Manual Miele VENTILATION SYSTEM DA 230-3

32 pages 0.63 mb
Download

Go to site of 32

Summary
  • Miele VENTILATION SYSTEM DA 230-3 - page 1

    Oper ating and installation instr uctions V entilation System D A 230-3 T o prevent accidents and machine damage, read these instructions bef ore installation or use. UV 05 853 520 M.-Nr . ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 2

    IMPOR T ANT SAFETY INSTR UCTIONS Functional description Appliance description Operation Main power switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 T urning on the fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Selecting the power le ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 3

    Read these Operating Instructions carefully bef ore installing or using the V entilation System. This appliance is intended for residential use only . Use the appliance only for its intended purpose. The manufacturer cannot be held responsible for damages caused by improper use of the hood. This appliance complies with current safety requir ements. ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 4

    This equipment is not designed for maritime use or for use in mobile installations such as caravans or air - craft. However , under cer tain conditions it may be possible for an installation in these applications. Please contact the nearest Miele dealer or the Miele T ech - nical Service Department with specific requir ements. Before servicing or c ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 5

    , W ARNING - T O REDUCE THE RISK OF A RANGE T OP GREASE FIRE: Never leave surface units unat - tended at high settings. Boilovers cause smoking and greasy spillovers may ignite. Heat oils slowly on low or medium settings. Always turn hood "ON" when cook - ing at high heat or when cooking flaming foods. Clean ventilating fans frequently . ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 6

    Installation , W ARNING T o reduce the risk of fire, only use metal ductwork. When installing the hood, follow the recommended minimum safety distances between a Miele cooktop and the hood: – 22" (55 cm) above electric cooktops, – 26" (65 cm) above gas cooktops, – 26" (65 cm) above an open grill. If local building codes requir ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 7

    The ventilation hood works by air ex - traction. The air is drawn in and cleaned by the grease filters and di - rected outside. The hood comes equipped with a non-return flap . This flap automatically closes when the hood is turned off so that no exchange of outside air and room air can occur . When the hood is turned on, the air pressure of the ex ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 8

    Appliance description 8 ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 9

    a Co ver plate b Chimney c Canopy d Contr ol panel e Grease filters f Overhead lighting g Main power s witc h h Light b utton This button turns the light on and off and also dims the light. The lighting can be used independently of the fan. i On/Off b utton j F an power le vel b uttons Four fan speed selection. k Dela yed Shut Do wn This button act ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 10

    Main power s witc h Press the main power switch to "I". The fan and the lighting can now be oper - ated. If the appliance is not going to be used for a long period of time (e.g. while va - cationing) turn the appliance off by pressing the main power switch to "0". The next time it is turned on, the hood will operate at the level ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 11

    T urning off the fan ^ Press the On/Of f button to turn the fan off. The indicator goes out. A utomatic Safety Shut Off The fan will turn off automatically 10 hours after the last button was acti - vated. The lighting however will remain on. ^ Press the On/Of f button to turn the fan back on again. T urning the lighting on/off The overhead lighting ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 12

    Grease filter timer A timer monitors the hours of fan opera - tion. The indicator for the grease filter will light after 30 hours of operation. The grease filters must then be cleaned. After the grease filters have been cleaned and put in place, the grease fil - ter timer must be reset. ^ T o do this, press the gr ease filter but - ton for about 3 ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 13

    Reprogramming the grease filter timer The grease filter timer is pr eset to 30 hours. This time can be lengthened or shortened to 20, 30, 40 or 50 hours. – A time of 20 hours should be pro - grammed in kitchens with frequent pan or deep frying. – A time of 20 hours should also be programmed if the kitchen is only used occasionally . Otherwise g ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 14

    Before cleaning or servicing the hood, disconnect it from the power supply by either removing the fuse, unplugging it from the outlet or man - ually "tripping" the circuit br eaker . Cleaning the casing , Never use abrasive cleaners, scouring pads, steel wool or caustic (oven) cleaners on the hood. They will damage the surface. ^ All exte ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 15

    Grease filters The reusable metal gr ease filters r e - move solid particles from the vented kitchen air (grease, dust, etc). The grease filters should be cleaned every 3-4 weeks or whenever the grease filter timer indicator lights. A dirty filter is a fire hazard. ^ T o remove the gr ease filters pr ess the locking clips in towards the middle of t ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 16

    Changing the light b ulb Before changing the light bulbs, dis - connect the hood from the power supply by either removing the fuse, unplugging it, or manually "tripping" the circuit br eaker . When in use halogen bulbs become extremely hot, and they can burn your hands. Do not attempt to change the bulbs until they have had sufficient tim ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 17

    In the event of a fault which you cannot correct yourself please contact: – Y our Miele Dealer or – The Miele T echnical Service Department USA 1-800-999-1360 techserv@mieleusa.com CDN 1-800-565-6435 service@miele.ca When contacting the T echnical Service Department, please quote the model and serial number of your appliance. These are shown on ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 18

    18 ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 19

    Installation instr uctions ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 20

    Caring f or the en vir onment Structural suppor t Electrical data Appliance dimensions Installation Air extraction T able of Contents 20 ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 21

    Disposal of pac king material The cardboar d box and packing materials protect the appliance during shipping. They have been designed to be biodegradable and recyclable. Please recycle. Ensure that any plastic wrappings, bags etc. are disposed of safely and kept out of the reach of childr en. Danger of suffocation! Disposal of an old appliance Old ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 22

    The ceiling mounting plate will sup - port the weight of the hood. This ceiling plate must be attached to rigid structural framing that is sup - ported in its entirety by the ceiling joists, or to the ceiling joists directly . Do not attach the plate directly to the ceiling by using anchors, mollies or toggle bolts. Structural suppor t 22 ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 23

    All electrical work should be per - formed by a qualified electrician in strict accordance with national and local safety regulations. Installation, repairs and other work by unqualified persons could be dangerous. The manufactur er can not be held responsible for unautho - rized work. Ensure that power to the appliance is OFF while installation or ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 24

    a Mounting bolt holes b Cut out for power cord c Exhaust connection 6" (150 mm) diameter Appliance dimensions 24 ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 25

    Do not install this exhaust hood over cooktops burning solid fuel. When installing the hood, make sure that the following minimum dis - tance ( S ) between the top of a Miele cooking surface and the bottom of the hood is: - 22" (55 cm) above electric cooktops - 26" (65 cm) above gas cooktops - 26" (65 cm) above an open grill For non- ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 26

    ^ Position the mounting plate and align the notches with the guide line. Mark the position of the four holes to be drilled a for securing the mount - ing plate and determining the posi- tion of the hole b the power cord will feed through. ^ Feed the ductwork and power cord through their r espective openings in the ceiling. If 6" (150mm) diamet ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 27

    ^ Secure the ducting to the mounting plate using a hose clip. ^ Insert the shor t edge of two spring clips into their slots from below and position so that the tab faces the cen- ter of the mounting plate. ^ Pull the power cord thr ough the mounting plate. ^ Insert the four countersunk screws M 6 x 20 into the recessed holes fr om above. T ape the ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 28

    ^ Secure the mounting plate to the ceil - ing using the 8 x 60 lag bolts. Once tight, make sure that the mounting plate can safely support the weight of the hood. ^ Pull the power cord thr ough its cut out on the flange of the chimney . ^ Using at least two people, lift the hood and guide the spring clips through their r espective slots in the flan ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 29

    ^ Bolt the flange firmly to the ceiling us - ing the four M6 nuts. ^ Shorten the power cord as much as possible and attach it to the ter minal block inside the chimney (see "Elec- trical data"). Before connecting the appliance read the "W ar ning and Safety In- structions" and the "Electrical data" sections. ^ Finally ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 30

    Danger of toxic fumes. Gas cooking appliances release carbon monoxide that can be har m - ful or fatal if inhaled. The exhaust gases extracted b y the hood should be vented outside of the b uilding only . Do not terminate the exhaust ducts in attics, gara ges, crawlspaces, etc. Please read and follow the "W arning and Safety Instructions" ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 31

    Never connect an exhaust hood to an active chimney , dryer vent, vent flue, or room venting ductwork. Seek professional advice befor e connect - ing an exhaust hood vent to an exist - ing, inactive chimney or vent flue. Ductwork with a diameter of less than 6" (150 mm) should only be used when absolutely necessar y . As duct diameter decreases ...

  • Miele VENTILATION SYSTEM DA 230-3 - page 32

    Alteration rights reserved / 5002 This paper consists of cellulose which has been bleached without the use of chlorine. 00 M.-Nr . 05 853 520 / V ...

Manufacturer Miele Category Ventilation Hood

Documents that we receive from a manufacturer of a Miele VENTILATION SYSTEM DA 230-3 can be divided into several groups. They are, among others:
- Miele technical drawings
- VENTILATION SYSTEM DA 230-3 manuals
- Miele product data sheets
- information booklets
- or energy labels Miele VENTILATION SYSTEM DA 230-3
All of them are important, but the most important information from the point of view of use of the device are in the user manual Miele VENTILATION SYSTEM DA 230-3.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Miele VENTILATION SYSTEM DA 230-3, service manual, brief instructions and user manuals Miele VENTILATION SYSTEM DA 230-3. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Miele VENTILATION SYSTEM DA 230-3.

Similar manuals

A complete manual for the device Miele VENTILATION SYSTEM DA 230-3, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Miele VENTILATION SYSTEM DA 230-3 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Miele VENTILATION SYSTEM DA 230-3.

A complete Miele manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Miele VENTILATION SYSTEM DA 230-3 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Miele VENTILATION SYSTEM DA 230-3, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Miele VENTILATION SYSTEM DA 230-3, that we can find in the current document
3. Tips how to use the basic functions of the device Miele VENTILATION SYSTEM DA 230-3 - which should help us in our first steps of using Miele VENTILATION SYSTEM DA 230-3
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Miele VENTILATION SYSTEM DA 230-3
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Miele VENTILATION SYSTEM DA 230-3 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Miele VENTILATION SYSTEM DA 230-3?

Use the form below

If you did not solve your problem by using a manual Miele VENTILATION SYSTEM DA 230-3, ask a question using the form below. If a user had a similar problem with Miele VENTILATION SYSTEM DA 230-3 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)