  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 1

    Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS .................1 GENERAL ..................................1 INST ALLA TION ............................ 1-12 Step 1 − Complete Pre-Installation Checks ..1 Step 2 − Rig and Place Unit ................7 • RIGGING • PLACING THE UNIT • VIBRA TION ISOLA TIO ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 2

    Fig. 1 — 09BY Unit (008-014 Shown) 2 ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 3

    LEGEND Refrigerant Connection Field-Supplied Refrigerant Piping *Field-Supplied Floor Stand (Height to Match W all Opening). Fig. 2 — Mounting Applications 09BY DISCHARGE DUCT INLET DUCT TO OUTSIDE INSULA TE IF THROUGH CONDITIONED SP ACE HANGER RODS TO RAIN DRAIN (REQUIRED IF RAIN WILL ENTER UNIT) TO REFRIGERANT PIPING COMPRESSOR/ EV APORA TOR UN ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 4

    09BY DIMENSIONS (English) DIMENSION 006 (Ft-in.) 008 (Ft-in.) 012 (Ft-in.) 014 (Ft-in.) 016,024 (Ft-in.) A 2-1 1 1 ⁄ 2 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 5- 0 B 1- 7 11 ⁄ 16 1-1 1 5 ⁄ 8 1-1 1 5 ⁄ 8 1-1 1 5 ⁄ 8 2- 9 7 ⁄ 16 C 4- 0 7 ⁄ 16 4- 8 5- 3 1 ⁄ 2 5-1 1 7- 6 9 ⁄ 16 D 1-1 1 1 ⁄ 4 2- 3 9 ⁄ 16 2- 3 9 ⁄ 16 2- 3 9 ? ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 5

    NOTES: 1. Operational clearances are 0 in. on all sides of the unit. 2. Service clearances are 0 in. (minimum) on the top, rear , and front of the unit. A minimum of 3 ft service clearance is required on the unit right side, an da3f t clearance is recommended on the left side (2 ft is the minimum). One side of the unit (either right, left, or rear) ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 6

    T able 1 — Condenser Unit Application UNIT 50BZ 09BY 006 008 012 014 016 024 006 S 008 S 012 OS 014 OS 016 OS 024 OS LEGEND S— Standard O— Optional NOTE: Contact your local representative for use with reciprocating air-cooled chillers and other compressor-bearing unit combinations. T able 2 — Physical Data UNIT 09BY 006 008 012 014 016 024 ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 7

    Step 2 — Rig and Place Unit RIGGING — The 09BY units are mounted on skids. Leave the unit on the skid until it is in the final position. While on the skid, the unit can be rolled, dragged or forklifted; do not apply for ce to the unit. Use a minimum of 3 rollers when rolling, and raise from above to remove the skid when unit is in the final p ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 8

    Step 3 — Install Accessory Low-Ambient Kit or Inlet Filter Kit (If Required) — If the unit will be op- erated with inlet air to the condenser below 50 F , a low- ambient damper may be required. The low-ambient kit con- trols head pressure by discharge dampers on the condenser fan. The dampers are actuated by a refrigerant-operated pis- ton conn ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 9

    LIQUID LIFT — Amount of liquid lift available before re- frigerant flashing occurs depends on amount of liquid sub- cooling in the system. All 09BY condensers have positive subcooling when ap- plied with optimum charge. W ith subcooling, it is possible to overcome an appreciable pressure drop and/or static head pressure (due to elevation of the ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 10

    CHECK V AL VE — When the 09BY condenser is installed with the condenser located above the compressor evapora- tor , it is recommended that a field-supplied check valve be installed on the hot gas discharge line. This prevents refrig- erant which condenses in the discharge line during the of f cycle from draining back into the compressor . Instal ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 11

    3. A high-density fiberglass (2 lb minimum density) or semi- rigid foamed insulation such as Styrofoam™ will be re- quired inside the ducts to prevent air erosion. The insu- lation must be firmly secured in the discharge duct near the blower discharge to withstand the high air velocity . Step 7 — Insulate the Unit — The 09BY units are not i ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 12

    Determine maximum deviation from average voltage: (AB) 243 – 23 9=4v (BC) 239 – 23 6=3v (AC) 239 – 23 8=1v Maximum deviation is then 4 v . T o determine the percentage of voltage imbalance: 4 % V oltage Imbalance = 100 x 239 = 1.7% This amount of phase imbalance is satisfactory since it is below the allowable maximum of 2%. IMPOR T ANT : If s ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 13

    ST ART -UP To prevent personal injury, be sure wire fan guards are secured in place over each fan discharge (or that fans are ducted) before starting the unit. Complete Unit Start-Up Checklist on page CL-1 prior to start-up of this system. System Evacuation and Dehydration — Refer to GT AC II, Module 4, ‘ ‘Dehydration for Proper Evacuation an ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 14

    T able 5 — Condenser Fan Performance UNIT 09BY AIRFLOW (Cfm) EXTERNAL ST A TIC PRESSURE (in. wg) 0.0 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 006 2000 676 0.26 905 0.51 1085 0.80 1230 1.08 1348 1.34 1449 1.60 2500 845 0.51 1039 0.82 1 197 1.14 1339 1.51 1466 1.88 1570 2.21 3000 1014 0.88 1 188 1.28 1321 1.61 1450 2.02 1 ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 15

    TO CHANGE F AN WHEEL — If a fan wheel should fail, it may be replaced as follows: 1. Remove belts from fan pulley . 2. Loosen locking collars on the fan bearings and set screws on the fan wheels. 3. Remove the shaft through the access panel on either side of the unit. 4. Remove the fan cut-of f plate in the fan discharge. 5. Remove the fan wheel ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 16

    TROUBLESHOOTING See T able 6 for problems and possible solutions. T a b l e6—T roubleshooting PROBLEM POTENTIAL CAUSE SOLUTION Unit is tripping on high-pressure switch or high discharge pressure is noted. 1. Fan belts are slipping or broken. 2. Fan is not delivering adequate air for condenser . 3. Low-ambient damper is not functioning correctly ( ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 17

    ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 18

    Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 4 Ta b 4 a 4 a PC 1 1 1 Catalog No. 530-969 Printed in U.S.A. Form 09BY -2SI Pg 18 9-96 Replaces: 09BY -1SI ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 19

    ST ART -UP CHECKLIST A. Preliminary Information COMPRESSOR BEARING UNIT : MODEL NO. SERIAL NO. 09BY UNIT : MODEL NO. SERIAL NO. FIELD-INST ALLED ACCESSORIES B. Pre-Start-Up CONDENSING UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y . DOES IT AGREE WITH UNIT? (Y/N) HAS THE GR ...

  • Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - page 20

    CHECK VOL T AGE IMBALANCE IS CONDENSER MOTOR WIRED FOR CORRECT VOL T AGE? (Y/N) LINE-TO-LINE VOL TS: AB VA C VB C V (AB + AC + BC)/3 = A VERAGE VOL T AGE = V MAXIMUM DEVIA TION FROM A VERAGE VOL T AGE = V VOL T AGE IMBALANCE = 100 X (MAX DEVIA TION)/(A VERAGE VOL T AGE) = % IF OVER 2% VOL T AGE IMBALANCE, DO NOT A TTEMPT TO ST AR T SYSTEM! CALL LOC ...

メーカー Carrier カテゴリー Fan

Carrier AIR-COOLED CONDENSER UNITS 09BY006-024のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- AIR-COOLED CONDENSER UNITS 09BY006-024の取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier AIR-COOLED CONDENSER UNITS 09BY006-024の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier AIR-COOLED CONDENSER UNITS 09BY006-024の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier AIR-COOLED CONDENSER UNITS 09BY006-024の取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier AIR-COOLED CONDENSER UNITS 09BY006-024のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier AIR-COOLED CONDENSER UNITS 09BY006-024の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Carrier AIR-COOLED CONDENSER UNITS 09BY006-024デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier AIR-COOLED CONDENSER UNITS 09BY006-024を使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier AIR-COOLED CONDENSER UNITS 09BY006-024ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier AIR-COOLED CONDENSER UNITS 09BY006-024の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier AIR-COOLED CONDENSER UNITS 09BY006-024の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier AIR-COOLED CONDENSER UNITS 09BY006-024に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier AIR-COOLED CONDENSER UNITS 09BY006-024デバイスの基本機能を使うにあたってのヒント。 Carrier AIR-COOLED CONDENSER UNITS 09BY006-024のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier AIR-COOLED CONDENSER UNITS 09BY006-024に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier AIR-COOLED CONDENSER UNITS 09BY006-024のメーカー/サービスへの連絡先に関する情報。

Carrier AIR-COOLED CONDENSER UNITS 09BY006-024についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCarrier AIR-COOLED CONDENSER UNITS 09BY006-024の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCarrier AIR-COOLED CONDENSER UNITS 09BY006-024で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)