    PowerLogic TM Series EM4000/EM4800 Multi-Circuit Meters 930-112-01-D.00 11/2013 ...

  • Schneider Electric EM400 - page 2

    ...

  • Schneider Electric EM400 - page 3

    Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the d evice before trying to install , operate, service o r maintain it. The following special messages may appe ar throughout this manual or on the equipment to warn of poten tial hazards or to call attentio n to information ...

  • Schneider Electric EM400 - page 4

    Notices FCC Part 15 Notice This equipment has be en tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of th e FCC Rules. These limits are des igned to provide reasonable protection against harmful interferen ce in a resid ential installation. This equipment gen erates, uses, and can radiate radio frequ enc ...

  • Schneider Electric EM400 - page 5

    telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with th e FCC if you believe it is necessary. The telephone company may ma ke changes in its facilitie s, equipment, operations or procedures that could affect the oper at ion of this equipment. If this happens, the telephone company wi ...

  • Schneider Electric EM400 - page 6

    ...

  • Schneider Electric EM400 - page 7

    930-112-01-D.00 PowerLogic TM EM4000/EM4800 Series 11/2013 Table of Con tents ©2013 Schneider Electric All Rights Reserved i Table of Contents PowerLogic configuration tool ............. .............. .............. ........... .............. ... 1 System Set-up and Description ..................... ................. .............. ......... 1 Co ...

  • Schneider Electric EM400 - page 8

    PowerLogic TM EM4000/EM4800 Series 930-112-01-D.00 Table of Contents 11/2013 ©2013 Schneider Electric All Rights Reserved ii ...

  • Schneider Electric EM400 - page 9

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 1 PowerLogic configuration tool This document describes how to conf igure the PowerLogic EM4000/EM4800 Series meters, using the PowerLogic co nfigur ation tool. It includes the following configuration tool information: • “System Set-up and D ...

  • Schneider Electric EM400 - page 10

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 2 ©2013 Schneider Electric All Rights Reserved Figure 1: Programming Switch locatio n Table 1 lists the pr ogramming capabilities associat ed with each parameter in combination w ith the pr ogramming switches. After the meter has been programme d, the prog ramming sw itches can be turned O ...

  • Schneider Electric EM400 - page 11

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 3 Display Navigation The display on the fron t of the me ter prov ides status information for each circuit, and general information for metering. The PowerLog ic meter has three b uttons for navigating: a Display button, and left  and right ? ...

  • Schneider Electric EM400 - page 12

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 4 ©2013 Schneider Electric All Rights Reserved Normal Mode In Normal mode, the Display butt on scrolls through the information for each meter. The left  and ri ght  arrow butto ns select the previous or next meter points respectively. The following information is available: • Real ...

  • Schneider Electric EM400 - page 13

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 5 • Ethernet po rt MAC addres s • Firmware revision • Potential transfo rmer ratio Communications Connections If you are configuring the meter at an installation site, see the PowerLogic EM4000 Series Meter Installation Guide or the PowerL ...

  • Schneider Electric EM400 - page 14

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 6 ©2013 Schneider Electric All Rights Reserved 7. Assign the PC a static IP address such that the first three segments are the same as the default IP address, an d th e last segment is different from the default IP address. For example, 169.254.0.xxx, wher e xxx di ffers from the last segm ...

  • Schneider Electric EM400 - page 15

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 7 4. Re-install the inner cover. 5. Using a CAT 5 Ethernet patch cable, connect the meter and the PC to a local Ethernet switch. 6. Re-install the outer cover . 7. Restore power. When control power is restored, the meter will receive an IP addre ...

  • Schneider Electric EM400 - page 16

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 8 ©2013 Schneider Electric All Rights Reserved Figure 3: Configuration too l main window Connecting to a Meter The configuration tool automatically d etect s and lists the PowerLogic meters on the same network segment as the PC. The conf iguration tool ca n also be used with meters on a di ...

  • Schneider Electric EM400 - page 17

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 9 To connect to a meter on the same network: 1. Click Unit in the menu bar, then select List from the drop-down menu. The Discovered Units window appears, displa ying a list of meters available for configuration. See Figure 4. Figure 4: Discover ...

  • Schneider Electric EM400 - page 18

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 10 ©2013 Schneider Electric All Rights Reserved 2. Enter the IP address of the meter to be configured, th en click Connect. The configuration tool main win dow appears populated with the current programming info rmation for the selecte d meter. See Figure 6. 3. Proceed to “Unit Fiel d Co ...

  • Schneider Electric EM400 - page 19

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 11 Table 2: Unit Field Co nfiguration tab pa rameters Field Parameter Description Unit Field Configuration Current IP Address The current IP address fo r the unit .This parameter is read onl y and cannot be changed by the user. Mac Address The c ...

  • Schneider Electric EM400 - page 20

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 12 ©2013 Schneider Electric All Rights Reserved Report Parameters The Report section in the main confi guration window has six tabs: • Intervals tab allows the user to configure the re cordin g interval at which meter data is collected, and the demand interval for whic h d emand readings ...

  • Schneider Electric EM400 - page 21

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 13 Example : Selecting a Recording Interval of 5 minutes with Sliding Window Demand enabled and 3 Sub- intervals, creates a demand calculation every 5 minutes based on the previous 15 min utes. This is the common demand measurement used by North ...

  • Schneider Electric EM400 - page 22

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 14 ©2013 Schneider Electric All Rights Reserved Table 4: Ty pes tab confi guration parame ters NOTE: If parameters are grayed out, they ar e not available on the variant or firmware revision of the meter bein g configured. Parameter Description Watt Hours Delivered Inte rval/Register Thes ...

  • Schneider Electric EM400 - page 23

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 15 Figure 9: Reporting Sch edule tab in the Repo rt section Table 5: Reportin g Schedule tab confi guration paramete rs NOTE: When selecting a Daily report schedule, t he Start Tim e must occur before the End Time within the midn ight to midnigh ...

  • Schneider Electric EM400 - page 24

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 16 ©2013 Schneider Electric All Rights Reserved Figure 10: Calculations & Format t ab in the Report section Table 6: Calculation s & Format tab configura tion parameters Parameter Description Power Factor Sign Format IEEE In the display, the sign ( + or -) indicates lea ding (+) or ...

  • Schneider Electric EM400 - page 25

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 17 Figure 11: BACnet tab in t he Report section Table 7: BACnet tab configuration parameters Parameter Description Device ID Set the BACnet device ID by entering a a numeric ID between 0 and 4194303. Network Port The BACnet specific port numbe r ...

  • Schneider Electric EM400 - page 26

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 18 ©2013 Schneider Electric All Rights Reserved Figure 12: Comms tab in the Report section ...

  • Schneider Electric EM400 - page 27

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 19 Table 8: Comms tab configura tion parameters NOTE: The Modbus and RTU Adapter Comms Option para meters are valid only when a Modem module or an RTU adapter module is present. The RTU Adapter parameters apply only to Modbus RTU commu nications ...

  • Schneider Electric EM400 - page 28

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 20 ©2013 Schneider Electric All Rights Reserved Table 9: List of supporte d PowerLogic metering confi gurations To view the manufacturing informa tion for a specific meter, sele ct a model number from the Model # pull-down list shown in Figure 13. The part num ber, revision number and seri ...

  • Schneider Electric EM400 - page 29

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 21 Meter Points (Circuits) Tab The Meter Po ints (Circuits) tab contain s the configurat ion info rmation for each of the metering points. It shows the number of elements used, the phase, the current ratings, and the user-d efined identification ...

  • Schneider Electric EM400 - page 30

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 22 ©2013 Schneider Electric All Rights Reserved To change the curren t rating for all probes assigned to a meter point : 1. Select a meter from the Meter Points ( Circuits) List. The selected meter will appear in the Name field of the middle pane. See Figure 14. 2. In the Alter Current for ...

  • Schneider Electric EM400 - page 31

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 23 Figure 15: Badge Numbering pan e Reset Buttons • Reset Dial Readings button - selecting this button rese ts all registers for all energy types and pulse coun ts to zero. This function takes effect immediately and does not require a send act ...

  • Schneider Electric EM400 - page 32

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 24 ©2013 Schneider Electric All Rights Reserved • Adjust Dial Re ading button - selecting this button allows the operator to set all of the following energy type registe r s to the same fixed initial value: • Delivered Watt Hou rs • Received Watt Hours • Delivered VAR Hours • Rec ...

  • Schneider Electric EM400 - page 33

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 25 Figure 16: Pulse Probes tab ...

  • Schneider Electric EM400 - page 34

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 26 ©2013 Schneider Electric All Rights Reserved Completing the Meter Configuration Once you have defined all of the configur able parameters, the PowerLogic meter is ready to be progra mmed. To complete the me ter configuration: 1. Click Unit in th e menu bar, then select Save from th e dr ...

  • Schneider Electric EM400 - page 35

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 27 2. Click Unit in the menu bar, then select Send from the drop-down menu to transmit the configuration settin gs from your PC to the selected PowerLogic meter. The confirmation me ssage File loaded succ essfully! should appear in the bottom le ...

  • Schneider Electric EM400 - page 36

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 28 ©2013 Schneider Electric All Rights Reserved ...

  • Schneider Electric EM400 - page 37

    930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 29 User notes ...

  • Schneider Electric EM400 - page 38

    PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 30 ©2013 Schneider Electric All Rights Reserved ...

  • Schneider Electric EM400 - page 39

    ...

  • Schneider Electric EM400 - page 40

    PowerLogic TM Series EM4000/EM4800 Multi-Circuit Meters Schneider Electric 35 rue Joseph Monier 92500 Rueil-Malmaison, France www.schneider-electric.com 930-112-01-D.00 11/2013 ©2013 All Rights Reserved PowerLogic is a trademark or regi stered trademar k of Schneid er Electric in France, the USA and other countries. Ot her trademarks used are the ...

Manufacturer Schneider Electric Category Marine Instruments

Documents that we receive from a manufacturer of a Schneider Electric EM400 can be divided into several groups. They are, among others:
- Schneider Electric technical drawings
- EM400 manuals
- Schneider Electric product data sheets
- information booklets
- or energy labels Schneider Electric EM400
All of them are important, but the most important information from the point of view of use of the device are in the user manual Schneider Electric EM400.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Schneider Electric EM400, service manual, brief instructions and user manuals Schneider Electric EM400. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Schneider Electric EM400.

A complete manual for the device Schneider Electric EM400, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Schneider Electric EM400 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Schneider Electric EM400.

A complete Schneider Electric manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Schneider Electric EM400 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Schneider Electric EM400, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Schneider Electric EM400, that we can find in the current document
3. Tips how to use the basic functions of the device Schneider Electric EM400 - which should help us in our first steps of using Schneider Electric EM400
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Schneider Electric EM400
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Schneider Electric EM400 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Schneider Electric EM400?

Use the form below

If you did not solve your problem by using a manual Schneider Electric EM400, ask a question using the form below. If a user had a similar problem with Schneider Electric EM400 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)