Manual Burnham 8H

92 pages 7.02 mb
Download

Go to site of 92

Summary
  • Burnham 8H - page 1

    1 81416021R3-6/10 D N A G N I T A R E P O , N O I T A L L A T S N I R O F S N O I T C U R T S N I E C I V R E S S E I R E S 8 H R E L I O B D E R I F - S A G , r e l i o b n o n o i t a m r o f n i g n i k e e s n e h W . r o t c a r t n o c g n i t a e h r u o y l l a c , r e l i o b o t s r i a p e r r o e c i v r e s r o F . l e b a L g n i t a ...

  • Burnham 8H - page 2

    2 IMPOR T ANT INFORMA TION - READ CAREFULL Y NOTE: The equipment must be installed in accordance with those installation regulations enforced in the area where the installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. The following te ...

  • Burnham 8H - page 3

    3 W ARNING This boiler requires regular maintenance and service to operate safely . Follow the instructions contained in this manual. Improper install ation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Read and understand the entire manual before attempting installation, start-up operat ...

  • Burnham 8H - page 4

    4 T able of Contents I. Pre-Installation .............................................................6 II. Boiler Assembly ........................................................... 8 III. Gas Control System Assembly .................................. 15 (Knockdown Boilers) IV . W ater T rim and Piping ............................................ ...

  • Burnham 8H - page 5

    5 Figure 1: Dimensional Data Boiler Model Dimensions (Inches) Recommended Chimney Size (Round) W ater Content (Gallons) Approx. Shipping Weight (LB.) A B C D E USA Canada USA Canada 805H 20 10 7 24-13/16 24-13/16 16-1/8 16-1/8 7” dia. x 15 ft. 1 1.9 705 806H 23-3/4 1 1-7/8 8 27-13/16 25-3/4 18 16 8” dia. x 15 ft. 13.9 785 807H 27-1/2 13-3/4 9 2 ...

  • Burnham 8H - page 6

    6 I. Pre-Installation W ARNING Carefully read all instructions before installing boiler . Failure to follow all instructions in proper order can cause personal injury or death. A . Inspect shipment carefully for any signs of damage. All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to c ...

  • Burnham 8H - page 7

    7 b. If result is less than 50 ft 3 per 1,000 Btuh, space is considered a conned space . 4. Determine building type. A building of unusually tight construction has the following characteristics: a. W alls and ceiling exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and se ...

  • Burnham 8H - page 8

    8 II. Boiler Assembly A. Remove Crate 1. Remove all fasteners at crate skid. 2. Lift outside container and remove with all other inside protective spacers and bracing. B. Remove boiler fr om skid. See Figure 2. Exercise care to avoid dropping boiler . 1. Place boiler in approximate location. Refer to Section I: Pre-Installation. Remove base hold do ...

  • Burnham 8H - page 9

    9 6. Lift boiler with pry bar . Remove wood blocks. Lower boiler . C. For Packaged Boiler only , proceed to Paragraph E. D. T est Section Assembly for leaks before connecting to system and installing controls, trim and jacket. Refer to Figure 3 and T able 3. 1. Plug T appings C & E (¾ NPT) and Return T apping B (2 NPT). 2. Insert ¾” NPT x ? ...

  • Burnham 8H - page 10

    10 F . Move boiler to permanent location by sliding or walking. Do not drop. For Packaged Boiler , proceed to Paragraph L. G. Conrm that one (1) Flue Bafe is properly positioned in each Boiler Flueway . T abs at the top of each Flue Bafe should be resting on top row of Flue Pins on each adjoining section. H. Install Canopy on section assem ...

  • Burnham 8H - page 11

    1 1 Figure 6: Flame Roll-out Switch Installation Figure 7: Burner/Burner Access Panel Installation ...

  • Burnham 8H - page 12

    12 M. Attach Flame Roll-out Switch to Burner Access Panel. See Figure 6. Flame Roll-out Switch and hardware are located in Combination Boiler Parts and Control Carton. Flame Roll-out Switch is a single use device - do not test with heat - switch cannot be reset. 1. Cut insulation from semicircular notch at right end of the burner access panel. Mode ...

  • Burnham 8H - page 13

    13 Figure 8: Jacket Assembly ...

  • Burnham 8H - page 14

    14 Figure 9: EP/OP Control Installation ...

  • Burnham 8H - page 15

    15 III. Gas Control System Assembly (Knockdown Boilers) A. 24V Standing Pilot Control System Install Gas Control System. All components are located in Combination Boiler Parts and Control Carton. 1. Install Gas Control Assembly on Manifold. See Figure 10. Use thread (joint) compound (pipe dope) resistant to action of liqueed petroleum gas. 2. In ...

  • Burnham 8H - page 16

    16 F . EP-CSD-1 Control System Install Gas Control System . All components are located in Combination Boiler Parts and Control Carton. 1. Install Gas Control Assembly on Manifold. See Figure 17. 2. Install pilot burner piping and controls. See Figure 17. 3. Install Ignition T ransformer . a. Attach Ignition T ransformer to Jacket V estibule Panel u ...

  • Burnham 8H - page 17

    17 Figure 10: Schematic Gas Piping, 24V Standing Pilot, 806H & 807H ...

  • Burnham 8H - page 18

    18 Figure 1 1: Main Gas Piping, Intermittent Ignition (EI) ...

  • Burnham 8H - page 19

    19 Figure 12: Schematic Pilot Piping (Honeywell EI), USA ...

  • Burnham 8H - page 20

    20 Figure 13: Schematic Pilot Piping (Honeywell EI) Canada: Natural Gas, 805H - 810H; LP Gas, 806H - 807H ...

  • Burnham 8H - page 21

    21 Figure 14: Schematic Gas Piping, OP Control System, 806H - 810H ...

  • Burnham 8H - page 22

    22 Figure 15: Schematic Gas Piping, OP-CSD-1 Control System, 808H - 810H ...

  • Burnham 8H - page 23

    23 Figure 16: Schematic Gas Piping, EP Control System (Natural Gas Only), 806H - 810H ...

  • Burnham 8H - page 24

    24 Figure 17: Schematic Gas Piping, EP-CSD-1 Control System, 808H - 810H ...

  • Burnham 8H - page 25

    25 IV . W ater T rim and Piping A . Design and install boiler and system piping to prevent oxygen contamination of boiler water and frequent water additions. 1. There are many possible causes of oxygen contamination such as: a. Addition of excessive make-up water as a result of system leaks. b. Absorption through open tanks and ttings. c. Oxygen ...

  • Burnham 8H - page 26

    26 D. Install Drain V alve in rear of Left End Section, T apping “G”. See Figure 19. Components are located in W ater T rim Carton. E. Install T emperature-Pr essure Gauge. Components are located in W ater T rim Carton. 1. Standard T emperature - Pressure Gauge Piping. See Figure 20. Figure 19: Drain Piping Installation Figure 22: Recommended P ...

  • Burnham 8H - page 27

    27 2. If boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air , boiler piping must be equipped with ow control valves to prevent gravity circulation of boiler water during cooling system operation. 3. The piping diagrams shown (Figure 23, Detail “A” and Detail “B”) are recommend ...

  • Burnham 8H - page 28

    28 a. A boiler by-pass is recommended for any installation for improved system temperature balance, while serving to protect the boiler from sustained condensing operation. The by-pass also provides some measure of low return water temperature protection by reducing ow through the boiler . See Figure 23. b. A blend pump is recommended to divert ...

  • Burnham 8H - page 29

    29 V . Gas Piping W ARNING Failure to properly pipe gas supply to boiler may result in improper operation and damage to the boiler or structure. Always assure gas piping is absolutely leak free and of the proper size and type for the connected load. An additional gas pressure regulator may be needed. Consult gas supplier . A. Size gas Piping. Desig ...

  • Burnham 8H - page 30

    30 Length (Feet) 0.3 Inch w .c. Pressure Drop 0.5 Inch w .c. Pressure Drop ½ ¾ 1 1¼ ½ ¾ 1 1¼ 10 132 278 520 1,050 175 360 680 1,400 20 92 190 350 730 120 250 465 950 30 73 152 285 590 97 200 375 770 40 63 130 245 500 82 170 320 660 50 56 1 15 215 440 73 151 285 580 60 50 105 195 400 66 138 260 530 70 46 96 180 370 61 125 240 490 80 43 90 170 ...

  • Burnham 8H - page 31

    31 A. Install vent system in accordance with local building codes; or local authority having jurisdiction; or National Fuel Gas Code , ANSI Z223.1/NFP A 54, Part 7, V enting of Equipment and/or CAN/CSA B149.1, V enting Systems and Air Supply for Appliances. Install any of the following for this Series 8H Category I, draft hood equipped appliance: 1 ...

  • Burnham 8H - page 32

    32 E. Boiler Equipped W ith V ent Damper . See Figure 26. 1. Open V ent Damper Carton and remove Installation Instructions. Read Installation Instructions thoroughly before proceeding. CAUTION Do not use one vent damper to control two or more heating appliances. 2. V ent damper must be same size as draft hood outlet. See Figure 1. Unpack vent dampe ...

  • Burnham 8H - page 33

    33 Figure 27: T ypical V ent System 9. Design vent system for sea level input. 10. Provide adequate ventilation of Boiler Room. See Section I: Pre-Installation. 1 1. Never pass any portion of vent system through a circulating air duct or plenum. W ARNING When an existing boiler is removed from a common venting system, the common venting system is l ...

  • Burnham 8H - page 34

    34 VII. Electrical W ARNING Failure to properly wire electrical connections to the boiler may result in serious physical harm. Electrical power may be from more than one source. Make sure all power is off before attempting any electrical work. Each boiler must be protected with a properly sized fused disconnect. Never jump out or make inoperative a ...

  • Burnham 8H - page 35

    35 E. Alliance SL™ W ater Heater (if used). May be used with Intermittent Circulation only . Refer to Alliance SL™ Installation, Operating and Service Instructions for wiring, piping and additional information. F . V ent Damper Sequence of Operation. See Figure 28 for schematic wiring diagram. 1. The V ent Damper is continuously powered at T er ...

  • Burnham 8H - page 36

    36 1. Standing Pilot (24) Sequence of Operation a. Normal Operation i. Thermostat or operating control calls for heat. V ent Damper (if used) opens. ii. Gas valves are energized allowing main gas ow and ignition of main burners. iii. Call or heat ends. Gas valves are de- energized, extinguishing main ame. V ent Damper (if used) closes. b. Saf ...

  • Burnham 8H - page 37

    37 Figure 29: Wiring Diagram, Standing Pilot (24V), USA and Canada, Continuous Circulation ...

  • Burnham 8H - page 38

    38 Figure 30: Wiring Diagram, Standing Pilot (24V), USA and Canada, Intermittent Circulation ...

  • Burnham 8H - page 39

    39 2. Electronically Supervised Standing Pilot (OP) Sequence of Operation a. Normal Operation i. Thermostat or operating control calls for heat. ii. T erminal #6 of RM7890C Burner Control is energized, initiating a microcomputer monitored circuit test. iii. Pilot Flame Establishing Period (PFEP) begins. iv . After pilot ame is proven, terminal # ...

  • Burnham 8H - page 40

    40 Figure 31: Wiring Diagram, OP/OP-CSD-1 Ignition System, Continuous Circulation ...

  • Burnham 8H - page 41

    41 Figure 32: Wiring Diagram, OP/OP-CSD-1 Ignition System, Intermittent Circulation ...

  • Burnham 8H - page 42

    42 4. Honeywell EI Sequence of Operation a. Normal Operation i. Thermostat or operating control calls for heat. V ent Damper (if used) opens. ii. Ignition Module T erminals PV , MV/PV and the Ignition T erminal are energized. T erminals PV and MV/PV power the Pilot V alve in the Gas V alve supplying gas to the Pilot. The Ignition T erminal supplies ...

  • Burnham 8H - page 43

    43 Figure 33: Wiring Diagram, Honeywell EI, USA, Continuous Circulation ...

  • Burnham 8H - page 44

    44 Figure 34: Wiring Diagram, Honeywell EI, USA, Intermittent Circulation ...

  • Burnham 8H - page 45

    45 Figure 35: Wiring Diagram, Honeywell EI, Canada, Continuous Circulation ...

  • Burnham 8H - page 46

    46 Figure 36: Wiring Diagram, Honeywell EI, Canada, Intermittent Circulation ...

  • Burnham 8H - page 47

    47 6. Electronically Supervised Intermittent Ignition (EP/EP-CSD-1) Sequence of Operation a. Normal Operation i. Thermostat or operating control calls for heat. ii. T erminal #6 of RM7890A Burner Control is energized, initiating a microcomputer monitored circuit test. iii. The pilot valve (terminal 8) and ignition transformer (terminal 10) are ener ...

  • Burnham 8H - page 48

    48 Figure 37: Wiring Diagram, EP/EP-CSD-1 Ignition System, USA, Continuous Circulation ...

  • Burnham 8H - page 49

    49 Figure 38: Wiring Diagram, EP/EP-CSD-1 Ignition System, USA, Intermittent Circulation ...

  • Burnham 8H - page 50

    50 Figure 39: McDonnell & Miller 750P-MT (120V) L.W .C.O. Wiring for Boilers with 24V Limit Circuits Figure 40: McDonnell & Miller 750P-MT (120V) L.W .C.O. Wiring for Boilers with 120V Limit Circuits (OP & EP) ...

  • Burnham 8H - page 51

    51 Figure 41: Hydrolevel OEM - 170/550/650/750 (120V) L.W .C.O. Wiring for Boilers with 24V Limit Circuits Figure 42: Hydrolevel OEM - 170/550/650/750 (120V) L.W .C.O. Wiring for Boilers with 120V Limit Circuits ...

  • Burnham 8H - page 52

    52 W ARNING Completely read, understand and follow all instructions in this manual before attempting start-up. A. Safe operation and other performance criteria were met with the gas manifold and control assembly provided on boiler when boiler underwent tests specied in American National Standar d for Gas-Fired Low- Pr essure Steam and Hot W ater ...

  • Burnham 8H - page 53

    53 Figure 43: Lighting Instructions (24V Standing Pilot) ...

  • Burnham 8H - page 54

    54 Figure 44: Operating Instructions (EI) ...

  • Burnham 8H - page 55

    55 Figure 45: Lighting Instructions (OP) ...

  • Burnham 8H - page 56

    56 Figure 46: Operating Instructions (EP) ...

  • Burnham 8H - page 57

    57 BOILER OPERA TING INSTRUCTIONS TO SHUT DOWN: 1. Close manual main shut-of f valve(s) and pilot valve(s). 2. T urn off main electric switch. TO ST ART UP: 1. Make sure that both the main manual and the pilot valve(s) have been off for at least ve minutes. 2. T urn room thermostat and all operating controls to lowest setting. 3. Remove burner a ...

  • Burnham 8H - page 58

    58 I. Check pilot burner ame and main burner ames through observation port. 1. Check pilot ame. Refer to T able 1 1 for appropriate pilot detail. 2. Adjust thermostat to highest setting. 3. Check main burner ames. See Figure 52. Flame should have clearly dened inner cones with no yellow tipping. Orange-yellow streaks caused by dust s ...

  • Burnham 8H - page 59

    59 CAUTION A void operating this boiler in an environment where saw dust, loose insulation bers, dry wall dust, etc. are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation. a. Loosen lock screw . b. Close air adjustment until yellow tips appear on ? ...

  • Burnham 8H - page 60

    60 b. Increase input rate if less than 98% of rating plate input. Increase manifold gas pressure no more than 0.3 inch w .c. If measured input rate is still less than 98% of rated input: i. Remove Main Burners per procedure in Section IX: Service. ii. Remove gas orices. Drill one (1) drill size larger (drill size is stamped on orice, or see K ...

  • Burnham 8H - page 61

    61 IX. Service W ARNING Service on this boiler should be undertaken only by trained and skilled personnel from a qualied service agency . Inspections should be performed at intervals specied in this manual. Maintain manual in a legible condition. Keep boiler area clear and free of combustible materials, gasoline and other ammable vapors an ...

  • Burnham 8H - page 62

    62 Important Produc t Safety Informati on Refractory Ceram ic Fiber Product Warning : The Repair Parts list designates parts that contain refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. When exposed to temperatures about 1805°F, such as during direct flame contact, RCF changes into crystalline silica, a kno ...

  • Burnham 8H - page 63

    63 F . Clean Combustion Chamber by vacuuming. Exercise care to avoid damaging Base Insulation. G. Install Burners by reversing procedures used to remove burners. V erify Main Burners are properly located on support bracket in Base Rear Panel, seated on Main Burner Orices, and secured with hitch pin clips. V erify Main Burner with Pilot Bracket i ...

  • Burnham 8H - page 64

    64 Y ellow LED Flash Code a Indicates Recommended Service Action Heartbeat Normal Flame Signal N/A 2 Weak Flame Signal - System will operate reliably but ame signal is less than desired. Note: This indication may ash temporarily during or shortly after lightoff on some applications. Perform routine maintenance to assure optimum ame signal. ...

  • Burnham 8H - page 65

    65 Green LED Flash Code (X + Y) a Indicates Next System Action Recommended Service Action OFF No “Call for Heat” N/A None Flash Fast Startup - Flame sense calibration N/A None Heartbeat Normal operation N/A None 2 5 minute Retry Delay- Pilot ame not detected during trial for ignition Initiate new trial for ignition after retry delay complete ...

  • Burnham 8H - page 66

    66 Honeywell EI T rouble Shooting Guide ...

  • Burnham 8H - page 67

    67 All Series 8H Repair Parts may be obtained through your local Burnham Wholesale distributor . Should you require assistance in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact Burnham Customer Service at: (717) 481-8400 or Fax (717) 481-8408. X. Repair P ...

  • Burnham 8H - page 68

    68 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 1. Heat Exchanger Assembly 1 Complete (Less Flue Bafes) 6171605 1 --- --- --- --- --- 6171606 --- 1 --- --- --- --- 6171607 --- --- 1 --- --- --- 6171608 --- --- --- 1 --- --- 6171609 --- --- --- --- 1 --- 6171610 --- --- --- --- --- 1 1A Left End Section 7171601 1 1 1 1 1 1 ...

  • Burnham 8H - page 69

    69 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 2. Canopy 2A Canopy 61 1 1605 1 --- --- --- --- --- 61 1 1606 --- 1 --- --- --- --- 61 1 1607 --- --- 1 --- --- --- 61 1 1608 --- --- --- 1 --- --- 61 1 1609 --- --- --- --- 1 --- 61 1 1610 --- --- --- --- --- 1 2B Bolt, Carriage, ¼ - 20 x 1” 808601 15 2 2 2 2 2 2 2C W asher ...

  • Burnham 8H - page 70

    70 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 3. Base Assembly 3A Base End Panel 7181601 2 2 2 2 2 2 3B Base Channel Assembly 61816052 2 --- --- --- --- --- 61816062 --- 2 --- --- --- --- 61816072 --- --- 2 --- --- --- 61816082 --- --- --- 2 --- --- 61816092 --- --- --- --- 2 --- 61816102 --- --- --- --- --- 2 3C Base Rear ...

  • Burnham 8H - page 71

    71 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 4. Manifold and Main Burners 4A Main Burner 8231602 8 10 12 15 17 19 4B Main Burner with Pilot Bracket, Standing Pilot (24V) 8231601 --- 1 1 1 1 1 Main burner with Pilot Bracket, Honeywell EI 8231604 1 1 1 1 1 1 Main Burner with Pilot Bracket, OP 8231603 --- 1 1 1 1 1 Main burn ...

  • Burnham 8H - page 72

    72 Item No. Description Part No. Size Quantity 5-1 Gas T rain -- Standing Pilot (24V , OP) 24V : USA & Canada, 6 & 7 Section, Natural & LP Gas OP: USA & Canada, 6 - 10 Section, Natural & LP Gas A Gas V alve, Robertshaw 7000ERHC-S7C, Natural Gas, 1” NPT 81660156 806H - 810H 1 Gas V alve, Robertshaw 7000ERHC-LP-S7C, LP Gas, 1” ...

  • Burnham 8H - page 73

    73 Item No. Description Part No. Quantity 5-2 Gas T rain -- Standing Pilot (OP-CSD-1) OP-CSD-1: USA Only , 8-10 Section, LP Gas Only A Gas V alve, Robertshaw 7000GVERHC-S7C, LP Gas, 1” NPT 81660271 1 B Solenoid Gas V alve, Honeywell V8295A1032, 1” NPT 81660236 1 C Lubricated Manual Shut-Off V alve, Conbraco #50-403-02, 1” NPT 822615 1 D Leak ...

  • Burnham 8H - page 74

    74 Item No. Description Part No. Size Quantity 5-3 Gas T rain -- Intermittent Ignition (EI) USA: 5 - 10 Section, Natural and LP Gas Canada: 5 - 10 Section, Natural Gas 5 - 7 Section, LP Gas A Gas V alve, Robertshaw 7000DERHC, Natural Gas, 1” NPT 81660151 805H-810H 1 Gas V alve, Robertshaw 7000DERHC-LP , LP Gas, 1” NPT 81660158 USA: 805H-810H Ca ...

  • Burnham 8H - page 75

    75 Item No. Description Part No. Size Quantity 5-4 Gas T rain -- Intermittent Ignition (EP) USA & Canada: 6 - 10 Section, Natural Gas Only A Gas V alve, Robertshaw 7000GVERHC-S7C, Natural Gas, 1” NPT 81660168 806H-810H 1 B Solenoid Gas V alve, Honeywell V8295A1024, ¾” NPT 81660235 806H-807H 1 Solenoid Gas V alve, Honeywell V8295A1032, 1” ...

  • Burnham 8H - page 76

    76 Item No. Description Part No. Quantity 5-5 Gas T rain -- Intermittent Ignition (EP-CSD-1) USA Only: 8 - 10 Section, Natural Gas Only A Gas V alve, Robertshaw 7000GVERHC-S7C, Natural Gas, 1” NPT 81660168 1 B Solenoid Gas V alve, Honeywell V8295A1032, 1” NPT 81660236 1 C Lubricated Manual Shut-Off V alve, Conbraco #50-403-02, 1” NPT 822615 1 ...

  • Burnham 8H - page 77

    77 Item No. Description Part No. Size Quantity 5-6 Pilot Assembly and Piping -- Standing Pilot (24V) USA & Canada: 6 & 7 Section, Natural and LP Gas A Pilot Burner , Honeywell Q314A3687, Natural Gas 8236033 All 1 Pilot Burner , Honeywell Q314A3828, LP Gas 8236034 B Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead 8236004 C Brass Compressi ...

  • Burnham 8H - page 78

    78 Item No. Description Part No. Size Quantity 5-7 Pilot Assembly and Piping -- Intermittent Ignition (Honeywell EI) USA 5 - 10 Section, Natural and LP Gas A Pilot Burner , Honeywell Q348A1002, Natural Gas 8236072U 805H-810H 1 Pilot Burner , Honeywell Q348A1010, LP Gas 8236081 B Igniter/Sensor Cable, 36” Lg., Honeywell 394803-2 8236121 C Ground W ...

  • Burnham 8H - page 79

    79 Item No. Description Part No. Size Quantity 5-8 Pilot Assembly and Piping -- Intermittent Ignition (Honeywell EI) Canada 5 - 10 Section, Natural Gas 5 - 7 Section, LP Gas A Pilot Burner , Honeywell Q348A1002, Natural Gas 8236072U 805H-810H 1 Pilot Burner , Honeywell Q348A1010, LP Gas 8236081 805H-807H B Igniter/Sensor Cable, 36” Lg., Honeywell ...

  • Burnham 8H - page 80

    80 Item No. Description Part No. Size Quantity 5-9 Pilot Assembly and Piping -- Standing Pilot (OP) USA & Canada: 6 - 10 Section, Natural and LP Gas A Pilot Burner , Honeywell Q179D1008, Natural Gas 8236025 806H-810H 1 Pilot Burner , Honeywell Q179D1008 w/388146KD Orice, LP Gas 6236039 B Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead 823 ...

  • Burnham 8H - page 81

    81 Item No. Description Part No. Size Quantity 5-10 Pilot Assembly and Piping -- Standing Pilot (OP-CSD-1) USA Only: 8 - 10 Section, LP Gas Only A Pilot Burner , Honeywell Q179D1008 w/388146KD Orice, LP Gas 6236039 808H-810H 1 B Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead 8236004 1 C Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg. 71362561 ...

  • Burnham 8H - page 82

    82 Item No. Description Part No. Size Quantity 5-1 1 Pilot Assembly and Piping -- Intermittent Ignition (EP) USA & Canada: 6 - 10 Section, Natural Gas Only A Pilot Burner , Honeywell Q179C1009, Natural Gas 8236017 806H-810H 1 B Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg. 71362561 1 C Rajah Connector , Honeywell 37356 8236021 2 D Ignition Lead ...

  • Burnham 8H - page 83

    83 Item No. Description Part No. Size Quantity 5-12 Pilot Assembly and Piping -- Intermittent Ignition (EP-CSD-1) USA Only: 10 Section, Natural Gas Only A Pilot Burner , Honeywell Q179C1009, Natural Gas 8236017 808H-810H 1 B Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg. 71362561 1 C Rajah Connector , Honeywell 37356 8236021 2 D Ignition Lead, Honey ...

  • Burnham 8H - page 84

    84 ...

  • Burnham 8H - page 85

    85 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 6. Jacket 6 Complete 604161 1 1 1 --- --- --- --- --- 60416121 --- 1 --- --- --- --- 60416131 ---- --- 1 --- --- --- 60416141 --- --- --- 1 --- --- 60416151 --- --- --- --- 1 --- 60416161 --- --- --- --- --- 1 6A Jacket T op Panel 70416053 1 --- --- --- --- --- 70416063 --- 1 - ...

  • Burnham 8H - page 86

    86 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 6. Jacket (Continued) 6G Jacket Front Removable Panel 7041605 1 --- --- --- --- --- 7041606 --- 1 --- --- --- --- 7041607 --- --- 1 --- --- --- 7041608 --- --- --- 1 --- --- 7041609 --- --- --- --- 1 --- 7041610 --- --- --- --- --- 1 6H Jacket Left Side Panel 6041601 1 1 1 1 1 ...

  • Burnham 8H - page 87

    87 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 7. T rim and Miscellaneous Controls A Limit, 140-220°F , Honeywell L4080D1218 (EI & Standing Pilot); L4080B1212 (EP * OP) 80160251 80160474 1 1 1 1 1 1 Immersion Well, ¾” NPT x 1½” Insul. Depth 80160426 1 1 1 1 1 1 B Limit, Manual Reset, Honeywell L4006E1 133 8016070 ...

  • Burnham 8H - page 88

    88 Item No. Description Part No. Quantity 805H 806H 807H 808H 809H 810H 8. Draft Hood and Automatic V ent Damper 8A Draft Hood 81 1 1605 1 --- --- --- --- --- 81 1 1604 --- 1* --- --- --- --- 81 1 1607 --- 1** --- --- --- --- 81 1 1603 --- --- 1* --- --- --- 81 1 1608 --- --- 1** --- --- --- 81 1 1602 --- --- --- 1* --- --- 81 1 1608 --- --- --- 1* ...

  • Burnham 8H - page 89

    89 SER VICE RECORD DA TE SERVICE PERFORMED ...

  • Burnham 8H - page 90

    90 SER VICE RECORD DA TE SERVICE PERFORMED ...

  • Burnham 8H - page 91

    91 SER VICE RECORD DA TE SERVICE PERFORMED ...

  • Burnham 8H - page 92

    92 ...

Manufacturer Burnham Category Boiler

Documents that we receive from a manufacturer of a Burnham 8H can be divided into several groups. They are, among others:
- Burnham technical drawings
- 8H manuals
- Burnham product data sheets
- information booklets
- or energy labels Burnham 8H
All of them are important, but the most important information from the point of view of use of the device are in the user manual Burnham 8H.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Burnham 8H, service manual, brief instructions and user manuals Burnham 8H. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Burnham 8H.

Similar manuals

A complete manual for the device Burnham 8H, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Burnham 8H by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Burnham 8H.

A complete Burnham manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Burnham 8H - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Burnham 8H, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Burnham 8H, that we can find in the current document
3. Tips how to use the basic functions of the device Burnham 8H - which should help us in our first steps of using Burnham 8H
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Burnham 8H
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Burnham 8H in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Burnham 8H?

Use the form below

If you did not solve your problem by using a manual Burnham 8H, ask a question using the form below. If a user had a similar problem with Burnham 8H it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)