handle onto cable sha ft (Do not obstruct cross hole in T- handle). 10. Push red T-handle into ferrule to seat o-ring. 11. Align holes in ferrule and T-handle. 12. Temporarily install pull pin. 13. Al ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 13

    13 3. Push the cable end through the hole on the cylinder manifold far enough to allow the flexible strand to be bent. 4. Place “S” hook through the hole in the MA lever. 5. Gently pull cable sheath back into manifold, aligning the groove in sheath with slot in the manifold. 6. Insert the wire retaining clip provided around the groove in the ca ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 14

    14 1. A loud sound similar to small arms fire. 2. A loud sound of rushing air. 3. An extinguished indicator lamp. 4. A stalled engine. When actuation occurs 1. Immediately shutdown all engines, powered ventilation, and electrical systems. 2. Extinguish all smoking materials. 3. Do not open the engine compartment. After actuation 1. Before inspectin ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 15

    15 Inspect manual discharge cabl e annually when inspe cting the fire extinguisher. 1. Do not remove the pull pin on the T-handle when disconnecting the manual discharge cable fro m the fire extinguisher manifold. 2. Remove the wire retaining clip secu ring the cable located at the sl ot in the top of the manifold. 3. C arefully push the cable from ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 16

    16 Automatic Engine Shutdown/Override System is required for u se with Fireboy systems in diesel powered cr aft. Returning Fireboy-Xintex Equipment No product may be returned for credit or repair withou t a written “Returned Material Authorization” (RMA) form. Pu rchaser must call or email Fireboy-Xintex 616-735-9380 or fireboy@fireboy-xintex . ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 17

    17 NOTE: Detroit Diesel engines may require Auto matic Engine Shutdown system s with time delay. Fireboy accessories are av ailable from y our Fireboy-Xintex distributor, dealer or retailer. ...

  • Fireboy- Xintex, LTD MA2 FE-241 - page 18

    18 3 YEAR LIMITED WARRANTY This Warranty is in lieu of all ot her expressed of implied Wa rranties Seller warrants title, materials, and workmanship on equipment, except components manufactured by others for whic h the Seller assigns, as permitted, the original manufacturer’ s warranty. Seller’s warranty shall b e for a period of (3) three year ...

メーカー Fireboy- Xintex, LTD カテゴリー Fire Extinguisher

Fireboy- Xintex, LTD MA2 FE-241のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MA2 FE-241の取扱説明書
- Fireboy- Xintex, LTDの製品カード
- パンフレット
- またはFireboy- Xintex, LTD MA2 FE-241の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Fireboy- Xintex, LTD MA2 FE-241の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Fireboy- Xintex, LTD MA2 FE-241の取り付け説明書、サービスマニュアル、簡易説明書、またはFireboy- Xintex, LTD MA2 FE-241のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Fireboy- Xintex, LTD MA2 FE-241の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Fireboy- Xintex, LTD MA2 FE-241デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがFireboy- Xintex, LTD MA2 FE-241を使用するのを助ける技術的文書のことです。説明書は通常、全てのFireboy- Xintex, LTD MA2 FE-241ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Fireboy- Xintex, LTDの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Fireboy- Xintex, LTD MA2 FE-241の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははFireboy- Xintex, LTD MA2 FE-241の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Fireboy- Xintex, LTD MA2 FE-241に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Fireboy- Xintex, LTD MA2 FE-241デバイスの基本機能を使うにあたってのヒント。 Fireboy- Xintex, LTD MA2 FE-241のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Fireboy- Xintex, LTD MA2 FE-241に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるFireboy- Xintex, LTD MA2 FE-241のメーカー/サービスへの連絡先に関する情報。

Fireboy- Xintex, LTD MA2 FE-241についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもFireboy- Xintex, LTD MA2 FE-241の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがFireboy- Xintex, LTD MA2 FE-241で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)