Manual Foster RBC20-60

32 pages 0.98 mb
Download

Go to site of 32

Summary
  • Foster RBC20-60 - page 1

    RBC20-60 Blast Chiller ...

  • Foster RBC20-60 - page 2

    1 Contents Page Introduction 1 to 2 Model Details 2 Controller Technical Detail 2 Parts List 2 Operating Instructions 3 to 6 Electrical Connections 7 Service Information 7 to 19 Diagnostics 8 Function Test 8 Passcode 8 Profiles 9 Parameter Access 9 Parameters 9 to 11 Parameter Definitions 11 to 18 Alarms and Warnings 18 Foot Print Test Operation 19 ...

  • Foster RBC20-60 - page 3

    2 The controller will determine the temperature to be maintain ed during the hold phase base d on the chilling cycle th at has been completed. If a soft or hard chill has taken pla ce the controller will maintain an air temp erature of 2°c. The hold mode is p rincipally intended as a tempora ry storage facility offering the op erator flexibility u ...

  • Foster RBC20-60 - page 4

    Blast Chill & Shock Freeze Operating Instructions. Standard Operation When mains electrical power is first applied to the controller it will carry out a self-test fun ction, for approximately 3 seconds. During this period the display will show. On completion of the self test, the controller w ill revert to the last chill program that was run 3 ...

  • Foster RBC20-60 - page 5

    4 Pre Chill This program is used to Pre Chill the cabinet prior to the first cycle. This is done with the Blast Chiller empty and is a short time based pro gram of about 20 minutes. It is generally recognised a s the correct me thod of preparing for a blast chill cycle. The program is selected by rotating the dial until the display sho ws, press an ...

  • Foster RBC20-60 - page 6

    Information Whilst in the program selection screen pre ss and hold the dial for 2 se conds, the information screen will be displayed. Rotate the dial until ‘INFORMATION’ is highlighted. Press and release the dial to display the screen showi ng t he last run cy cle. The information relates to date, program run, start time, start temperatu re a n ...

  • Foster RBC20-60 - page 7

    6 High Temperature: This alarm will only occur in the hold mode only. Probe the product to determin e it is at the correct temperature. If it is at the correct temperature plac e in a storage refrigerato r or freezer and call you r Foster Authorised Service Company. If the produ ct te mperature is above the gui delin es check the chill time selecte ...

  • Foster RBC20-60 - page 8

    Electrical Connections. Inputs. L - Mains ‘Live’ supply (115V 230V, 50Hz / 60Hz). 4 terminals. N - Mains ‘Neutral’ supply – 16 terminals. E - Protective Earth – 16 terminals. DOOR - Door Switching connectio n (not voltage carrying). DOOR2 - Safety door switch connection (not voltage carryin g). HP - High Pressu re swit ch c onnection (n ...

  • Foster RBC20-60 - page 9

    Diagnostics Rotate the dial until you reac h ‘Diagnostics’, below left, pres s and release the dial to highlight the com ponent. In this program you can test each of the majo r components on the machine in sequen ce, 1- COMPRESSOR, 2-FAN1, 3-FAN2, 4- DEFROST, 5- ALARM, 6- CC AP (Capacity Contro l), 7- UV-L (UV light if fi tted), ESC (escape). R ...

  • Foster RBC20-60 - page 10

    Profiles. You are now in the pr ogram profiles. Th e controller has 9 operating programs – Pre Chill, Soft Chill, Hard Chill, Hard Chill Max, Shock Freeze, Professional 1, Prof essional 2, Professional 3, Defrost a nd 2 optional pro grams – UV Sanitisation and Information. These programs are al l available dependi ng upon which of the profile s ...

  • Foster RBC20-60 - page 11

    10 HA RD MA X P14 AIR TEMP °C -20 15 -15 P15 Chill Time MINUTES 5 480 90 P16 CHILL TEMP °C -15 15 3 P17 HOLD TEMP °C -15 15 3 SHOCK FREEZE P18 AIR TEMP °C -35 15 -30 P19 CHILL TIME MINUTES 5 480 240 P20 CHILL TEMP °C -35 15 -21 P21 HOLD TEMP °C -35 15 -21 PROFFESSIONAL 1 P22 Air Temp. Std. °C -20 15 -15 P23 Chill Time Std. Minutes P24 P25 90 ...

  • Foster RBC20-60 - page 12

    11 P86 Alarm Buzzer Function NO YES NO P87 Air Probe Offset °K -15 15 0 P88 Coil Probe Offset °K -15 15 0 P89 Food 1 Offset °K -15 15 0 P90 Food 2 Enable Function NO YES NO P91 Food 2 Offset °K -15 15 0 P92 Food 3 Enable Function NO YES NO P93 Food 3 Offset °K -15 15 0 P94 Address Integer 1 255 255 Parameter Definitions Pre-Chill P01 Pre-Chill ...

  • Foster RBC20-60 - page 13

    12 P13 Change Temp The percentage of a temperature b ased chill cycle, wh ich is passed bef ore automatically adjustin g the air temperature set point to 1°C.The rang e is adjustable in 5% increme nts. Range 5% to 95%. Hard Max P14 Air Temp The temperature, which the air probe must re ad before the condensin g system is de-energi sed in the chill ...

  • Foster RBC20-60 - page 14

    13 P27 Chill Temp Minimum The minimum value that the temperature, which Food Probe 1 must read before the condensi ng system is de- energised in the chill mode of the Professional 1 program, prior to entering the Hold mode of a temperatu re based cycle, which it can be adjusted to by the operator. Range -20°C to -5°C. P28 Chill Temp Maximum The m ...

  • Foster RBC20-60 - page 15

    14 P40 Chill Temp Maximum The maximum value that the tempe rature, which F ood Pr obe 1 must read before the condensing system is de- energised in the chill mode of the Professional 2 program, prior to entering the Hold mode of a temperatu re based cycle, which it can be adjusted to by the operator. Range -5°C to -15° C. P41 Hold Temp Std The sta ...

  • Foster RBC20-60 - page 16

    15 P53 Hold Temp Std The standard temperature, which the air probe must r ead before the conden sing system is de-energised in the Hold mode of the Professional 3 Progra m. Range -15°C to 15°C. P54 Hold Temp Minimum The minimum value that the Hold tem perature set point ca n be adj usted to by the operator i n the Professional 3 program. Range -1 ...

  • Foster RBC20-60 - page 17

    16 Note: The fan 1 hold operation does not effect routine defros t operat ion. P66 FAN 2 Hold Operation Determines the evaporator fan relay energisation d uring ‘Hold’ mode. ‘OFF’ = Evaporator fan 2 relay is not energised in ‘Hold’. ‘CYCLE’ = Evaporator fan 2 relay cycles with condensing syste m relay in ‘Ho ld’. ‘AUTO’ = Ev ...

  • Foster RBC20-60 - page 18

    17 NO = No safety door switch fitted. YES = Safety door switch fitted. Note: Usually fitted to the e vaporator fan door on Mod ular Blast Chillers. P79 Door Switch 1 Determines if a d oor switch is fitted or not, and conseque ntly dictates Eva porator Fa n opera tion, UV Sanitisation operation and door alarm activation’s. Also used to initiate th ...

  • Foster RBC20-60 - page 19

    NO = No third food probe fitted. YES = Third food probe fitted. P93 Food 3 Offse t Allows the value of Food Probe 3 to be offset allowing for the product temperatu re to be accurately measured. Range -15°C to +15°C. P94 Address The controller periphe ral number. This is only necessary when controlle r are linked via a network to a computer manage ...

  • Foster RBC20-60 - page 20

    Foot Print Test operation The foot print test is a method of checking the operati on of the process in a redu ced time pe ri od The foot print test takes ten minutes. The first ten seconds are used for the display test, after that the relays are energised in a simple operating pattern to ensure each are energised. During the fi nal ten seconds the ...

  • Foster RBC20-60 - page 21

    20 Technical Data RBC20-60 RBC20-60R Nominal Chilling Capacity 60Kg 60Kg Duty @ -15°C 3800w 3800w Fans 3 3 Evaporating Temperature -15°C -15°C HP Switch Setting Refrigerant Control TEV TEV Refrigerant R404a R404a Refrigerant Quantity System 1 1900grms System 2 1900grms Electrical Supply 400/3/50 – 16amp 230/1/50 13 amp (Fans & Defrost) Tot ...

  • Foster RBC20-60 - page 22

    21 EVAPORATOR ASSE MBLY RBC20-60 SERVICE PLATE SYSTEM 1 & SYSTEM 2 PHIALS MUST BE FITTED IN THE HORIZONTAL POSITION AND CORK TAPED FAN PLATE ...

  • Foster RBC20-60 - page 23

    22 Schematic Dual Circuit Refrigeration Layout CONDENSER - DUAL CIRCUIT COMPRESSOR COMPRESSOR EVAPORATOR – DUAL CIRCUIT SIGHT GLASS SOL. VALVE DRIER SIGHT GLASS SOL. VALVE DRIER EXP. VALVE EXP. VALVE LIQUID RECEIVER LIQUID RECEIVER HP SW. HP SW. LP SW. LP SW. PHIAL PHIAL STAT EQUALISING LINE EQUALISING LINE ...

  • Foster RBC20-60 - page 24

    23 COMPRESSOR WIRING RBC20-60 ...

  • Foster RBC20-60 - page 25

    RBC20-60 1 of 2 Wiring Diagram 24 ...

  • Foster RBC20-60 - page 26

    RBC20-60 2 of 2 Wiring Diagram 25 ...

  • Foster RBC20-60 - page 27

    RBC20-60R 1 of 2 Wiring Diagram 26 ...

  • Foster RBC20-60 - page 28

    27 RBC20-60R 2 of 2 Wiring Diagram ...

  • Foster RBC20-60 - page 29

    ...

  • Foster RBC20-60 - page 30

    2 ...

  • Foster RBC20-60 - page 31

    3 ...

  • Foster RBC20-60 - page 32

    4 Foster European Oper ations rance oster Refrigerator France SA el: (33) 01 34 30 22 22 Fax: (33) 01 30 37 68 74 Email: info@f osterfrance.com F F T Germany oster Refrigerator Germany el: (0781) 96 93 00 Fax: (0781) 96 93 019 Email: info@fosterrefrige rator.de F T oster Refrigerator ldmedow R oad, King’s Ly nn, orfolk Pe 30 4JU ngland el: 01553 ...

Manufacturer Foster Category Refrigerator

Documents that we receive from a manufacturer of a Foster RBC20-60 can be divided into several groups. They are, among others:
- Foster technical drawings
- RBC20-60 manuals
- Foster product data sheets
- information booklets
- or energy labels Foster RBC20-60
All of them are important, but the most important information from the point of view of use of the device are in the user manual Foster RBC20-60.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Foster RBC20-60, service manual, brief instructions and user manuals Foster RBC20-60. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Foster RBC20-60.

Similar manuals

A complete manual for the device Foster RBC20-60, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Foster RBC20-60 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Foster RBC20-60.

A complete Foster manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Foster RBC20-60 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Foster RBC20-60, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Foster RBC20-60, that we can find in the current document
3. Tips how to use the basic functions of the device Foster RBC20-60 - which should help us in our first steps of using Foster RBC20-60
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Foster RBC20-60
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Foster RBC20-60 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Foster RBC20-60?

Use the form below

If you did not solve your problem by using a manual Foster RBC20-60, ask a question using the form below. If a user had a similar problem with Foster RBC20-60 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)