Summary
  • APC 40004075KVA208Vi - page 1

    MGE Galaxy 4000 40–75 kV A 208 V Installation ...

  • APC 40004075KVA208Vi - page 2

    ...

  • APC 40004075KVA208Vi - page 3

    T able of Contents Safety .................................................................................................................................... 1 Safety Instructions ...................................................................................................... 1 Certication Standards — Three Phase UPS ................... ...

  • APC 40004075KVA208Vi - page 4

    Battery Connections ...................................................................................................13 Battery Control Connections ....................................................................................13 Connect AC Output ............................................................................................... ...

  • APC 40004075KVA208Vi - page 5

    Safety Safety Instructions This manual contains important instructions for MGE Galaxy 4000 that must be followed during operation and maintenance of the equipment. W ARNING: Opening enclosur es expose hazardous voltages. Always r efer service to qualied personnel only . W ARNING: As standards, specications, and designs ar e subject to change, ...

  • APC 40004075KVA208Vi - page 6

    Safety of Persons • The UPS has its own internal power source (the battery). Consequently , the power terminals may be ener gized even if the UPS is disconnected from the AC power source. • The UPS must be properly grounded. • The battery supplied with the UPS contains small amounts of toxic materials. T o avoid accidents, the directives list ...

  • APC 40004075KVA208Vi - page 7

    Specications Environmental Recommendations Recommended Environment 20° to 25°C (68° to 77°F .); 50% relative humidity; computer room or other temperature, and humidity-controlled environment Operating T emperature 0° to 30°C (32° to 86°F) except battery Storage -20° to 40°C (-4° to 1 13°F) except battery Humidity Up to 90% non-conden ...

  • APC 40004075KVA208Vi - page 8

    Mechanical Assembly General Description The MGE Galaxy 4000 is the world’ s rst data center grade Uninterruptible Power Supply system designed specically for mid-range enterprise level applications. The MGE Galaxy 4000 family consists of units available in power ratings from 40 - 75KV A, and are optimized for compatibility with nonlinear co ...

  • APC 40004075KVA208Vi - page 9

    Major Components Rectier Converts AC input voltage to DC voltage. The rectier uses IGBT (Insulated Gate Bipolar T ransistor) power transistors and a Pulse W idth Modulated (PWM) technique to provide input power factor correction and to minimize any harmonic reected onto the input power lines. Inverter Converts DC voltage from the rectie ...

  • APC 40004075KVA208Vi - page 10

    Preparation for Operation Several items must be considered when preparing the MGE Galaxy 4000 UPS system for operation. 1. The UPS cabinet and its auxiliary cabinets must be arranged in the required conguration to insure that the interconnection cables are located in the correct adjacent cabinets. 2. The cabinets must be in a location that provi ...

  • APC 40004075KVA208Vi - page 11

    Heat Rejection The MGE Galaxy 4000 UPS cabinets generate heat and exhaust air through the top portion of its enclosures. Air intake is through the bottom and front of the cabinet. All other cabinets are convection cooled. T o assist you in planning for your HV AC needs, heat rejection data is provided in table below . The cabinet airow and recom ...

  • APC 40004075KVA208Vi - page 12

    Prepare the Installation Conduit Plate Locations for Bottom Entry Cable entry through the bottom is the standard preferred design for the MGE Galaxy 4000 UPS cabinet. The bottom entry conduit plate provides space for up to ve (5) separate conduit entries. The plate is secured with screws which should be retained for the conduit plate after the p ...

  • APC 40004075KVA208Vi - page 13

    Conduit Plate Locations for T op Entry The UPS cabinet for the MGE Galaxy 4000 is capable of accepting power input and output cables through a top entry . The conduit plate on the top of the cabinet provides provisions for knockouts for conduit and is secured to the cabinet with screws. A 10 x 20.5 conduit E UPS B Air exhaust Do not block F Distrib ...

  • APC 40004075KVA208Vi - page 14

    Connect AC Input and Power Cables Installation Steps APC r ecommends corr ect installation verication and unit startup to be performed by an APC certied Service partner . Caution: Scheduling of the APC certied Service partner typically should be done 7 to 10 days before they are required on-site. If the startup of the UPS is critical to ma ...

  • APC 40004075KVA208Vi - page 15

    T ypical Power Connections A Front view N B B Rear area O C C Front P Output TB2 D TB4 Q A E TB1 R B F TB2 S C G Ground T TB3 Bypass input H Neutral Negative Positive Busbars U TB1 Main input I TB4 Control V Ground J A W Neutral K B X Battery Positive L C Y Battery Negative M A Z Busbars 990–3964–001 MGE Galaxy 4000 40–75 kV A 208 V 1 1 ...

  • APC 40004075KVA208Vi - page 16

    UPS Connections Electrical connections and cabinet interconnection will vary depending upon the conguration and options selected with your MGE Galaxy 4000 UPS system. Refer to the installation drawings supplied with your equipment. Connecting Power Cable Connections: T o access the connection terminal blocks, open the right door to the MGE Galax ...

  • APC 40004075KVA208Vi - page 17

    Connect Battery Cables Battery Connections The connections to be made are the positive, negative, and ground cables from the battery cabinet to the UPS. The battery cables are terminated at the positive, negative, and ground busbars. See “T ypical Power Connections“ . Battery Control Connections The battery control connections are made with the ...

  • APC 40004075KVA208Vi - page 18

    Connect AC Output AC Output Connections The connections to be made are the three phases, neutral, and ground cables from the load to the UPS. The output cables are terminated at the output terminal block (TB2). See “T ypical Power Connections“ . External Maintenance Bypass Control Connections (optional) The external maintenance bypass (MBP) con ...

  • APC 40004075KVA208Vi - page 19

    Connect Remote Emergency Power Off Remote Emergency Power Off Connections The control connections are available for Remote Emergency Power Of f (REPO) through a customer-supplied (normally closed) pushbutton. W ith REPO connected, the jumper on the REPO terminal blocks must be removed. See “T ypical Power Connections“ . A. Remove the jumper fro ...

  • APC 40004075KVA208Vi - page 20

    Connect Relay Communication Card Relay Communication Card Contacts The relay communication card contains six programmable dry contact outputs and two programmable dry inputs and is standard on the MGE Galaxy 4000. The inputs and outputs are factory programmed according to functions listed in table below . Inputs Factory Settings Options (available ...

  • APC 40004075KVA208Vi - page 21

    1 2 3 4 5 6 A B 1 2 3 4 5 6 A B 1 2 2 3 4 6 5 5 4 3 1 2 2 7 6 7 990–3964–001 MGE Galaxy 4000 40–75 kV A 208 V 17 ...

  • APC 40004075KVA208Vi - page 22

    Relay Communication Card Connections Refer to “Relay Communication Card Contacts“ for relay communication card, cover and hardware details. See “MGE Galaxy 4000 40–75 kV A 208 V Operation Manual — Operation — Preparing for Startup“ for communication card port location in the unit. 1. Remove the cover “3” secured by the screws “1 ...

  • APC 40004075KVA208Vi - page 23

    Appendix Single Line Diagram A UPS M Main Input TB1 B Battery N Optional Bypass Input 208YV AC C Distribution O Main Input 280YV AC D Supplied by MGE & Connected by customer P Input Fuses E T o critical load Q Input Static Switch F 42 Pole Panel board R PFC Boost Rectier G Output (optional) S Inverter H Output T Output Static Switch I (optio ...

  • APC 40004075KVA208Vi - page 24

    Worldwide Customer Support Customer support for this or any other product is available at no char ge: • Contact the Customer Support Center by telephone or e-mail. For local, country-specic centers: go to www .apc.com/support/contact for contact information. © APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric Ind ...

Manufacturer APC Category Power Supply

Documents that we receive from a manufacturer of a APC 40004075KVA208Vi can be divided into several groups. They are, among others:
- APC technical drawings
- 40004075KVA208Vi manuals
- APC product data sheets
- information booklets
- or energy labels APC 40004075KVA208Vi
All of them are important, but the most important information from the point of view of use of the device are in the user manual APC 40004075KVA208Vi.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals APC 40004075KVA208Vi, service manual, brief instructions and user manuals APC 40004075KVA208Vi. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product APC 40004075KVA208Vi.

Similar manuals

A complete manual for the device APC 40004075KVA208Vi, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use APC 40004075KVA208Vi by users. Manuals are usually written by a technical writer, but in a language understandable to all users of APC 40004075KVA208Vi.

A complete APC manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual APC 40004075KVA208Vi - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the APC 40004075KVA208Vi, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the APC 40004075KVA208Vi, that we can find in the current document
3. Tips how to use the basic functions of the device APC 40004075KVA208Vi - which should help us in our first steps of using APC 40004075KVA208Vi
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with APC 40004075KVA208Vi
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of APC 40004075KVA208Vi in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning APC 40004075KVA208Vi?

Use the form below

If you did not solve your problem by using a manual APC 40004075KVA208Vi, ask a question using the form below. If a user had a similar problem with APC 40004075KVA208Vi it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)