    GENERAL YORK Model B1HH units are factory assembled heat pumps designed for outdoor installation on a roof top or a slab. Field- installed electric heater accessories are available to provide supplemental electric heat combined with electric cooling and heating. The units are completely assembled on rigid, removable base rails. All piping, refriger ...

  • York THRU 060 - page 2

    LIMIT ATIONS These units must be installed in accordance with the following national and local safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions). 2. Local plumbing and waste water codes and other applica - ble local codes. Refer to T able 1 for unit application data and to T able ...

  • York THRU 060 - page 3

    CLEARANCES All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for com - bustion, construction, servicing and proper unit operation. WARNING: Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet. DUCT WORK These units are adaptable to downflow ...

  • York THRU 060 - page 4

    66297-YIM-C-0205 4 Unitary Products Group T ABLE 3 - PHYSICAL DA T A MODELS BHH 018 024 030 036 042 048 060 INDOOR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd. in.) 9 X 6 10 X 8 10 X 8 10 x 8 1 1 x 10 1 1 x 10 1 1 x 10 F AN MOTOR HP (Three Speed) 1 INDOOR COIL ROWS DEEP 2233333 FINS PER INCH 15 15 13 15 16 16 16 F ACE AREA (Sq. Ft.) 4.38 4.38 4.38 4.38 5. ...

  • York THRU 060 - page 5

    66297-YIM-C-0205 Unitary Products Group 5 MODEL BHH POWER SUP - PL Y VOL TAGE LIMIT ATIONS 1 COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, AMPS 2 MAX. HACR BREAKER SIZE, AMPS UNIT POWER F ACTOR TRANSFORMER SIZE (V A) MIN. MAX. RLA LRA 018 208/230-1-60 187 253 7.1 48.0 1.1 2.6 12.5 15 15 0 ...

  • York THRU 060 - page 6

    66297-YIM-C-0205 6 Unitary Products Group T ABLE 5 - ELECTRICAL DA T A (12 SEER HEA T PUMP / ELECTRIC HEA T) MODEL BHH POWER SUPPL Y COMPRESSOR COND. FA N MOTOR FLA SUPPL Y AIR BLOWER MOTOR, FLA ELECTRIC HEA T ACCESSORY MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, 1 AMPS MAX. HACR 2 BREAKER SIZE RLA LRA MODEL NO. KW TOT AL AMPS 018 208/230-1-60 7.1 48 ...

  • York THRU 060 - page 7

    Unitary Products Group 7 66297-YIM-C-0205 T ABLE 5 - ELECTRICAL DA T A (12 SEER HEA T PUMP / ELECTRIC HEA T) (Continued) MODEL BHH POWER SUPPL Y COMPRESSOR COND. FA N MOTOR FLA SUPPL Y AIR BLOWER MOTOR, FLA ELECTRIC HEA T ACCESSORY MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, 1 AMPS MAX. HACR 2 BREAKER SIZE RLA LRA MODEL NO. KW TOT AL AMPS 036 575-3-6 ...

  • York THRU 060 - page 8

    8 Unitary Products Group 66297-YIM-C-0205 INDOOR DB TEMPERATURE, ° F HEA TING SUPERHEA T A T COMPRESSOR SUCTION, ° F - 1 0 0 1 02 03 04 05 06 0 55 4.4 4.4 4.6 4.9 5.6 7.1 10.2 16.6 7 0 —————— 5 . 9 12.3 8 0 ——————— 9 . 3 T ABLE 9 - HEA TING SUPERHEA T A T COMPRESSOR SUCTION, AIRFLOW = 800 CFM (B1HH024) T ABLE 8 - COOLING ...

  • York THRU 060 - page 9

    Unitary Products Group 9 66297-YIM-C-0205 T ABLE 13 - HEA TING SUPERHEA T A T COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036) T ABLE 12 - COOLING SUPERHEA T A T COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036) INDOOR DB TEMPERATURE, ° F HEA TING SUPERHEA T A T COMPRESSOR SUCTION, ° F - 1 0 0 1 02 03 04 05 06 0 55 — — 3.3 4.1 5.3 7.0 9.5 13 ...

  • York THRU 060 - page 10

    10 Unitary Products Group 66297-YIM-C-0205 T ABLE 16 - COOLING SUPERHEA T A T COMPRESSOR SUCTION, AIRFLOW = 1,600 CFM (B1HH048) T ABLE 15 - HEA TING SUPERHEA T A T COMPRESSOR SUCTION, AIRFLOW = 1,400 CFM (B1HH042) INDOOR DB TEMPERATURE, ° F HEA TING SUPERHEA T A T COMPRESSOR SUCTION, ° F - 1 0 0 1 02 03 04 05 06 0 55 — — — 4.0 6.2 9.0 12.5 ...

  • York THRU 060 - page 11

    Unitary Products Group 11 66297-YIM-C-0205 T ABLE 18 - COOLING SUPERHEA T A T COMPRESSOR SUCTION, AIRFLOW = 2,000 CFM (B1HH060) OUTDOOR TEMPERATURE, ° F INDOOR WB TEMPERATURE, ° F 55 57 59 61 63 65 67 69 71 73 75 65 — — — 5.4 6.8 8.3 9.8 15.5 21.2 27.0 32.7 7 0 ———— 6 . 3 7 . 8 9 . 2 14.9 20.6 26.2 31.9 7 5 ———— 5 . 8 7 . 2 ...

  • York THRU 060 - page 12

    12 Unitary Products Group 66297-YIM-C-0205 MODEL NO. BHH MOTOR SPEED EXTERNAL ST A TIC PRESSURE - IWG .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM W A TTS CFM W A TTS CFM W A TTS CFM W A TTS CFM W A TTS CFM W A TTS CFM W A TTS CFM W A TTS CFM W A TTS CFM W A TTS 018 HI MED LOW — — 741 — — 226 — — 686 — — 212 — — 632 — — 198 ...

  • York THRU 060 - page 13

    Unitary Products Group 13 66297-YIM-C-0205 T ABLE 21 - ADDITIONAL ST A TIC PRESSURE RESIST ANCE FIG. 3 - CLEARANCES DESCRIPTION RESIST ANCE, IWG CFM 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000 Wet Indoor coil 0.01 0.01 0.01 0.02 0.01 0.02 0.03 0.04 0.04 0.03 0.04 0.04 0.05 0.05 0.06 0.07 Economizer 0.00 0.0 ...

  • York THRU 060 - page 14

    14 Unitary Products Group 66297-YIM-C-0205 FIG. 4 - DIMENSIONS OUTDOOR COIL 15 4 BACK SIDE RETURN AIR OPENING SIDE SUPPL Y AIR OPENING BOTTOM RETURN AIR OPENING 15 15 BOTTOM SUPPL Y AIR OPENING LOW VOL TAGE CONN. “ DIA. KNOCKOUT HIGH VOL TAGE CONN. " DIA. KNOCKOUT FRONT ELECTRICAL/FILTER SERVICE ACCESS COMP ARTMENT P ANEL (OVERALL) (OVERALL) ...

  • York THRU 060 - page 15

    Anti-short Cycle Timer This unit has an anti-short cycle timer built in to the defrost con - trol. This timer will not permit the compressor to start within five minutes after the completion of the last cycle or power interrup - tion. T o bypass the anti-short cycle feature, short the “TEST” pins together for 2 seconds. The following sequences ...

  • York THRU 060 - page 16

    gized. Power is supplied to the compressor and outdoor fan motor , and the reversing valve switched to the cooling posi - tion. When the fan switch on the thermostat is in the “AUT O” position the indoor blower motor is energized at the cooling airflow . 3. When the demand for cooling has been satisfied, the 24 volt “Y” signal is removed, a ...

  • York THRU 060 - page 17

    Unitary Products Group 17 66297-YIM-C-0205 NORMAL MAINTENANCE WARNING: Prior to any of the following maintenance proce - dures, shut off all power to the unit, to avoid per - sonal injury . Periodic maintenance consists of changing or cleaning filters and general cleaning of the outdoor coil. FILTERS - Inspect once a month. Replace Disposable or cl ...

  • York THRU 060 - page 18

    18 Unitary Products Group 66297-YIM-C-0205 TROUBLESHOOTING WARNING: T roubleshooting of components necessarily re - quires opening the electrical control box with the power connected to the unit. Use extreme care when working with live circuit! Check the unit nameplate for the correct range before making any connections with line terminals. CAUTION ...

  • York THRU 060 - page 19

    Unitary Products Group 19 66297-YIM-C-0205 TYPICAL WIRING DIAGRAM LEGEND (See page 18) TYPICAL WIRING DIAGRAM NOTES (See page 18) CAUTION - OPEN ALL DISCONNECTS BEFORE SERVICING THIS UNIT 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. 2. CAUTION: LABEL ALL WIRES PRI ...

  • York THRU 060 - page 20

    20 Unitary Products Group 66297-YIM-C-0205 FIG. 6 - TYPICAL WIRING DIAGRAM BHH060 - 208/230-3-60 POWER SUPPL Y ...

  • York THRU 060 - page 21

    Unitary Products Group 21 66297-YIM-C-0205 TYPICAL WIRING DIAGRAM LEGEND (See page 20) TYPICAL WIRING DIAGRAM NOTES (See page 20) N O T E S : 6 . I F O P T I O N A L S A F E T Y S W I T C H K I T I S I N S T A L L E D , W I R E 2 1 9 / B K I S R E M 0 V E D . 7 . W I R E 2 0 4 / B R I S R E M O V E D W H E N E L E C T R I C H E A T I S I N S T A L ...

  • York THRU 060 - page 22

    22 Unitary Products Group 66297-YIM-C-0205 FIG. 7 - TYPICAL WIRING DIAGRAM BHH060 - 460-3-60 POWER SUPPL Y ...

  • York THRU 060 - page 23

    Unitary Products Group 23 66297-YIM-C-0205 S 3 / P 3 S O C K E T / P L U G C O N N E C T I O N O N C O N T R O L B O A R D , L O W V O L T A G E S 2 / P 2 S O C K E T / P L U G C O N N E C T I O N O N C O N T R O L B O A R D , L O W V O L T A G E L S L I M I T S W I T C H , E L E C T R I C H E A T ( P A R T O F E L E C H E A T A C C E S S O R Y ) F ...

  • York THRU 060 - page 24

    24 Unitary Products Group 66297-YIM-C-0205 POWER SUPPLY POWER SUPPLY 208/230-1-60 208/230-1-60 USE COPPER USE COPPER CONDUCTORS ONLY CONDUCTORS ONLY SECONDARY POWER SUPPLY SECONDARY POWER SUPPLY FOR DUAL POINT ELEC HEAT FOR DUAL POINT ELEC HEAT 208/230-1-60 208/230-1-60 USE COPPER USE COPPER CONDUCTORS ONLY CONDUCTORS ONLY (HTR5) (HTR5) (HTR4) (HTR ...

  • York THRU 060 - page 25

    Unitary Products Group 25 66297-YIM-C-0205 FIG. 9 - TYPICAL WIRING DIAGRAM (230-3-60 POWER SUPPL Y) ...

  • York THRU 060 - page 26

    26 Unitary Products Group 66297-YIM-C-0205 L 2 L 1 P O W E R S U P P L Y W / O U T E L E C H E A T 4 6 0 - 3 - 6 0 O R 5 7 5 - 3 - 6 0 U S E C O P P E R CO NDUCT O RS O N L Y G N D L U G P O W E R S U P P L Y W / E L E C H E A T 4 6 0 - 3 - 6 0 O R 5 7 5 - 3 - 6 0 ( S E E D E T A ) ( S E E D E T A ) ( S E E D E T A ) 1 2 0 / Y S E E N O T E 6 7 0 9 ...

  • York THRU 060 - page 27

    Unitary Products Group 27 66297-YIM-C-0205 TYPICAL WIRING DIAGRAM LEGEND (See page 24, 25 and 25) CB CCH COMPR DS F1 F2 F3 F4 F5 F6 F7 F8 F9 F24 FS HP HTR 1 HTR 2 HTR 3 HTR 4 HTR 5 HTR 6 K1 K2 K3 K7 LP LS M1 M2 M3 PTCR RC1/RC2 RC1 RC2 RC3 RV S S2/P2 S3/P3 S4/P4 S3/P3 T1 TB2 CIRCUIT BREAKER 24V , 3 AMP CRANKCASE HEA TER (OPTIONAL) COMPRESSOR DEFROST ...

  • York THRU 060 - page 28

    Unitary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A. Copyright © 2005 by Y ork International Corporation. All Rights Reserved. 66297-YIM-C-0205 ...

メーカー York カテゴリー Heat Pump

York THRU 060のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- THRU 060の取扱説明書
- Yorkの製品カード
- パンフレット
- またはYork THRU 060の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、York THRU 060の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、York THRU 060の取り付け説明書、サービスマニュアル、簡易説明書、またはYork THRU 060のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、York THRU 060の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

York THRU 060デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがYork THRU 060を使用するのを助ける技術的文書のことです。説明書は通常、全てのYork THRU 060ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Yorkの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. York THRU 060の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははYork THRU 060の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。York THRU 060に関してこのドキュメントで見つけることができる全てのヒントの目次
3. York THRU 060デバイスの基本機能を使うにあたってのヒント。 York THRU 060のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。York THRU 060に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるYork THRU 060のメーカー/サービスへの連絡先に関する情報。

York THRU 060についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもYork THRU 060の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがYork THRU 060で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)