    Rev F Date: 11.2.2006 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com READ AND SAVE THESE INSTRUCTIONS OPEN REFRIGERATED SELF-SE RVICE MERCHANDISE R Model DO3637R 38 1/8”L x 28 5/8”D x 37 1/4”H ( Upper Display Case Only) 38 1/8”L x 28 5/8”D x 61 1/8”H ( Upper Display Case + Drop-In Re ...

  • Impulse DO4837R - page 2

    2 TABLE OF CONTENTS OVERVIEW AND WARNINGS ...………………………..…… ……………..…….………….....….. CUSTOMER CABINET PROVISIONS…… ……………..…………………..…….……… ….....….. CLEARANCE AND AIR FLOW ...……………… ………..…………………..…….………….....….. VENTING ...

  • Impulse DO4837R - page 3

    3 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com OVERVIEW AND WARNINGS OVERVIEW • The Structural Concepts® Oasis® refrigerated self-service cases are designed to merchandise packaged products at 5° Celsius / 41° Fahrenheit or less product temperatures. • These cases should be installed a ...

  • Impulse DO4837R - page 4

    R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com CUSTOMER CABINET PROVI SIONS Customer Cabinet Provisions • Customer provided cabinet must adhere to the minimum requirements in ANSI/UL Std. 471 and ANSI/NSF Std. 7. • Among the factors that are to be taken into consideration when judging the ac ...

  • Impulse DO4837R - page 5

    R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com CLEARANCE AND AIR FLOW 5 Service Top Cutout Dimensions Note : See Manual Cover for DO3637R, DO4837R, DO3623R & 4823R Service Top Cutout Dimensions. Clearance Dimensions The Refrigerated section must maintain airflow clear- ance. Dimensions are a ...

  • Impulse DO4837R - page 6

    R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com VENTING INSTRUCTIONS FOR AIR INTAKE / EXHAUST - DO3637 R 6 BACK VIEW OF CABINET AFTER POSITIONED ON CUSTOMER-SUPPLIE D COUNTER/BASE 1 9 ” M I N I M U M A I R E X H A U S T S P A C E 1 3 ” M IN I M U M A I R I N T A K E S P A C E 9 1 / 2 ” Warn ...

  • Impulse DO4837R - page 7

    R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com VENTING INSTRUCTIONS FOR AIR INTAKE / EXHAUST - DO4837 R 7 BACK VIEW OF CABINET AFTER POSITIONED ON CUSTOMER-SUPPLIE D COUNTER/BASE 1 5 ” M I N I M U M A I R E X H A U S T S P A C E 9 1 / 2 ” 1 9 ” M I N I M U M A I R E X H A U S T S P A C E 4 ...

  • Impulse DO4837R - page 8

    R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com VENTING INSTRUCTIONS FOR AIR INTAKE / EXHAUST - DO3623 R & DO482 3R 8 BACK VIEW OF CABINET AFTER POSITIONED ON CUSTOMER-SUPPLIE D COUNTER/BASE Warning: The minimum intake and exhaust areas must be allowed (as illustrated below) or case temperatu ...

  • Impulse DO4837R - page 9

    2. Display Case Setup • SCC® Service Drop-In Refrigerated Merchan- diser Case consists of two sections: The Upper Display Case and Drop-In Refrigerated Section. • As both sections make up one conjoined unit, it is both large and heavy. A team effort is re- quired for lowering Case into the Customer Sup- plied Base. • After lowering into Base ...

  • Impulse DO4837R - page 10

    R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com START-UP AND OPERATION Case Start-Up • Plug cord into a certified electrical outlet with ground. • Turn on the Main Power Switch. Switch is in the Drop-In Refrigerated Section on the rear right hand side of base. • The Temperature Control Modu ...

  • Impulse DO4837R - page 11

    Shelf Assembly Shelf Bracket 11 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com MAINTENANCE FUNDAME NTALS Adjustable Shelf • Adjustment of the angle of the shelves can be made by pivoting the lower portion of the shelf bracket in the upright. • The shelves can be adjusted to an angle of: 0, 5 ...

  • Impulse DO4837R - page 12

    12 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com MAINTENANCE FUNDAME NTALS, CONTINUED Warning, disconnect power before provid- ing maintenance and service to unit. As- sembly or disassembly and servicing to be accomplished by licensed electrical con- tractor. Evaporator Coil Fans Access and Rem ...

  • Impulse DO4837R - page 13

    13 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com MAINTENANCE FUNDAME NTALS, CONTINUED Removing the Rear Doors • Remove Thumbscrews (4 each side). Thumbscrew removal will allow Rear Doors to be removed. • See illustration on this page for locations of Thumbscrews, Nuts, Perforated Acrylic Pl ...

  • Impulse DO4837R - page 14

    14 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com REFRIGERATION FUNDAMENT ALS Refrigeration Access, Connections & Servicing Assembly or disassembly and servicing to be accomplished by licensed refrigeration contractor. • Refrigeration Unit slides directly out from lower section to allow fo ...

  • Impulse DO4837R - page 15

    15 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com REFRIGERATION SLIDE-OUT EXPLODED PICTORI AL The following images show the various parts pertaining to the Refrigeration Unit (that is slid directly out from lower section) to be serviced. Copper Tubing Refrigeration Service Valve Sight Glass Capa ...

  • Impulse DO4837R - page 16

    16 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com TECHNICAL INFORMATION SHEET - MODEL DO3637R ...

  • Impulse DO4837R - page 17

    17 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com TECHNICAL INFORMATION SHEET - MODEL DO4837R ...

  • Impulse DO4837R - page 18

    18 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com TECHNICAL INFORMATION SHEET - MODEL DO3623R ...

  • Impulse DO4837R - page 19

    19 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com TECHNICAL INFORMATION SHEET - MODEL DO4823R ...

  • Impulse DO4837R - page 20

    20 TROUBLESHOOTING R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com Product is Drying Out Check the relative humidity in the store. Water on the Floor Check that all of the hoses are connected. Check that the drain trap is free of debris. Excessive Fan Noise Check that the case is aligned properly ...

  • Impulse DO4837R - page 21

    21 TROUBLESHOOTING, CONTINUED R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com Alarm Going Off, CPC ESC3 E0 flashing, Air probe has failed. E1 flashing, Defrost termination or product probe has failed. L0 flashing, Low temperature alarm. H1 flashing, High temperature alarm. Ed flashing, Defrost ti ...

  • Impulse DO4837R - page 22

    22 CLEANING SCHEDULE R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com Cleaning Daily Weekly Monthly Task Clean Case Exterior X Clean outside surface of front curved glass with a household or commercial glass cleaner. X Clean wood, laminate and painted surfaces with a mild soap and water solution a ...

  • Impulse DO4837R - page 23

    23 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com CPC® CONTROLLER - OVERVIE W Controller Overview The CPC ® ESC3 series is an electronic refrigeration controller that provides control of compressor, fan and defrost management. The ESC3 provides control of a compressor (or solenoid) valve in re ...

  • Impulse DO4837R - page 24

    R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com 24 CPC® - ESC3 CONTROLLER OPERATI ON Code Meaning E0 Air probe has failed. E1 Defrost termination or product probe has failed. L0 Low temperature alarm. HI High temperature alarm. Ed Defrost timeout has occurred (did not terminate correctly). dF Co ...

  • Impulse DO4837R - page 25

    25 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com CPC ® ESC3 SET POINT CHAN GING INSTRUCTIONS Viewing and Changing the Temperature Set Point The temperature set point is the comparison point for the control temperature input. To change the set point value: 1. Press the Alarm key for 3 seconds, ...

  • Impulse DO4837R - page 26

    26 WARRANTY R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com All sales by Structural Concept s Corporation (SCC) are subject to the following limited warranty. “Goods” refers to the product or products being sold b y SCC. Warranty; Remedies; Limitations . SCC warrants that if any Goods are fou ...

  • Impulse DO4837R - page 27

    27 TECHNICAL SERVICE TECHNICAL SERVICE DEP ARTMENT 1.800.433.9489 R 888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com ...

Manufacturer Impulse Category Refrigerator

Documents that we receive from a manufacturer of a Impulse DO4837R can be divided into several groups. They are, among others:
- Impulse technical drawings
- DO4837R manuals
- Impulse product data sheets
- information booklets
- or energy labels Impulse DO4837R
All of them are important, but the most important information from the point of view of use of the device are in the user manual Impulse DO4837R.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Impulse DO4837R, service manual, brief instructions and user manuals Impulse DO4837R. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Impulse DO4837R.

Similar manuals

A complete manual for the device Impulse DO4837R, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Impulse DO4837R by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Impulse DO4837R.

A complete Impulse manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Impulse DO4837R - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Impulse DO4837R, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Impulse DO4837R, that we can find in the current document
3. Tips how to use the basic functions of the device Impulse DO4837R - which should help us in our first steps of using Impulse DO4837R
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Impulse DO4837R
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Impulse DO4837R in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Impulse DO4837R?

Use the form below

If you did not solve your problem by using a manual Impulse DO4837R, ask a question using the form below. If a user had a similar problem with Impulse DO4837R it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)