NEC 500 UPS Uninterruptible Power Suppl y 100 VA C Use r ’s Manual 990-5021, Revision 1, 12/98 N8580-31 ...
-
NEC N8580-31 - page 2
i Important! Please read and save this manual. It provides installation and operating instructions that will help you get the fullest performance and service life from your UPS. About Your New UPS This Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags and surges from reaching your computer and other valuable elect ...
-
NEC N8580-31 - page 3
ii Table of Contents About Your New UPS .................................................................................................................................................... i 1. Safety ..................................................................................................................................................... ...
-
NEC N8580-31 - page 4
1 1. Safety ...
-
NEC N8580-31 - page 5
2 2. Attention from the Safety Point of View This section contains important instructions that should be followed during installation and maintenance of the NEC 500 and batteries. It is intended for customers who setup, install, relocate, or maintain APC equipment. Electrical Safety • EMC verification is VCCI - A. • Do not work alone under haza ...
-
NEC N8580-31 - page 6
3 3. Attention from the Operational and Maintenance Points of View Please charge the battery. The battery may not be fully charged when your UPS arrives. Please allow four to six hours for charging. To turn off the UPS, set the Enable switch to OFF. Pressing the Off button, does not turn off the UPS. To manually turn it off, set the Enable switch t ...
-
NEC N8580-31 - page 7
4 5. Name and Function of Parts 1) Front View 5 0 0 With the UPS plugged in, press and release the large upper on/test button to supply power to the loads. The loads are immediately powered while the UPS beeps and performs a self-test . Press and release the small, lower off button to turn off power to the loads. It may be convenient to use the UPS ...
-
NEC N8580-31 - page 8
5 Replace Battery If the battery fails a self-test, the UPS emits short beeps for one minute and the replace battery LED illuminates. The UPS repeats the alarm every five hours. Perform the self-test procedure to confirm replace battery conditions. The alarm stops when the battery passes the self-test. Battery Charge Bar Graph The 5-LED display on ...
-
NEC N8580-31 - page 9
6 2) Rear View 500 V A Computer Interface Port Power management software and interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the 9-pin computer interface port on the back panel of the UPS. Secure the connector’s screws to complete the connection. Ground Lead ...
-
NEC N8580-31 - page 10
7 7. Operating Instructions With the UPS plugged in, press and release the large upper on/test button to supply power to the loads. Press and release the small, lower off button to turn off power to the loads. Note: Whenever the UPS is plugged in and utility voltage is present, the charger maintains battery charge. The on-line LED illuminates when ...
-
NEC N8580-31 - page 11
8 8. Function Self-test The UPS performs a self-test automatically when turned on with the enable switch (by default). Automatic self-test eases maintenance requirements by eliminating the need for periodic manual self-tests. During the self-test, the UPS briefly operates the loads on-battery. If the UPS passes the self-test, it returns to on-line ...
-
NEC N8580-31 - page 12
9 9. Abnormal Conditions and Protection Functions Smart Boost / Smart Trim The SmartBoost LED comes on to indicate that the UPS is compensating for a low voltage . The SmartTrim LED comes on to indicate that the UPS is compensating for a high voltage . Overload When the UPS is overloaded (when the connected loads exceed the maximum specified in the ...
-
NEC N8580-31 - page 13
10 10. Troubleshooting Use the chart below to solve minor UPS installation problems. Contact NEC Technical Support Staff for assistance with complex UPS problems. Problem and Possible Cause Solution UPS will not turn on. • On/test button not pushed. Set the UPS enable switch to 1. Set the Auto/Local switch to Local. Then press the on/test button ...
-
NEC N8580-31 - page 14
11 11. Maintenance and Checks Storage Storage Conditions Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least 4 hours. Extended storage • At -15 to +30 ° C (+5 to +86 ° F), charge the UPS’s battery every 6 months. • At +30 to +45 ° C (+86 to +113 ° F), charg ...
-
NEC N8580-31 - page 15
12 Specifications N8580-31 500 VA Acceptable input voltage 0 - 160 VAC Output voltage 90 - 110 VAC Input Protection Resettable circuit breaker Frequency limits (on-line operation) 50 or 60 Hz, +2%, -4% Transfer time 2 ms (normal) 4 ms (maximum) Maximum load 500 VA / 320 W On-battery output voltage 100 VAC On-battery frequency 50 or 60, ± 0.1 Hz; u ...