Manual National Instruments FP-CTR-502

22 pages 0.44 mb
Download

Go to site of 22

Summary
  • National Instruments FP-CTR-502 - page 1

    323324B-01 June 2003 © 2002–2003 Nationa l Instruments Corp. A ll rights res erved. FieldPoint™, Nati onal Instruments™, NI™, and ni.com™ are trademarks of N ational Instruments Corpo ration. Product and company names ment ioned herein are trademark s or trade names of their respecti ve companies. For patents covering National Inst rumen ...

  • National Instruments FP-CTR-502 - page 2

    FP-CTR-502 and cFP-CTR-502 2 ni.com Installing the FP-CTR-502 The FP-CTR-502 mounts on a FieldPoint terminal base (FP-TB- x ), which provides operating po wer to the module. Instal ling the FP-CTR-502 onto a po wered termin al base does not disrupt the operation of the FieldPoint bank. T o install the FP-CTR-502, refer to Figure 1 and complete the ...

  • National Instruments FP-CTR-502 - page 3

    © National Instruments Corp. 3 FP-CTR-502 and cFP-CTR-502 2. Press firmly to seat the cFP-CTR-502 on the backplane. 3. Using a number 2 Phillips scre wdri ver with a shank of at least 64 mm (2.5 in.) length, tighten the capti v e scre ws to 1.1 N ⋅ m (10 lb ⋅ in.) of torque. The nylon coating on the screws pre v ents them from loosening. Figur ...

  • National Instruments FP-CTR-502 - page 4

    FP-CTR-502 and cFP-CTR-502 4 ni.com Use a 5–30 VDC external po wer s upply for the input channels. The power supply must provid e e nough current to po wer all of the input channels and all of the f i eld de vices on the output channels. Connect the external po wer supply to multiple V and V SUP terminals and to multiple C and COM t erminals as n ...

  • National Instruments FP-CTR-502 - page 5

    © National Instruments Corp. 5 FP-CTR-502 and cFP-CTR-502 Inputs Each input channel has one input terminal, V IN . Each channel also has V SUP and COM terminals that can supply power to f ield de vices or provide additional conne ctions to the external po wer supply . Y ou can connect the eigh t count-input channels and four gate-input channels to ...

  • National Instruments FP-CTR-502 - page 6

    FP-CTR-502 and cFP-CTR-502 6 ni.com V IN is 21 V or lower , a nd an OF F state when V IN is 22 V or higher . The channel state is indeterminate when V IN is between 21 V a n d2 2V . Ensure that the sinking-output de vices ha v e OFF state leak age currents of less than 0.3 mA so they do not send false ON state readings to the [c]FP-CTR-502. Note Yo ...

  • National Instruments FP-CTR-502 - page 7

    © National Instruments Corp. 7 FP-CTR-502 and cFP-CTR-502 Figure 4. Wiring an O utput Channel to a Sourcing-Input Device If you connect a [c]FP-CTR-502 output to an e xternally po wered sourcing-input device, be a ware th at the voltage applied to the V OUT terminal b y the exte rnal de vice must not exceed the volta ge lev el of the po wer supply ...

  • National Instruments FP-CTR-502 - page 8

    FP-CTR-502 and cFP-CTR-502 8 ni.com Configuring Count-Input Channels Channels 0 –7 are count-input channels. In FieldPoint software, you can conf igure each count-i nput channel to operate with attributes and comman ds. In th e Channel Conf iguration dialog box, select attrib utes for ea ch channel from the Attributes menu and commands from the C ...

  • National Instruments FP-CTR-502 - page 9

    © National Instruments Corp. 9 FP-CTR-502 and cFP-CTR-502 to Channel 0, Channel 0 to Chan nel 7, Channel 7 to Channel 6, and so on. If you select this op ti on for all of the channels, no counting occurs. Gate Source Select Gate Input 0 –3 from the V alue menu to associate a gate-input channel with a count-i nput channel. If the count-input chan ...

  • National Instruments FP-CTR-502 - page 10

    FP-CTR-502 and cFP-CTR-502 10 ni.com Noise Rejection Each count-input channel has a so ftware-enabled lo wpass f ilter that you can set to reject freque ncies abov e 200 Hz or 50 kHz. Select 200 Hz or 50 kHz from the V alue menu to configure noise rejection. The default is 50 kHz. Control Y ou can set the Control command to increment or reset by se ...

  • National Instruments FP-CTR-502 - page 11

    © National Instruments Corp. 1 1 FP-CTR-502 and cFP-CTR-502 Output Mode For each output channe l select one of the follo wing output modes from the V alue menu : Toggle, Reset Off ; Toggle, Reset On ; On Pulse ; or Off Pulse . The output modes work only if you select Counter Channel 0 –7 for the Output Source . The follo wing sections describe t ...

  • National Instruments FP-CTR-502 - page 12

    FP-CTR-502 and cFP-CTR-502 12 ni.com On Pulse In On Pulse mode, the output ch annel starts low and goes high when the terminal count is e xce eded. The output channel returns to low after one count. In Figure 9, the terminal count is 4. Figure 9. Output of a Channel Set to On Puls e Mode Off Pulse In Of f Pulse mode, the output ch annel starts high ...

  • National Instruments FP-CTR-502 - page 13

    © National Instruments Corp. 1 3 FP-CTR-502 and cFP-CTR-502 Application Note: Generating a Contin uous Pulse T rain Y ou can use two [c]FP-CTR-502 count-input cha nnels and one output channel to generate a co ntinuous pulse train with a controllable duty cycle and period . The f irst count-input channel serves as a clock prescaler and di vides the ...

  • National Instruments FP-CTR-502 - page 14

    FP-CTR-502 and cFP-CTR-502 14 ni.com 4. Set the Count Source of the pr escaler cou nter to the clock on which you want to base your pul se train. This can be the external counter input or one of the [c]FP-CTR-502 internal references. 5. Subtract 1 from the value that you w ant to divide the input clock by , and set the terminal c ount of the presca ...

  • National Instruments FP-CTR-502 - page 15

    © National Instruments Corp. 1 5 FP-CTR-502 and cFP-CTR-502 T o determine the frequenc y of the output from the pulse counter , use the follo wing formula: where f pulse is the pulse counter output frequency f pre is the prescaler c ounter output frequency term pulse is the terminal count value for the pulse counter Step 3. Configure the Pulse T r ...

  • National Instruments FP-CTR-502 - page 16

    FP-CTR-502 and cFP-CTR-502 16 ni.com Status Indicators Figure 12 shows the status indica tor LEDs on the [c]FP-CTR-502 . Figure 12. Status Indicators The [c]FP-CTR-502 has two green status LEDs, POWER and READY . After you install the [c]FP-CTR-502 onto a terminal base or backplane and apply po wer to the connected network module, the green POWER i ...

  • National Instruments FP-CTR-502 - page 17

    © National Instruments Corp. 1 7 FP-CTR-502 and cFP-CTR-502 Follo w these guideli nes to ensure a safe total system. • The [c]FP-CTR -50 2 has a safety isolation barrier between the I/O channels and the inter-modu le commu nication b us. Th ere is no isolation between channe ls unless otherwise noted. If any of the channels on a module are wired ...

  • National Instruments FP-CTR-502 - page 18

    FP-CTR-502 and cFP-CTR-502 18 ni.com Specifications The follo wing specif ications are typical for a range of – 40 to 70 °C unless otherwise noted. 1 Input Characteristic s Number of channels ... ........... ............ 12 (8 count, 4 gate) Input type ............ ...................... ........ 5–30 VDC sourcing , compatible with TTL devices ...

  • National Instruments FP-CTR-502 - page 19

    © National Instruments Corp. 1 9 FP-CTR-502 and cFP-CTR-502 Maximum output current Per channel .......... ........... ........... . 1 A Across all channe ls .................. ... 4 A Output impedance ... .............. ........... . 0.12 Ω Output bandwidth ................. ............ 16 kHz for a cu rrent flow ≥ 3.2 mA Maximum of f-state l ...

  • National Instruments FP-CTR-502 - page 20

    FP-CTR-502 and cFP-CTR-502 20 ni.com Shock and Vibration These specifications apply only to the cFP-CTR-502. NI recommends Compact FieldPoi nt if your application is subject to shock and vibration. Operating vibration, random (IEC 60068-2-64)....... ........... ............ 1 0 –500 Hz, 5 g rms Operating vibration, sinusoidal (IEC 60068-2-6)..... ...

  • National Instruments FP-CTR-502 - page 21

    © National Instruments Corp. 2 1 FP-CTR-502 and cFP-CTR-502 CE Compliance This product meets the essentia l requirements of applicable European Directi v es, as amended for CE Marking, as follo ws: Lo w-V oltage Directi v e (s afety). ..... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) ... ........... ......... ........ 89/336/EEC ...

  • National Instruments FP-CTR-502 - page 22

    FP-CTR-502 and cFP-CTR-502 22 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating instructions Go to ni. ...

Manufacturer National Instruments Category Network Card

Documents that we receive from a manufacturer of a National Instruments FP-CTR-502 can be divided into several groups. They are, among others:
- National Instruments technical drawings
- FP-CTR-502 manuals
- National Instruments product data sheets
- information booklets
- or energy labels National Instruments FP-CTR-502
All of them are important, but the most important information from the point of view of use of the device are in the user manual National Instruments FP-CTR-502.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals National Instruments FP-CTR-502, service manual, brief instructions and user manuals National Instruments FP-CTR-502. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product National Instruments FP-CTR-502.

A complete manual for the device National Instruments FP-CTR-502, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use National Instruments FP-CTR-502 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of National Instruments FP-CTR-502.

A complete National Instruments manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual National Instruments FP-CTR-502 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the National Instruments FP-CTR-502, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the National Instruments FP-CTR-502, that we can find in the current document
3. Tips how to use the basic functions of the device National Instruments FP-CTR-502 - which should help us in our first steps of using National Instruments FP-CTR-502
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with National Instruments FP-CTR-502
5. FAQ - Frequently Asked Questions