    S h i n c o S e r v i c e M a n u a l - 1 - SERVICE MANUAL Model: KFR-25GWZ/BM KFR-35GWZ/BM KFR-50GWZ/BM KFR-70GWZ/BM Inverter Split system Air Conditioner R410A ...

  • Shinco KFR-25GWZ BM - page 2

    S h i n c o S e r v i c e M a n u a l - 2 - T able of contents Part I 1. Introductions of Part Names and Functions 2. Outline Dimension of Indoor and Outdoor Units 3 . S p e c i f i c a t i o n 4. W iring Diagram 5. Refrigeration System Diagram 6. Refrigeration Piping Length and Height Dif ference T able Additional Refrigerant Char ge T able 7. Sen ...

  • Shinco KFR-25GWZ BM - page 3

    S h i n c o S e r v i c e M a n u a l - 3 - Part I 1. Intr oductions of Part Names and Functions 1.1 Remote controller ...

  • Shinco KFR-25GWZ BM - page 4

    S h i n c o S e r v i c e M a n u a l - 4 - 1.2 Indoor panel 1.3 Outdoor panel ...

  • Shinco KFR-25GWZ BM - page 5

    S h i n c o S e r v i c e M a n u a l - 5 - 2. Outline Dimension of Indoor and Outdoor Units 2.1. Outdoor unit SIZE mm MODEL A B C D E F G KFR-25GWZ/BM 542 762 58 257 285 321 540 KFR-35GWZ/BM 542 762 58 257 285 321 540 KFR-50GWZ/BM 656 865 52 307 339.5 372 633 KFR-70GWZ/BM 840 950 60 352 388 425 582 ...

  • Shinco KFR-25GWZ BM - page 6

    S h i n c o S e r v i c e M a n u a l - 6 - 2.2 Indoor unit U n i t : mm KFR-25GWZ/BM KFR-35GWZ/BM ...

  • Shinco KFR-25GWZ BM - page 7

    S h i n c o S e r v i c e M a n u a l - 7 - KFR-50GWZ/BM ...

  • Shinco KFR-25GWZ BM - page 8

    S h i n c o S e r v i c e M a n u a l - 8 - KFR-70GWZ/BM ...

  • Shinco KFR-25GWZ BM - page 9

    S h i n c o S e r v i c e M a n u a l - 9 - SIZE mm MODEL X Y Z L M N O KFR-25GWZ/BM 814 272 197 604 255 55 498 KFR-35GWZ/BM 814 272 197 604 255 55 498 KFR-50GWZ/BM 1013 323 198 648 295 57 502 KFR-70GWZ/BM 1 138 323 212 1055 312 180 679 3. Specification Product type KFR-25GWZ/BM KFR- 35GWZ/BM KFR-50GWZ/BM KFR- 70GWZ/BM Product N u m b e r Indoor be ...

  • Shinco KFR-25GWZ BM - page 10

    S h i n c o S e r v i c e M a n u a l - 10 - 4. Wiring Diagram 4.1 Indoor unit Wiring diagram KFR-25GWZ/BM KFR-35GWZ/BM ...

  • Shinco KFR-25GWZ BM - page 11

    S h i n c o S e r v i c e M a n u a l - 11 - KFR-50GWZ/BM KFR-70GWZ/BM ...

  • Shinco KFR-25GWZ BM - page 12

    S h i n c o S e r v i c e M a n u a l - 12 - 4.2 Outdoor unit Wiring diagram KFR-25GWZ/BM KFR-35GWZ/BM ...

  • Shinco KFR-25GWZ BM - page 13

    S h i n c o S e r v i c e M a n u a l - 13 - KFR-50GWZ/BM KFR-70GWZ/BM ...

  • Shinco KFR-25GWZ BM - page 14

    S h i n c o S e r v i c e M a n u a l - 14 - 5. Refrigerant system diagram ...

  • Shinco KFR-25GWZ BM - page 15

    S h i n c o S e r v i c e M a n u a l - 15 - 6. Max. r efrigerant piping length and max. height differ e nce 6.1 Piping length and height differ ence REFRIGERANT PIPING:M PIPING SIZE O.D:mm MODEL Max. length Max. Height difference Gas Liquid KFR-25GWZ/BM 15 5 9.52 6.35 KFR-35GWZ/BM KFR-50GWZ/BM 15 5 12.7 6.35 KFR-70GWZ/BM 15 5 9.52 12.88 6.2 Additi ...

  • Shinco KFR-25GWZ BM - page 16

    S h i n c o S e r v i c e M a n u a l - 16 - 7. Sensor Resistance T able 7.1 KFR-25GWZ/BM 、 KFR-35GWZ /BM Sensor Resistance T able 7.1.1 indoor air sensor、indoor pipe sensor、outdoor air sensor、outdoor pipe sensor R-T datasheet 10K±0 .5% ;3976K±0.5%,B(25/8 5)=3976K±0.5% R-T datasheet Temp.( ℃ ) R(K Ω ) Temp.( ℃ ) R(K Ω ) Temp.( ...

  • Shinco KFR-25GWZ BM - page 17

    S h i n c o S e r v i c e M a n u a l - 17 - 7.1.2 outdoor discharge pipe R(0)=187.25K±6.3% ;B(0/100)=3979K±1% R -T datasheet Temp.( ℃ ) R(min) (K Ω ) R(cent) (K Ω ) R(max) (K Ω ) Δ R(mi n) Δ R(max) -20 488.35 526.61 565.60 -7.3% 7.4% -19 461.94 497.84 534.41 -7.2% 7.3% -18 437.15 470.87 505.17 -7.2% 7.3% -17 413.89 445.57 477.76 -7.1% 7.2 ...

  • Shinco KFR-25GWZ BM - page 18

    S h i n c o S e r v i c e M a n u a l - 18 - 31 47.054 50.876 54.791 -7.5% 7.7% 32 45.273 48.939 52.757 -7.5% 7.8% 33 43.565 47.140 50.806 -7.6% 7.8% 34 41.928 45.386 48.934 -7.6% 7.8% 35 40.358 43.703 47.137 -7.7% 7.9% 36 38.852 42.087 45.412 -7.7% 7.9% 37 37.408 40.536 43.755 -7.7% 7.9% 38 36.018 39.047 42.163 -7.8% 8.0% 39 34.685 37.616 40.632 - ...

  • Shinco KFR-25GWZ BM - page 19

    S h i n c o S e r v i c e M a n u a l - 19 - 84 6.4273 7.0878 7.7850 -9.3% 9.8% 85 6.1825 6.8204 7.4942 -9.4% 9.9% 86 5.9462 6.5623 7.2135 -9.4% 9.9% 87 5.7184 6.3133 6.9424 -9.4% 10.0% 88 5.4987 6.0731 6.6808 -9.5% 10.0% 89 5.2867 5.8413 6.4284 -9.5% 10.1% 90 5.0827 5.6177 6.1847 -9.5% 10.1% 91 4.8853 5.4018 5.9495 -9.6% 10.1% 92 4.6953 5.1939 5.7 ...

  • Shinco KFR-25GWZ BM - page 20

    S h i n c o S e r v i c e M a n u a l - 20 - -8 23.11 24.59 26.15 -6.0% 6.3% -7 21.94 23.33 24.78 -5.9% 6.2% -6 20.84 22.13 23.48 -5.8% 6.1% -5 19.79 21.00 22.26 -5.7% 6.0% -4 18.81 19.94 21.11 -5.6% 5.9% -3 17.88 18.93 20.03 -5.5% 5.8% -2 17.00 17.98 19.00 -5.5% 5.7% -1 16.17 17.09 18.04 -5.4% 5.6% 0 15.39 16.24 17.13 -5.3% 5.5% 1 14.64 15.44 16.2 ...

  • Shinco KFR-25GWZ BM - page 21

    S h i n c o S e r v i c e M a n u a l - 21 - 45 2.077 2.178 2.280 -4.6% 4.7% 46 1.996 2.094 2.194 -4.7% 4.8% 47 1.918 2.014 2.112 -4.7% 4.9% 48 1.843 1.937 2.033 -4.8% 5.0% 49 1.772 1.863 1.958 -4.9% 5.1% 50 1.704 1.793 1.885 -5.0% 5.1% 51 1.639 1.726 1.816 -5.0% 5.2% 52 1.577 1.662 1.749 -5.1% 5.3% 53 1.517 1.600 1.686 -5.2% 5.4% 54 1.460 1.541 1. ...

  • Shinco KFR-25GWZ BM - page 22

    S h i n c o S e r v i c e M a n u a l - 22 - 98 0.3253 0.3536 0.3840 -8.0% 8.6% 99 0.3156 0.3433 0.3730 -8.1% 8.7% 100 0.3063 0.3333 0.3624 -8.1% 8.7% 101 0.2973 0.3237 0.3522 -8.2% 8.8% 102 0.2886 0.3144 0.3423 -8.2% 8.9% 103 0.2802 0.3055 0.3327 -8.3% 8.9% 104 0.2721 0.2968 0.3235 -8.3% 9.0% 105 0.2643 0.2885 0.3146 -8.4% 9.0% 106 0.2568 0.2804 0 ...

  • Shinco KFR-25GWZ BM - page 23

    S h i n c o S e r v i c e M a n u a l - 23 - 151 0.0822 0.0918 0.1025 -10.5% 11.6% 152 0.0805 0.0899 0.1003 -10.5% 11.6% 153 0.0787 0.0880 0.0983 -10.5% 11.7% 154 0.0771 0.0862 0.0963 -10.6% 11.7% 155 0.0755 0.0844 0.0943 -10.6% 11.8% 156 0.0739 0.0827 0.0924 -10.6% 11.8% 157 0.0724 0.0810 0.0906 -10.7% 11.9% 158 0.0709 0.0794 0.0888 -10.7% 11.9% 1 ...

  • Shinco KFR-25GWZ BM - page 24

    S h i n c o S e r v i c e M a n u a l - 24 - 19 71.119 76.120 81.343 -6.6% 6.9% 20 67.899 72.772 77.870 -6.7% 7.0% 21 64.840 69.587 74.562 -6.8% 7.1% 22 61.935 66.558 71.412 -6.9% 7.3% 23 59.175 63.676 68.411 -7.1% 7.4% 24 56.551 60.934 65.550 -7.2% 7.6% 25 54.057 58.323 62.824 -7.3% 7.7% 26 51.685 55.836 60.225 -7.4% 7.9% 27 49.429 53.469 57.746 - ...

  • Shinco KFR-25GWZ BM - page 25

    S h i n c o S e r v i c e M a n u a l - 25 - 72 8.1928 9.3386 10.628 -12.3% 13.8% 73 7.9040 9.0189 10.275 -12.4% 13.9% 74 7.6266 8.7114 9.9346 -12.5% 14.0% 75 7.3600 8.4156 9.6072 -12.5% 14.2% 76 7.1038 8.1310 9.2920 -12.6% 14.3% 77 6.8575 7.8572 8.9883 -12.7% 14.4% 78 6.6208 7.5938 8.6958 -12.8% 14.5% 79 6.3932 7.3401 8.4139 -12.9% 14.6% 80 6.1742 ...

  • Shinco KFR-25GWZ BM - page 26

    S h i n c o S e r v i c e M a n u a l - 26 - -40 106.800 113.500 120.50 0 -5.90% 6.17% -39 101.000 107.200 113.70 0 -5.78% 6.06% -38 95.600 101.300 107.400 -5.63% 6.02% -37 90.430 95.760 101.400 -5.57% 5.89% -36 85.610 90.550 95.740 -5.46% 5.73% -35 81.070 85.660 90.470 -5.36% 5.62% -34 76.800 81.060 85.510 -5.26% 5.49% -33 72.780 76.730 80.860 -5. ...

  • Shinco KFR-25GWZ BM - page 27

    S h i n c o S e r v i c e M a n u a l - 27 - 14 7.9920 8.253 8.519 -3.16% 3.22% 15 7.667 7.924 8.186 -3.24% 3.31% 16 7.357 7.609 7.867 -3.31% 3.39% 17 7.061 7.309 7.563 -3.39% 3.48% 18 6.778 7.023 7.273 -3.49% 3.56% 19 6.509 6.749 6.995 -3.56% 3.64% 20 6.252 6.487 6.729 -3.62% 3.73% 21 6.006 6.238 6.475 -3.72% 3.80% 22 5.772 5.999 6.232 -3.78% 3.88 ...

  • Shinco KFR-25GWZ BM - page 28

    S h i n c o S e r v i c e M a n u a l - 28 - 67 1.1980 1.2840 1.3760 -6.70% 7.17% 68 1.1620 1.2460 1.3360 -6.74% 7.22% 69 1.1270 1.2090 1.2970 -6.78% 7.28% 70 1.0930 1.1740 1.2600 -6.90% 7.33% 71 1.0600 1.1390 1.2240 -6.94% 7.46% 72 1.0290 1.1060 1.1890 -6.96% 7.50% 73 0.9985 1.0740 1.1550 -7.03% 7.54% 74 0.9691 1.0430 1.1220 -7.09% 7.57% 75 0.9407 ...

  • Shinco KFR-25GWZ BM - page 29

    S h i n c o S e r v i c e M a n u a l - 29 - 119 0.2838 0.3129 0.3448 -9.30% 10.19% 120 0.2767 0.3052 0.3365 -9.34% 10.26% 7.2.4 outdoor discharg e pipe R(0)=187.25K±6.3% ;B(0/100)=3979K± 1% R-T datasheet Temp.( ℃ ) R(min) (K Ω ) R(cent) (K Ω ) R(max) (K Ω ) Δ R(mi n) Δ R(max) -20 488.35 526.61 565.60 -7.3% 7.4% -19 461.94 497.84 534.41 -7 ...

  • Shinco KFR-25GWZ BM - page 30

    S h i n c o S e r v i c e M a n u a l - 30 - 28 52.880 57.110 61.433 -7.4% 7.6% 29 50.853 54.942 59.124 -7.4% 7.6% 30 48.913 52.866 56.911 -7.5% 7.7% 31 47.054 50.876 54.791 -7.5% 7.7% 32 45.273 48.939 52.757 -7.5% 7.8% 33 43.565 47.140 50.806 -7.6% 7.8% 34 41.928 45.386 48.934 -7.6% 7.8% 35 40.358 43.703 47.137 -7.7% 7.9% 36 38.852 42.087 45.412 - ...

  • Shinco KFR-25GWZ BM - page 31

    S h i n c o S e r v i c e M a n u a l - 31 - 81 7.2170 7.9495 8.7215 -9.2% 9.7% 82 6.9443 7.6520 8.3983 -9.2% 9.8% 83 6.6812 7.3649 8.0883 -9.3% 9.8% 84 6.4273 7.0878 7.7850 -9.3% 9.8% 85 6.1825 6.8204 7.4942 -9.4% 9.9% 86 5.9462 6.5623 7.2135 -9.4% 9.9% 87 5.7184 6.3133 6.9424 -9.4% 10.0% 88 5.4987 6.0731 6.6808 -9.5% 10.0% 89 5.2867 5.8413 6.4284 ...

  • Shinco KFR-25GWZ BM - page 32

    S h i n c o S e r v i c e M a n u a l - 32 - 8. Parts List and exploding view Exploding view and part list of KFR-25GWZ /BM Indoor unit No. Part Name Quantity BOM code 1 Wall Mount ed Board 1 e18503 2 Chassis A ssembly 1 e535123 3 Cross Fan 1 e19294 4 Left Axial Co ver 1 e19257 5 Evaporator Pipe 1 e20747 6 Evaporator 1 eQ0013 8 7 Frame Assembly 1 e ...

  • Shinco KFR-25GWZ BM - page 33

    S h i n c o S e r v i c e M a n u a l - 33 - 12 Indoor 1 eb3515 3 13 Air Sensor 1 eb1166 5 14 Pipe sensor 1 eb11666 15 Motor Cover 1 e1 9258 16 Indoor Mot or 1 eb38560 17 Step Motor 1 eb60073 18 Copper Pip e Clip 1 e1 9256 19 Electric Controlling box Up Cover 1 e1929 6 20 Indoor Contro lling Board 1 e50582 21 Electric Controlling box soleplate 1 e ...

  • Shinco KFR-25GWZ BM - page 34

    S h i n c o S e r v i c e M a n u a l - 34 - 3 Axial Fan 1 eb38658 4 Motor Brac ket 1 e30206 5 Outdo or Air Sensor 1 eb11667 6 Condenser 1 eQ00136 7 Top Cover 1 e14335/e 14336 8 4-way valve win ding 1 eb40103 9 4-way valve 1 eb40090 10 dis charge sensor 1 eb11664 11 pipe sensor 1 eb 11667 12 Capillary assem bly 1 e20603 13 middle cli pboard 1 e1560 ...

  • Shinco KFR-25GWZ BM - page 35

    S h i n c o S e r v i c e M a n u a l - 35 - Exploding view and part list of KFR-35GWZ /BM Indoor unit No. Part Name Quantity BOM code 1 Wall Mounted Board 1 e18503 2 Chassis Assembly 1 e535123 3 Cross Fan 1 e19294 4 Left Axial Cover 1 e19257 5 Evaporator Pipe 1 e20748 6 Evaporator 1 eQ00138 7 Frame Assembly 1 e19297 8 Frame 1 7 include 8 9 PVC 1 e ...

  • Shinco KFR-25GWZ BM - page 36

    S h i n c o S e r v i c e M a n u a l - 36 - 12 Indoor terminal block 1 eb35153 13 Air Sensor 1 eb11665 14 Pipe sensor 1 eb11666 15 Motor Cover 1 e19258 16 Indoor Motor 1 eb38560 17 Step Motor 1 eb60073 18 Copper Pipe Clip 1 e19256 19 Electric Controlling box Up Cover 1 e19296 20 Indoor Controlling Board 1 e52125 21 Electric Controlling box solepla ...

  • Shinco KFR-25GWZ BM - page 37

    S h i n c o S e r v i c e M a n u a l - 37 - No. Part Name Quantity BOM code 1 Chassis A ssembly 1 e3064 0/e30641 2 Front Frame Assembly 1 e14598/e1 4599 3 Axial Fan 1 eb38658 4 Motor Brac ket 1 e30308 5 Outdo or Air Sensor 1 eb11667 6 Condenser 1 eQ00137 7 Top Cover 1 e14335/e 14336 8 4-way valve win ding 1 eb40103 9 4-way valve 1 eb40094 10 dis c ...

  • Shinco KFR-25GWZ BM - page 38

    S h i n c o S e r v i c e M a n u a l - 38 - 8.3 Exploding view and pa rt list of KFR-50GWZ /BM Indoor unit No. Part N ame Quantity BOM code 1 Wall Mounte d Board 1 e17978 2 Chassis Ass embly 1 e19341 3 Cross Fan 1 eb38669 4 Left Axial Cover 1 e17980 5 Evaporator Pipe 1 e20509 6 Evaporator 1 eQ00139 7 Frame Assem bly 1 e19340 8 Frame 1 7 include 8 ...

  • Shinco KFR-25GWZ BM - page 39

    S h i n c o S e r v i c e M a n u a l - 39 - 10 Filter 1 e17989 11 Display board Assembly 1 e50543 12 Indoor termin al block 1 eb35153 13 Air Sensor 1 eb10007 14 Motor Cover 1 e17982 15 Indoor Motor 1 eb38668 16 Step Motor 1 eb38162 17 Flume 1 e19342 18 Copper Pipe C lip 1 e17987 19 Electric Cont rolling box 1 e30706 20 Electric Controlling box sol ...

  • Shinco KFR-25GWZ BM - page 40

    S h i n c o S e r v i c e M a n u a l - 40 - No. Part N ame Quantity BOM code 1 C hassis Assembly 1 e30708/e30709 2 Front Fra me Assembly 1 e30741/e3 0742 3 Axial Fan 1 eb38670 5 Motor Brac ket 1 e30684 6 Outdoor Air Se nsor 1 eb100 11 7 Condenser 1 eQ00140 8 Top Cover 1 e30680 /e30681 9 4-way valv e winding 1 eb40103 10 4-way valv e 1 eb40094 11 d ...

  • Shinco KFR-25GWZ BM - page 41

    S h i n c o S e r v i c e M a n u a l - 41 - Exploding view and part list of KFR-70GWZ /BM Indoor unit No. Part Name Quantity BOM code 1 Wall Mount ed Board 1 e18416 2 Air outlet vent assembly 1 e53512 6 3 Chassis As sembly 1 e19326 4 Cross Fa n 1 eb38667 5 ind oor connect pip e 1/2 1 e20442/e1 8771 6 Evaporator 1 eQ00141 7 Part Name 1 e19328 8 PVC ...

  • Shinco KFR-25GWZ BM - page 42

    S h i n c o S e r v i c e M a n u a l - 42 - 9 Remote Controller 1 eb8 5093 10 Display bo ard Assembl y 1 e50543 11 Ai r Sensor 1 eb10007 12 Indoor Controll ing Board 1 e50610 13 Indoor power Board 1 e50609 14 Electric Controlling box top Cover 1 e19325 15 Electric Con trolling box 1 e1932 4 16 Indoor terminal block 1 e35153 17 Indoor Motor 1 eb615 ...

  • Shinco KFR-25GWZ BM - page 43

    S h i n c o S e r v i c e M a n u a l - 43 - No. Part Name Quantity BOM code 1 Chass is Assembly 1 e30478/e3 0479 2 Fro nt Frame Assemb ly 1 e30693/e30694 3 Axial Fa n 1 eb38666 4 Outdoor motor 1 eb61532 5 Motor Bracket 1 e30512 6 middle cli pboard 1 e19166 7 outdo or air sensor 1 eb1 0011 8 Condense r 1 eQ00142 9 Top Cove r 1 e15838 /e15839 10 out ...

  • Shinco KFR-25GWZ BM - page 44

    S h i n c o S e r v i c e M a n u a l - 44 - Part II 1. Service warning Part I General W arnings 1 、 The service person should wear safety belt if working more than 2.5m above the ground. 2 、 If working above ground level, m easures should be adopted to prevent the outdoor unit or tools from falling and causing injuries or damage. 3 、 Check t ...

  • Shinco KFR-25GWZ BM - page 45

    S h i n c o S e r v i c e M a n u a l - 45 - 2. Frequency table F0 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 KFR-25GWZ/BM COOLING 0 30 35 40 45 52 55 58 66 69 73 KFR-25GWZ/BM HEATING 0 30 35 40 45 52 55 59 66 69 73 KFR-35GWZ/BM COOLING 0 30 36 42 48 54 61 66 72 78 84 KFR-35GWZ/BM HEATING 0 30 36 42 48 54 61 66 72 78 84 KFR-50GWZ/BM COOLING 0 30 36 43 49 56 64 ...

  • Shinco KFR-25GWZ BM - page 46

    S h i n c o S e r v i c e M a n u a l - 46 - 4. Running mode 4.1. Defrosting 1. Entry condition: Defrosting starts when m eeting one of the following c onditions a. The temperature of out door heat exchanger re mains cons ecutively lower than 3°c for m ore than 40 minutes, and the temperature remains consec utively -6°c for more than 3 minutes b. ...

  • Shinco KFR-25GWZ BM - page 47

    S h i n c o S e r v i c e M a n u a l - 47 - A- — E: rise the present frequency one class (for example, from F3 to F4) F: Frequency keep unchanged G:lower the present frequency on class ( for example, from F4 to F3), and the maximum frequency is F3 in G area. H:The compressor stops. c. Frequency will chan ge due to outdoor tempera ture, detai ...

  • Shinco KFR-25GWZ BM - page 48

    S h i n c o S e r v i c e M a n u a l - 48 - When condense r temperatur e is higher than 60 ℃, the comp ressor will stop, and hen t he condenser temperatur e lower to 50℃ and keep for 5 minutes, and compr essor frequency will rise to former valu e 4.4. Dehumidifying mode 4.4.1 Temperature set and motor control in dehumidifying mode The comp ...

  • Shinco KFR-25GWZ BM - page 49

    S h i n c o S e r v i c e M a n u a l - 49 - b. Frequency control d uring operation The frequency will change according to the RT-ST, and details s ee following fig. A- — E: rise the present frequency one class (for example, from F3 to F4) F: Frequency keep unchanged G:Lower the present frequency on class (for example, from F4 to F3), and the m ...

  • Shinco KFR-25GWZ BM - page 50

    S h i n c o S e r v i c e M a n u a l - 50 - 4.5.2 Indoor heat exch anger anti-overheated When indoor exchanger temperature is higher than 50 ℃, the compressor frequency will be lowered down to protect t he h eat exchanger . Wh en indoor exchanger tempera ture lower down to 46 ℃, the compressor frequency ri se up, and whe n the indoor exchanger ...

  • Shinco KFR-25GWZ BM - page 51

    S h i n c o S e r v i c e M a n u a l - 51 - 4.9 Refrigerant charge mode Entry condition : Press the emergenc y switch over 5 seconds, there will be three “DU” sound in the indoor unit, and start the unit with the remote controller. Actions : 1. On cooling mode, th e indoor fan speed is low the frequency is fixed on F6, 2. Cancel the mode ? ...

  • Shinco KFR-25GWZ BM - page 52

    S h i n c o S e r v i c e M a n u a l - 52 - KFR-25GWZ/BM MODE I1 I2 I3 COOLING A ND DEHUMIDIFYING 7.1 8.3 10.3 HEATING 6.3 7.5 9.5 KFR-35GWZ/BM MODE I1 I2 I3 COOLIGN A ND DEHUMIDIFYING 8.1 9.6 11.6 HEATING 10.5 12 14 KFR-50GWZ/BM MODE I1 I2 I3 COOLING A ND DEHUMIDIFYING 8.5 10.5 12.5 HEATING 8.5 10.5 12.5 KFR-70GWZ/BM MODE I1 I2 I3 COOLIGN AN D DE ...

  • Shinco KFR-25GWZ BM - page 53

    S h i n c o S e r v i c e M a n u a l - 53 - 6、Display lamp 6.1 Indoor display 5 6 7 1 2 3 4 1 Dual-Digital lamp; 2 Timer Lamp; 3 Operation lamp; 4 Protection Lamp; 5 cooling mode; 6 dehumidify mode; 7 heating mode 。 6.2 Fault code display KFR-25GWZ/BM、KFR- 35GWZ/BM Item FAULT CODE CHECK POIN T COUNT MEAS URE 1 INDOOR UNIT DON ’ T MATCH OUT ...

  • Shinco KFR-25GWZ BM - page 54

    S h i n c o S e r v i c e M a n u a l - 54 - 3 COMMUNICA TION FAULT BETWEEN I NDOOR UNIT AND OUTDOOR UN IT E4 1.CHECK IF THE CONNECTING WIRING IS CONNECT WELL 2.TEST THE VOLTAGE VALUE BETWE EN L4 AND S, IF IT ‘ S CHANGE REGUL ARLY,THE SINGAL TRANSFERI NG BE TWEEN INDOOR AND OUTDOOR UNIT IS GOOD, WHEN IT‘ S NO CHANGE IF VALUE IS BELOW 14 ...

  • Shinco KFR-25GWZ BM - page 55

    S h i n c o S e r v i c e M a n u a l - 55 - 13 INDOOR MOT OR IS FAULT E3 1、INDOOR MOTOR OR INDOOR MOTOR CAPACITOR IS FAULT 2、INNER WIRING DON ’ T CONNECT WEL L 3、INDOOR PCB IS FAULT 4、INDOOR MOTOR IS BLOCKE D 1、CHANGE MOTOR OR CAPACI TOR 2、FIX TH E WIRINGS 3、CHANGE INDOOR PCB 4、REMOVE THE BLOCKING 14 INDOOR PCB BAORD IS FAULTY EE ...

  • Shinco KFR-25GWZ BM - page 56

    S h i n c o S e r v i c e M a n u a l - 56 - HIGH 2、CHECK IF THE VOLTAGE I S TOO LOW, POWER WRINGIS T OO THIN OR TOO L ONG OR CONTACT BADLY 3、CHECK IF THE OUTLET IS BLOCKED OR THE CONDENSOR IS DIRTY 2、 UPDATING POWER SUPPLY, CHANG POWER WIRING 3、REMOVE OBSTACLE AROUND OUTDOOR UNIT OR WASH THE C ONDENSER 8 DRIVER BOARD IS F AULT P0 DRIVER BO ...

  • Shinco KFR-25GWZ BM - page 57

    S h i n c o S e r v i c e M a n u a l - 57 - KFR-50GWZ/BM、KFR- 70GWZ/BM Item FAULT CODE CHECK POIN T COUNT MEASURE 1 INDOOR AIR SENSOR IS FAULTY E1 2 INDOO R PIPE SENSOR I S FAULTY E2 1、CHECK THE SENSOR VALUE 2、INDOOR BOARD IS FAULT CHANGE SEN DOR CHANGE IND OOR BOARD 3 INDOO R IN-PHASE MOTO R IS FAULT E3 ---------------- ------- ------------ ...

  • Shinco KFR-25GWZ BM - page 58

    S h i n c o S e r v i c e M a n u a l - 58 - Note: The fault code doesn ’ t display directly, and it will display as following instruction: Press the ON/OFF button 6 times within 7 seconds, there will be three DU sound on indoor unit, and the indoor unit will displa y the fault code. 9 DRIVE R BOARD IS FAUL T P0 DRIVE R BOARD IS FAULT DRIVER BO A ...

  • Shinco KFR-25GWZ BM - page 59

    S h i n c o S e r v i c e M a n u a l - 59 - Annex PCB diagram KFR-25GWZ/BM 、 KFR-35GWZ/BM 1 、 Indoor PCB ...

  • Shinco KFR-25GWZ BM - page 60

    S h i n c o S e r v i c e M a n u a l - 60 - 2 、 Outdoor power board ...

  • Shinco KFR-25GWZ BM - page 61

    S h i n c o S e r v i c e M a n u a l - 61 - 3 、 Outdoor diver board ...

  • Shinco KFR-25GWZ BM - page 62

    S h i n c o S e r v i c e M a n u a l - 62 - 4 、 Outdoor PFC board ...

  • Shinco KFR-25GWZ BM - page 63

    S h i n c o S e r v i c e M a n u a l - 63 - KFR-50GWZ/BM 1 、 Indoor PCB ...

  • Shinco KFR-25GWZ BM - page 64

    S h i n c o S e r v i c e M a n u a l - 64 - 2 、 Outdoor power board ...

  • Shinco KFR-25GWZ BM - page 65

    S h i n c o S e r v i c e M a n u a l - 65 - 3 、 outdoor driver board ...

  • Shinco KFR-25GWZ BM - page 66

    S h i n c o S e r v i c e M a n u a l - 66 - KFR-70GWZ/BM 1 、 Indoor power board ...

  • Shinco KFR-25GWZ BM - page 67

    S h i n c o S e r v i c e M a n u a l - 67 - 2 、 Indoor d river board ...

  • Shinco KFR-25GWZ BM - page 68

    S h i n c o S e r v i c e M a n u a l - 68 - 3 、 outdoor power board ...

  • Shinco KFR-25GWZ BM - page 69

    S h i n c o S e r v i c e M a n u a l - 69 - 4 、 outdoor driver board ...

  • Shinco KFR-25GWZ BM - page 70

    S h i n c o S e r v i c e M a n u a l - 70 - Schematic KFR-25GWZ/BM 、 KFR-35GWZ/BM 1 、 Indoor PCB ...

  • Shinco KFR-25GWZ BM - page 71

    S h i n c o S e r v i c e M a n u a l - 71 - 2 、 Outdoor power board ...

  • Shinco KFR-25GWZ BM - page 72

    S h i n c o S e r v i c e M a n u a l - 72 - 3 、 Outdoor diver board ...

  • Shinco KFR-25GWZ BM - page 73

    S h i n c o S e r v i c e M a n u a l - 73 - 4 、 Outdoor PFC board ...

  • Shinco KFR-25GWZ BM - page 74

    S h i n c o S e r v i c e M a n u a l - 74 - KFR-50GWZ/BM 1 、 Indoor PCB ...

  • Shinco KFR-25GWZ BM - page 75

    S h i n c o S e r v i c e M a n u a l - 75 - 2 、 outdoor power board ...

  • Shinco KFR-25GWZ BM - page 76

    S h i n c o S e r v i c e M a n u a l - 76 - 3 、 outdoor driver board ...

  • Shinco KFR-25GWZ BM - page 77

    S h i n c o S e r v i c e M a n u a l - 77 - KFR-70GWZ/BM 1 、 Indoor power board ...

  • Shinco KFR-25GWZ BM - page 78

    S h i n c o S e r v i c e M a n u a l - 78 - 2 、 Indoor d river board ...

  • Shinco KFR-25GWZ BM - page 79

    S h i n c o S e r v i c e M a n u a l - 79 - 3 、 outdoor power board ...

  • Shinco KFR-25GWZ BM - page 80

    S h i n c o S e r v i c e M a n u a l - 80 - 4 、 outdoor driver board ...

  • Shinco KFR-25GWZ BM - page 81

    S h i n c o S e r v i c e M a n u a l - 81 - ...

Manufacturer Shinco Category Air Conditioner

Documents that we receive from a manufacturer of a Shinco KFR-25GWZ BM can be divided into several groups. They are, among others:
- Shinco technical drawings
- KFR-25GWZ BM manuals
- Shinco product data sheets
- information booklets
- or energy labels Shinco KFR-25GWZ BM
All of them are important, but the most important information from the point of view of use of the device are in the user manual Shinco KFR-25GWZ BM.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Shinco KFR-25GWZ BM, service manual, brief instructions and user manuals Shinco KFR-25GWZ BM. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Shinco KFR-25GWZ BM.

Similar manuals

A complete manual for the device Shinco KFR-25GWZ BM, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Shinco KFR-25GWZ BM by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Shinco KFR-25GWZ BM.

A complete Shinco manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Shinco KFR-25GWZ BM - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Shinco KFR-25GWZ BM, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Shinco KFR-25GWZ BM, that we can find in the current document
3. Tips how to use the basic functions of the device Shinco KFR-25GWZ BM - which should help us in our first steps of using Shinco KFR-25GWZ BM
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Shinco KFR-25GWZ BM
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Shinco KFR-25GWZ BM in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Shinco KFR-25GWZ BM?

Use the form below

If you did not solve your problem by using a manual Shinco KFR-25GWZ BM, ask a question using the form below. If a user had a similar problem with Shinco KFR-25GWZ BM it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)