    IMPORT ANT —READ BEFORE INST ALLING 1. Read and become familiar with these installation instructions before installing this unit (Fig. 1). 2. Be sure the installation conforms to all applicable local and national codes. 3. These instructions contain important information for the proper maintenance and repair of this equipment. Re- tain these inst ...

  • Bryant 569C - page 2

    NOTE: If vibration isolators are required for a particular in- stallation, use corner weight information in Fig. 2 to make proper selection. I. LOCA TE THE UNIT A. Clearance Maintain clearance around and above unit to provide mini- mum distance from combustible materials, proper airflow , and service access. Refer to Fig. 2 and 3. Minimum clearanc ...

  • Bryant 569C - page 3

    T able 1A — Specifications (English) UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAP ACITY (T ons) 67 1 ⁄ 2 10 7 1 ⁄ 2 8 1 ⁄ 2 10 OPERA TING WEIGHT (lb) Aluminum Coils (Standard) 340 370 395 510 564 564 Copper Coils (Optional) 386 438 472 578 632 632 RIGGING WEIGHT (lb) Aluminum Coils (Standard) 390 420 445 560 614 614 Cop ...

  • Bryant 569C - page 4

    T able 1B — Specifications (SI) UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAP ACITY (kW) 21 26 35 26 29.9 35 OPERA TING WEIGHT (kg) Aluminum Coils (Standard) 154 168 179 231 256 256 Copper Coils (Optional) 175 199 214 262 287 287 RIGGING WEIGHT (kg) Aluminum Coils (Standard) 176 191 202 254 279 279 Copper Coils (Optional) 198 ...

  • Bryant 569C - page 5

    UNIT DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F 569C072 1 8 -6 1 ⁄ 2 9 1 8 -2 3 ⁄ 4 9 —1 8 -2 1 ⁄ 4 9 1 8 -4 5 ⁄ 16 9 2 8 -9 5 ⁄ 16 9 [470.0] [375.0] — [362] [415] [846.5] 569C090 1 8 -8 9 1 8 -6 1 ⁄ 2 9 —1 8 -3 9 2 8 - 5 ⁄ 16 9 3 8 -5 7 ⁄ 16 9 [508.0] [470.0] — [381] [613] [1052.5] 569C120 1 8 -9 9 1 8 -8 9 2 8 -0 9 1 8 -3 9 ...

  • Bryant 569C - page 6

    B. Filter Drier and Moisture Indicator The filter drier is factory installed. Moisture indicator is a field-installed accessory and should be installed just after liq- uid line shutof f valve. Do not use a receiver . A receiver is not supplied with the unit and should not be used. NOTE: Unit is shipped with R-22 holding charge. System pres- sure ...

  • Bryant 569C - page 7

    All units except 208/230-v units are factory wired for the volt- age shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply , the transformer must be rewired by moving the black wire from the 230-v orange wire on the transformer and connecting it to the 200-v red wire from the transformer . The end of the orange wi ...

  • Bryant 569C - page 8

    T able 4 — Electrical Data UNIT NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y Min Max RLA LRA FLA MCA MOCP 569C072 208/230-3-60 187 254 21.8 142 1.9 25.6 35 460-3-60 414 508 9.6 72 1.0 12.9 15 575-3-60 518 632 7.6 58 1.9 1 1.4 15 220-3-50 198 242 19.0 142 1.0 25.6 35 400-3-50 360 440 9.5 72 1.0 12.9 15 569C090 208/230- ...

  • Bryant 569C - page 9

    T able 5 — American/European Wire Conversions AMERICAN EUROPEAN Industry Standard Size American Conversion (mm 2 ) Industry Standard Size (mm 2 ) 18 A WG 0.82 1.0 16 A WG 1.30 1.5 14 A WG 2.08 2.5 12 A WG 3.30 4.0 10 A WG 5.25 6.0 8A W G 6.36 10.0 6A W G 13.29 16.0 4A W G 21.14 25.0 3A W G 26.65 — 2A W G 33.61 35.0 1A W G 42.39 50.0 1/0 A WG 53 ...

  • Bryant 569C - page 10

    ST ART -UP I. ST ART -UP AND ADJUSTMENTS CAUTION: Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor tem- perature is below 25 F ( 2 4 C) (unless accessory low am- bient kit is installed). A. Checking Co ...

  • Bryant 569C - page 11

    SERVICE W ARNING: When servicing unit, shut of f all electri- cal power to unit to avoid shock hazard or injury from rotating parts. I. CLEANING Inspect unit interior at the beginning of each cooling season and as operating conditions require. A. Condenser Coil Inspect coil monthly . Clean condenser coil annually , and as required by location and o ...

  • Bryant 569C - page 12

    IV . CAP ACITY CONTROL (576B120 Only) A suction pressure-actuated unloader controls 2 cylinders and provides capacity control. Unloaders are factory set (see T able 1A or 1B), but may be field adjusted: A. Control Set Point The control set point (cylinder load point) is adjustable from 0 to 85 psig (586 kPa). T o adjust, turn control set point ad- ...

  • Bryant 569C - page 13

    Fig. 14 — Cooling Charging Chart — 569C072 Fig. 15 — Cooling Charging Chart — 569C090,120 and 576B090,102,120 —13— ...

  • Bryant 569C - page 14

    TROUBLESHOOTING GUIDE SYMPTOM CAUSE REMEDY Compressor does not run — Contactor open Power off. Restore power . Fuses blown. Replace with correct fuses after finding cause and correcting. T ransformer open/shorted. Replace transformer if primary windings are receiving power and no output. Thermostat circuit open. Check thermostat setting. Low-pre ...

  • Bryant 569C - page 15

    LEGEND FOR FIG. 16 AND 17 C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor COTP — Compressor T emperature Protection EQUIP — Equipment GND — Ground HPS — High-Pressure Switch LPS — Low-Pressure Switch NEC — National Electrical Code OFC — O ...

  • Bryant 569C - page 16

    ...

  • Bryant 569C - page 17

    ...

  • Bryant 569C - page 18

    Copyright 1999 Bryant Heating & Cooling Systems CA TALOG NO. 5356-902 ...

  • Bryant 569C - page 19

    ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES II. PRE-ST ART -UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y . DOES IT AGREE WITH UNIT? (Y/N) HAS THE G ...

  • Bryant 569C - page 20

    III. ST ART -UP CHECK EV APORA TOR-F AN SPEED AND RECORD. CHECK CONDENSER-F AN SPEED AND RECORD. AFTER A T LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE (576B only) SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER-AIR TEMP LEA VING CONDENSER-AIR TEMP EV AP ENTERING-AIR DB ...

メーカー Bryant カテゴリー Air Conditioner

Bryant 569Cのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 569Cの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant 569Cの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant 569Cの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant 569Cの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant 569Cのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant 569Cの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant 569Cデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant 569Cを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant 569Cユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant 569Cの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant 569Cの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant 569Cに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant 569Cデバイスの基本機能を使うにあたってのヒント。 Bryant 569Cのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant 569Cに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant 569Cのメーカー/サービスへの連絡先に関する情報。

Bryant 569Cについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant 569Cの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant 569Cで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)