    Model 109SS Temperature Probe Revision: 12/10 Copyright © 1983-2010 Campbell Scientific, Inc. ...

  • Campbell TEMPERATURE PROBE 109SS - page 2

    Warranty and Assistance The MODEL 109SS TEMPERATURE PROBE FOR HARSH ENVIRONMENTS is warranted by Campbell Scientific, Inc. to be free from defects in mat erials and workma nship under normal use and servi ce for twelve (12) months from date of shipm ent unless specified otherwi se. Batteri es have no warranty. Cam pbell Scienti fic, Inc. 's ob ...

  • Campbell TEMPERATURE PROBE 109SS - page 3

    109SS Table of Contents PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat® bookmarks tab for links to specific sections. 1. General ......................................................................... 1 1.1 Specifications................................................................... ...

  • Campbell TEMPERATURE PROBE 109SS - page 4

    ...

  • Campbell TEMPERATURE PROBE 109SS - page 5

    Model 109SS Temperature Probe 1. General The –L portion of this probe’s m odel number i ndicates the probe has a user- specified lead length. For readab ility purposes, the pro b e will be referred to as the 109SS throughout this docum ent. The 109SS consists of a thermistor encas ed in a stainless-steel sheath. The rugged stainless-steel sheat ...

  • Campbell TEMPERATURE PROBE 109SS - page 6

    Model 109SS Temperature Probe 1.1 Specifications Temperature Range: -40° to +70°C Survival Range: -50° to +100°C (thermist or); -50°C to +70°C (overm olded joint and cable) Thermistor Interchangeability Tolerance: Temperature Tolerance -40°C ± 0.6°C 0°C ± 0.38°C 25°C ± 0.1°C 50°C ± 0.3°C 70°C ± 0.45°C Time Constant: Fluid τ St ...

  • Campbell TEMPERATURE PROBE 109SS - page 7

    Model 109SS Temperature Probe 2. Accuracy The overall probe accuracy is a combinati on of the thermi stor's interchangeability specification and the accuracy of the bri dge resistor. The Steinhart and Hart equation used to calculate temperature has a negl igible error (Figure 2-1). In a "worst case" the errors add to an accuracy of ? ...

  • Campbell TEMPERATURE PROBE 109SS - page 8

    Model 109SS Temperature Probe 3. Installation and Wiring 3.1 Burial The 109SS is suitable for shallow burial onl y. It should be placed horizontally at the desired depth to avoid thermal conduction from the surface to the thermistor. Placem ent of the cable in side a rugged conduit may be advisable for long cable runs, especially in locations subje ...

  • Campbell TEMPERATURE PROBE 109SS - page 9

    Model 109SS Temperature Probe The datalogger is programme d using eith er CRBasic or Edlog. Dataloggers that use CRBasic include our CR200( X)-series, CR800, CR850, CR1000, CR3000, CR5000, and CR9000(X); see Section 5.1. Dataloggers t hat use Edlog include our CR10, CR 10(X), CR23X, and CR7; refer t o Section 5.2. CRBasic and Edlog are included in ...

  • Campbell TEMPERATURE PROBE 109SS - page 10

    Model 109SS Temperature Probe 5.1.1.1 Sample Program for CR200(X) Series Datalogger 'CR200(X) Seri es Datalogger ‘This example program measures a single 109SS Thermist or Probe ‘once a second and stores the aver age temperature every 10 minutes. ‘Declare the variable for th e temperature measurement Public Air_Temp ‘Define a data table ...

  • Campbell TEMPERATURE PROBE 109SS - page 11

    Model 109SS Temperature Probe 5.1.1.3 Sample Program for CR5000 'CR5000 'This example program measures a single 109 Thermist or probe 'once a second and stores the aver age temperature every 10 minutes. 'Declare the variable for the temperature. Public Air_Temp 'Declare variables for the raw measurement, t hermistor resista ...

  • Campbell TEMPERATURE PROBE 109SS - page 12

    Model 109SS Temperature Probe Example Program for CR10X ;{CR10X} ; *Table 1 Program 01: 1 Execution Interval (seconds) 1: AC Half Bridge (P5) 1: 1 Reps 2: 25 2500 mV 60 Hz Reject ion Range 3: 1 SE Channel 4: 1 Excite all reps w/Exchan 1 5: 2500 mV Excitati on 6: 1 Loc [ V_Vx ] 7: 1.0 Mult 8: 0.0 Offset 2: Z=1/X (P42) 1: 1 X Loc [ V_Vx ] 2: 2 Z Loc ...

  • Campbell TEMPERATURE PROBE 109SS - page 13

    Model 109SS Temperature Probe 9: Z=X+F (P34) 1: 8 X Loc [ Tk ] 2: -273.15 F 3: 9 Z Loc [ Air_Temp ] 10: If tim e is (P92) 1: 0 Minutes (Seconds --) into a 2: 10 Interval (same uni ts as above) 3: 10 Set Output Flag Hi gh (Flag 0) 11: Real Tim e (P77) 1: 110 Day,Hour/Minut e (midni ght = 0000) 12: Average (P71) 1: 1 Reps 2: 9 Loc [ Air_Temp ] *Table ...

  • Campbell TEMPERATURE PROBE 109SS - page 14

    Model 109SS Temperature Probe 1: Excite-Delay (SE) (P4) 1: 1 Reps 2: 25 2500 mV 60 Hz Rejecti on Range (Delay m ust be zero) 3: 1 SE Channel 4: 1 Excite all reps w/Exchan 1 5: 2 Delay (0.01 sec units) 6: 2500 mV Excitati on 7: 3 Loc [V_Vx ] 8: .0004 Multiplier 9: 0.0 Offset 6. Measurement Details Understanding the detail s in this section are not n ...

  • Campbell TEMPERATURE PROBE 109SS - page 15

    Model 109SS Temperature Probe The resistance of the thermistor is: ⎟ ⎠ ⎞ ⎜ ⎝ ⎛ − = 1 900 , 24 V V R EX t The Steinhart and Hart equation i s used to calculate temperature from Resistance: 3 )) (ln( ) ln( 1 T T K R C R B A T + + = Where T K is the temperature in Kelvin . Th e Steinhart and Ha rt coefficients used in the Therm109 instru ...

  • Campbell TEMPERATURE PROBE 109SS - page 16

    Model 109SS Temperature Probe 12 Symptom: Unstable Tem perature Try using the 60 Hz o r 50 Hz integratio n options, and /o r increasing the settling time as descri bed in Sections 8 and 9. Make sure the clear shi eld wire is connected to datalogger ground, and the dat alogger is properly grounded. ...

  • Campbell TEMPERATURE PROBE 109SS - page 17

    ...

  • Campbell TEMPERATURE PROBE 109SS - page 18

    Campbell Scientific Companies Campbell Scientific, Inc. (CSI) 815 West 1800 Nort h Logan, Utah 84 321 UNITED STATES www.campbellsci.com • info@cam pbellsci.com Campbell Scientific Afri ca Pty. Lt d. (CSAf) PO Box 2450 Somerset West 7129 SOUTH AFRICA www.csafrica.co .za • cleroux@csafrica.co.za Campbell Scientific Aust ralia Pty. Ltd. (CSA) PO B ...

メーカー Campbell カテゴリー Power Supply

Campbell TEMPERATURE PROBE 109SSのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- TEMPERATURE PROBE 109SSの取扱説明書
- Campbellの製品カード
- パンフレット
- またはCampbell TEMPERATURE PROBE 109SSの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Campbell TEMPERATURE PROBE 109SSの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Campbell TEMPERATURE PROBE 109SSの取り付け説明書、サービスマニュアル、簡易説明書、またはCampbell TEMPERATURE PROBE 109SSのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Campbell TEMPERATURE PROBE 109SSの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Campbell TEMPERATURE PROBE 109SSデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCampbell TEMPERATURE PROBE 109SSを使用するのを助ける技術的文書のことです。説明書は通常、全てのCampbell TEMPERATURE PROBE 109SSユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Campbellの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Campbell TEMPERATURE PROBE 109SSの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCampbell TEMPERATURE PROBE 109SSの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Campbell TEMPERATURE PROBE 109SSに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Campbell TEMPERATURE PROBE 109SSデバイスの基本機能を使うにあたってのヒント。 Campbell TEMPERATURE PROBE 109SSのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Campbell TEMPERATURE PROBE 109SSに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCampbell TEMPERATURE PROBE 109SSのメーカー/サービスへの連絡先に関する情報。

Campbell TEMPERATURE PROBE 109SSについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCampbell TEMPERATURE PROBE 109SSの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCampbell TEMPERATURE PROBE 109SSで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)