    INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W A4822 W A4823 W A6022 W A6023 W A602N Manual : 2100-348D Supersedes: 2100-348C File: V olume III T ab 16 Date: 05-20-01 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2001 ...

  • Bard WA6023 - page 2

    CONTENTS Figures Figure 1 Unit Dimensions ...................................... 3 W A602N, W A6023, WA4823 Figure 2 Unit Dimensions ...................................... 4 W A6022, WA4822 Figure 3 Mounting Instructions .............................. 8 W A602N, W A6023, WA4823 Figure 4 Mounting Instructions .............................. 9 W A6022 ...

  • Bard WA6023 - page 3

    Manual 2100-348 Page 1 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ........................ ANSI/NFPA 70 ...

  • Bard WA6023 - page 4

    Manual 2100-348 Page 2 W ALL MOUNT GENERAL INFORMA TION AIR CONDITIONING WALL MOUNT MODEL NOMENCLATURE W A 60 2 3 A 10 X N X X X A NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building. WA4822A, WA4822B, WA4823A, WA4823B, WA6022A, WA6022B are not approved for use with electric heat. ...

  • Bard WA6023 - page 5

    Manual 2100-348 Page 3 FIGURE 1 UNIT DIMENSIONS WA602N, WA6023, WA4823 ONLY MIS-1348 ...

  • Bard WA6023 - page 6

    Manual 2100-348 Page 4 FIGURE 2 UNIT DIMENSIONS WA6022, WA4822 ONLY MIS-1442 ...

  • Bard WA6023 - page 7

    Manual 2100-348 Page 5 TABLE 2 ELECTRICAL SPECIFICATIONS j k l Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75 ° C copper wire. All Wiring must conform to NEC and all local codes. These “ minimum Circuit Ampacity ” values are to be used for sizing the field power conductor ...

  • Bard WA6023 - page 8

    Manual 2100-348 Page 6 A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 3A for further details. Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity. Some ...

  • Bard WA6023 - page 9

    Manual 2100-348 Page 7 INST ALLA TION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 1 or 2. Figure 1 is for models WA4823, and WA6023. Figure 2 is for Models WA4822 and WA6022. 2. On wood frame walls, the wall construction must be strong and rigid enough to ...

  • Bard WA6023 - page 10

    Manual 2100-348 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WA602N, WA6023, WA4823 ONLY MIS-1349 ...

  • Bard WA6023 - page 11

    Manual 2100-348 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WA6022, WA4822 ONLY MIS-1444 ...

  • Bard WA6023 - page 12

    Manual 2100-348 Page 10 FIGURE 5 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPL Y AIR DUCT FOR W ALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURF ACES. MIS-277 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is ...

  • Bard WA6023 - page 13

    Manual 2100-348 Page 11 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT. RETURN AIR OPENING SUPPLY AIR OPENING WALL STRUCTURE FACTORY ...

  • Bard WA6023 - page 14

    Manual 2100-348 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-550 ...

  • Bard WA6023 - page 15

    Manual 2100-348 Page 13 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of el ...

  • Bard WA6023 - page 16

    Manual 2100-348 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS-1373A ...

  • Bard WA6023 - page 17

    Manual 2100-348 Page 15 ST ART UP IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. CRANKCASE HEATERS These units are not provided with crankcase heat. These units utilize scroll compressors which do not require crankcase heat in this application. HIGH PRESSURE SWITCH The models are suppl ...

  • Bard WA6023 - page 18

    Manual 2100-348 Page 16 PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number. Low Pressure Switch, Bypass, an ...

  • Bard WA6023 - page 19

    Manual 2100-348 Page 17 The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle. REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. ...

  • Bard WA6023 - page 20

    Manual 2100-348 Page 18 Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions. COOLING TABLE 10 PRESSURE TABLE Ai ...

  • Bard WA6023 - page 21

    Manual 2100-348 Page 19 TABLE 11 OPTIONAL ACCESSORIES WA6023A. WA6022A WA6023B, WA6022B WA4823A, WA4822A WA4823B, WA4822B t r a P r e b m u Nn o i t p i r c s e D 5 1 - C M Ct i K t r a t SX X A 9 0 - B C M W B 7 0 - B C M W A 8 0 - B C M W B 5 0 - B C M W t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u ...

Manufacturer Bard Category Air Conditioner

Documents that we receive from a manufacturer of a Bard WA6023 can be divided into several groups. They are, among others:
- Bard technical drawings
- WA6023 manuals
- Bard product data sheets
- information booklets
- or energy labels Bard WA6023
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bard WA6023.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bard WA6023, service manual, brief instructions and user manuals Bard WA6023. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bard WA6023.

Similar manuals

A complete manual for the device Bard WA6023, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bard WA6023 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bard WA6023.

A complete Bard manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bard WA6023 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bard WA6023, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bard WA6023, that we can find in the current document
3. Tips how to use the basic functions of the device Bard WA6023 - which should help us in our first steps of using Bard WA6023
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bard WA6023