    Air -Conditioner s SEZ-A12, A18, A24AR English INST ALLA TION MAN U AL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. FOR INSTALLER ...

  • Mitsubishi Electronics SEZ-A12 - page 2

    2 Contents 1. Safety precautions ................................................................................... 2 2. Selecting the installation location ............................................................. 2 3. Installation diagram & Accessories .......................................................... 3 4. Indoor unit installati ...

  • Mitsubishi Electronics SEZ-A12 - page 3

    3 3. Installation diagram & Accessories 3.1. Indoor unit (Fig. 3-1) 1 Air inlet (rear side) *Select the either back side or bottom side 2 Electrical par ts bo x 3 Suspension bolt pitch 5 Access door 6 Service space (It is necessar y to maintain a working service area from the ceiling.) 7 Air inlet (bottom side) *Select the either back side or b ...

  • Mitsubishi Electronics SEZ-A12 - page 4

    4 AB 1 2 3 3. Installation diagram & Accessories Fig. 3-3 3.3. Checking the indoor unit accessories (Fig. 3-3) Check that the indoor unit is equipped with the f ollo wing parts and accessor ies: A Refrigerant pipe parts 1 Pipe cov er (for refrigerant piping joint) Small diameter × 1 Large diameter × 1 2 Bands for tempor ary tightening of pipe ...

  • Mitsubishi Electronics SEZ-A12 - page 5

    5 5. Refrig erant piping w ork 5.1. Refrigerant pipe (Fig. 5-1) Maximum difference betw een heights of indoor unit and outdoor unit, the length of refrigerant piping and the number of bends in piping are within limits shown belo w . Models (A) Pipe length (B) Height (C) Number of (one wa y) difference bends (one way) SEZ-A12AR max. 20 m max. 12 m m ...

  • Mitsubishi Electronics SEZ-A12 - page 6

    6 a d c b ef 90 ° d c b a 5. Refrigerant piping work b a a b e b c d c A 5.2. Flaring work • Main cause of gas leakage is def ect in flaring work. Carry out correct flar ing w ork in the following procedure . 5.2.1. Pipe cutting (Fig. 5-3) • Using a pipe cutter cut the copper tube correctly . 5.2.2. Burrs remo v al (Fig. 5-4) • Completely re ...

  • Mitsubishi Electronics SEZ-A12 - page 7

    7 5. Refrig erant piping w ork 5.4. Purging pr ocedures leak test PURGING PROCEDURES Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor and the outdoor units. Remove the service port cap of the stop valv e on the side of the outdoor unit gas pipe . (The stop valv e will not work in its initial state fresh out of the f ...

  • Mitsubishi Electronics SEZ-A12 - page 8

    8 7. Electrical work N A B H C F D E A G N 2 3 N 2 3 N L L 1 2 N B C F E N 2 3 12 N L L A H A D C E A G N 3 N F N L L (1) SEZ-A12AR (1:1 SYSTEM) 7.1. P ower supply (Fig. 7-1) Electrical specification Input capacity Main Switch/Fuse (A) P ow er supply SEZ-A12AR SEZ-A18AR SEZ-A24AR (1 phase ~/N, 220-240V , 50Hz) 10 20 20 Warning: • Do not use inter ...

  • Mitsubishi Electronics SEZ-A12 - page 9

    9 7. Electrical work Fig. 7-4 LN N 2 3 N 2 3 1 2 5 12 7 6 3 4 65 mm 15 mm 1 2 Fig. 7-3 • P erform wiring as shown in the diagr am to the lower left. (Procure the cable lo- cally). (Fig. 7-3) Make sure to use cables of the correct polarity only . 1 Connecting cable 2 P ow er supply cable 4 core VVF cab le 3 core with ground IEC cord • SEZ-A12:1. ...

  • Mitsubishi Electronics SEZ-A12 - page 10

    10 7.4. Outdoor unit (Fig. 7-8) • Connect cable from the indoor unit correctly on the terminal-bloc k. • Use the same terminal block and polarity as is used with the indoor unit. • For aftercare maintenance , giv e extr a length to connecting cable . • Both end of connecting cable (e xtension wire) are peeled off . When too long, or connect ...

  • Mitsubishi Electronics SEZ-A12 - page 11

    11 9. Air filter installation 9.1. Confirmation of enc losed par ts (Fig. 9-1) • Please ensure all the par ts sho wn below are present bef ore starting installation. 1 Filter × 1 2 Filter rail × 1 3 Filter rail × 1 4 ST . screw (4 × 10) × 14 5 Clamp × 2 6 Seal × 2 12 3 Fig. 9-1 6 Cut out Cut out Hole 45 A A B C C 2 1 3 4 Fig. 9-2 9.2. Filt ...

  • Mitsubishi Electronics SEZ-A12 - page 12

    12 9. Air filter installation 9.4. Filter installation points (Rear air intake) (Fig. 9-4) 1. Inser t the filter into rail 2 2. Hook the filter onto rail 3 A Control box B Drain pan D Filter E Rail 2 F Rail 3 Fig. 9-4 1 2 B A E D F Fig. 9-5 2 1 A E D F A F H G E 9.5. Filter installation points (Bottom air intake) (Fig. 9-5) 1. Inser t the filter in ...

  • Mitsubishi Electronics SEZ-A12 - page 13

    13 10.1. Bef ore test run s After completing installation and the wiring and piping of the indoor and outdoor units, c heck f or refrigerant leakage, looseness in the power suppl y or control wiring, wr ong polarity , and no disconnection of one phase in the supply . s Use a 500-volt megohmmeter to c heck that the resistance between the po wer supp ...

  • Mitsubishi Electronics SEZ-A12 - page 14

    14 10.4. A UT O REST ART FUNCTION This model is equipped with the A UT O REST ART FUNCTION. When the indoor unit is controlled with the remote controller , the operation mode, set temperature , and the fan speed are memorized b y the indoor controller board. The auto restart function sets to wor k the moment the po wer has restored after power f ai ...

  • Mitsubishi Electronics SEZ-A12 - page 15

    15 1 Wiring from the Remote Control This wire is connected to terminal block f or remote controller of the indoor unit (non- polar). 2 When a Different Refrigerant System Grouping is Used. Up to 4 refrigerant systems can be controlled as one group using the MA remote controller . There is need to set up JP17, JP18 jumper wire of indoor controller b ...

  • Mitsubishi Electronics SEZ-A12 - page 16

    Please be sure to put the contact address/telephone number on this manual before handing it to the customer. • Low Voltage Directive 73/23/ EEC • Electromagnetic Compatibility Directive 89/ 336/ EEC This product is designed and intended for use in the residential, commercial and light-industrial environment. HEAD OFFICE: MITSUBISHI DENKI BLDG., ...

メーカー Mitsubishi Electronics カテゴリー Air Conditioner

Mitsubishi Electronics SEZ-A12のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- SEZ-A12の取扱説明書
- Mitsubishi Electronicsの製品カード
- パンフレット
- またはMitsubishi Electronics SEZ-A12の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Mitsubishi Electronics SEZ-A12の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Mitsubishi Electronics SEZ-A12の取り付け説明書、サービスマニュアル、簡易説明書、またはMitsubishi Electronics SEZ-A12のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Mitsubishi Electronics SEZ-A12の製品を使用するにあたって最も人気のある説明書を閲覧できます。

Mitsubishi Electronics SEZ-A12デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがMitsubishi Electronics SEZ-A12を使用するのを助ける技術的文書のことです。説明書は通常、全てのMitsubishi Electronics SEZ-A12ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Mitsubishi Electronicsの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Mitsubishi Electronics SEZ-A12の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははMitsubishi Electronics SEZ-A12の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Mitsubishi Electronics SEZ-A12に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Mitsubishi Electronics SEZ-A12デバイスの基本機能を使うにあたってのヒント。 Mitsubishi Electronics SEZ-A12のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Mitsubishi Electronics SEZ-A12に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるMitsubishi Electronics SEZ-A12のメーカー/サービスへの連絡先に関する情報。

Mitsubishi Electronics SEZ-A12についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもMitsubishi Electronics SEZ-A12の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがMitsubishi Electronics SEZ-A12で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)