    • Refer to Service Manual RS6100004 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. Models listed on page 3. GSH 14 SEER Remote Heat Pump RT6213004 April 2006 This manual is to be used by qualified HV AC technicians only . Goodman does not assume any re ...

  • Goodman Mfg GSC140421A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROP- ERTY DAMAGE, PERSONAL INJURY OR DEA ...

  • Goodman Mfg GSC140421A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING DO NOT CONNECT OR USE ANY DEVICE THAT IS NOT DESIGN CERTI- FIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES. WARNING WARNING TO PREVENT THE RISK OF PROPERTY DAMAGE, PERS ...

  • Goodman Mfg GSC140421A - page 4

    PRODUCT DESIGN 4 GSH14 SEER split system heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications. Air is drawn through the outdoor coil by a propeller fan, and is discharged vertically out the top of the unit. No additional restriction (ductwork) shall be applied. The suction and liq ...

  • Goodman Mfg GSC140421A - page 5

    5 HEA T PUMP SPECIFICA TIONS GSH14[018-060]1A* (1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes . (2) May use fuses or HACR type Circuit Breakers of the same size as noted. NOTE: This data is provided as a guide, it is important to electrically connect the unit and pr ...

  • Goodman Mfg GSC140421A - page 6

    6 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OP ERA TI ON M ODEL: G SH140181A * / C A*F3131B6A *+TXV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid servic e valve, ARI 95 test conditio ns Outdoor A mbient Temperat ure 65 75 85 95 105 115 Entering Indoor W et Bulb Te mperature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg GSC140421A - page 7

    7 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA C OOL IN G OPER AT ION M ODEL: GSH 140181A * / CA* F 3131B6A *+T XV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid service valve, A R I 95 test conditio ns Ou tdo or Amb ie nt Tem per atu r e 65 75 85 95 105 115 Entering Indoor Wet Bulb T emperature I D B * A i r f l o w ...

  • Goodman Mfg GSC140421A - page 8

    8 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DA TA COOLI NG OPER A TION MO DEL: GSH140 241A * / CA *F3636B6A *+TXV / MBR800** 1 Design Subc ooling 9 ±3 °F @ the li qui d servic e valve, A RI 95 test c ondit ions Outdoor A mbient T emperature 65 75 85 95 105 115 Entering I ndoor Wet Bul b Te mperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140421A - page 9

    9 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DATA COOLING OPER A TION MO DEL: GSH140 241A * / CA *F3636B 6A *+TXV / MBR800 **1 Desi gn Subc ooling 9 ±3 °F @ the liqui d se rvice valve, A RI 95 test c onditions Outdoor A m bien t Temperature 65 75 85 95 105 115 Entering I ndoor Wet B ulb T emperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140421A - page 10

    10 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service valve, A RI 95 test conditi on s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140421A - page 11

    11 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service valve, A RI 95 test conditi on s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140421A - page 12

    12 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service valve, A RI 95 test condi tions Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140421A - page 13

    13 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service valve, A RI 95 test condi tions Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140421A - page 14

    14 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DATA COOLING OPERA TION M ODEL: GSH140421A* / CA *F4860D6A*+TXV / M BR2000**-1 Design Subcooling, 9 ± 3 °F @ the liquid service valv e, A RI 95 test condit i ons Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb T emperature I D B * A i r f l o w 5 96 36 77 1 ...

  • Goodman Mfg GSC140421A - page 15

    15 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140421A * / CA*F4860D6A *+TXV / M BR2000**-1 D esign Subcoolin g, 9 ±3 °F @ th e liquid serv ice valve, AR I 95 te st conditi ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng I nd oor W et Bulb Temp eratur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140421A - page 16

    16 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / MBR2000**-1 Design Subcooling 9 ±3 °F @ th e liquid servi ce valve, AR I 95 test condit io ns Outdoor Ambient Temper ature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Tempe ratur e I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg GSC140421A - page 17

    17 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / M BR2000**-1 Design Su bcooling 9 ±3 °F @ th e liquid serv ice valve, ARI 95 te st conditio ns Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng I nd oor W et Bulb Temp eratur e I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg GSC140421A - page 18

    18 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service valv e, ARI 95 te st con diti ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140421A - page 19

    19 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service valv e, ARI 95 te st con diti ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg GSC140421A - page 20

    20 PERFORMANCE DA T A Outdo or Temp. ° F. Total Btuh Sensib le Btuh Latent Btuh Total Watts 75° 18,900 13,282 5,618 1,367 80° 18,675 13,290 5,385 1,410 85° 18,450 13,295 5,155 1,452 90° 18,225 13,344 4,881 1,489 95° 18,000 13,389 4,611 1,526 100° 17 ,550 13,301 4,249 1,558 105° 17 ,100 13,201 3,899 1,589 110° 16 ,470 12,768 3,702 1,616 115 ...

  • Goodman Mfg GSC140421A - page 21

    21 EXPA NDED PERFO RMANC E DA TA MO DEL: G SH140181A* / CA*F3131B6A*+TXV / M BR800** -1 HEA TING OPERA TION Outdoor A mbient Temperature 65 60 55 50 47 45 40 35 30 25 20 17 1 5 10 5 0 -5 -10 MBh 22.6 21.4 20.2 18.8 18.0 17.4 16.2 14.9 13.6 12.5 11.5 10.9 10.5 9.4 8.3 7. 3 6.2 5.1 Delta T 34.9 33.1 31.1 29.1 27.8 26.9 25.0 23.1 20.9 19.3 17.8 16.8 1 ...

  • Goodman Mfg GSC140421A - page 22

    22 SPLIT SYSTEM HEA TING PERFORMANCE EXPA NDED PE RFO RMA NCE DA TA MODEL: GS H140421A * / CA *F4860D6A *+TXV / MB R2000**-1 HE AT I N G OP E R AT I O N Outdoor A mbient T emperat ure 65 60 55 50 47 45 40 35 30 2 5 20 1 7 15 10 5 - 5 -10 MBh 49.8 47.1 44.4 41. 5 39 .6 3 8 . 43 5 . 63 2 . 93 1 . 22 8 . 82 6 . 62 5 . 12 4 . 12 1 . 71 9 . 21 6 . 81 4 ...

  • Goodman Mfg GSC140421A - page 23

    23 HEA TING SPECIFICA TIONS capacity btuh c.o.p. 4.8 9.6 14.4 19.2 65 22.63 4.23 39.008 55.391 71.7732 88. 156 60 21.42 4.09 37.802 54.185 70.5672 86. 950 55 20.16 3.93 36.542 52.925 69.3072 85. 690 50 18.85 3.75 35.228 51.611 67.9932 84. 376 45 17.44 3.54 33.824 50.207 66.5892 82. 972 40 16.20 3.36 32.582 48.965 65.3472 81. 730 35 14.94 3.16 31.32 ...

  • Goodman Mfg GSC140421A - page 24

    24 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a s ...

  • Goodman Mfg GSC140421A - page 25

    WIRING DIAGRAMS 25 TO AVOID POSSI BLE ELECTRI CAL SHOCK, PERSONAL I NJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI C ING. WARNING ! GSH140[18-60]1A* US E N .E .C. CL AS S 2 WI R E NOTES : 1) TO INDOOR U NIT LOW VOL T AGE TER MINAL BLO CK & INDO OR TH ER M O ST A T . 2) STA RT AS SI ST FAC TO R Y E QUI P PED WH EN REQ U I RE D. 3) C RA NKC ...

Manufacturer Goodman Mfg Category Heat Pump

Documents that we receive from a manufacturer of a Goodman Mfg GSC140421A can be divided into several groups. They are, among others:
- Goodman Mfg technical drawings
- GSC140421A manuals
- Goodman Mfg product data sheets
- information booklets
- or energy labels Goodman Mfg GSC140421A
All of them are important, but the most important information from the point of view of use of the device are in the user manual Goodman Mfg GSC140421A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Goodman Mfg GSC140421A, service manual, brief instructions and user manuals Goodman Mfg GSC140421A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Goodman Mfg GSC140421A.

A complete manual for the device Goodman Mfg GSC140421A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Goodman Mfg GSC140421A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Goodman Mfg GSC140421A.

A complete Goodman Mfg manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Goodman Mfg GSC140421A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Goodman Mfg GSC140421A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Goodman Mfg GSC140421A, that we can find in the current document
3. Tips how to use the basic functions of the device Goodman Mfg GSC140421A - which should help us in our first steps of using Goodman Mfg GSC140421A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Goodman Mfg GSC140421A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Goodman Mfg GSC140421A in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Goodman Mfg GSC140421A?

Use the form below

If you did not solve your problem by using a manual Goodman Mfg GSC140421A, ask a question using the form below. If a user had a similar problem with Goodman Mfg GSC140421A it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)