    Quick Start Guide 00825-0200 -4840, Rev BA December 2014 R osemount Ultrasonic 3107 Lev el and 3108 F low T ransmitt ers ...

  • Emerson 3108 - page 2

    December 2014 2 Quick Start Guide © NOTICE This installation guide provides ba sic guidelines for the R ose mount 3107 and Ros emount 3108. It does not provide instruc tions for detailed configuration, diagnostics, mainte nance , service, trouble shooting, or installations. Re fer t o the Rose mount 3107 and 3108 Re fe rence Manu al (Document Numb ...

  • Emerson 3108 - page 3

    Quick Start Guide 3 December 2014 Ove r view of the R osemount 3107 and 3108 The Rosemount 3107 and 3108 are sealed 4–20 mA loop-powered liquid level transmitter s, specifically desi gned for use in waste w ater and effluent treatment plant on aqueous applic ations. These rugged UPV C transmitters are c ertified Intrinsically Safe for use in Zone ...

  • Emerson 3108 - page 4

    December 2014 4 Quick Start Guide Compone nts o f the transmitter The transmitter has a housing containing advanced electron ics to generate ultraso nic pulses, process the resultant signals, and provide a 4–20mA and HART output. There is a fact ory-fitted cable for th e sign al output and c onnecting an external power supply. The 3108 has a fact ...

  • Emerson 3108 - page 5

    Quick Start Guide 5 December 2014  The transmitter is Double Insulated , and there fore Protective Ear thing is not required. Howeve r , the cable screen should be connec ted (see Figure 9 on page 10 ).  Note th at if the eq uipmen t is used in a manne r not s pecifie d by the manu facturer , the protection afforded by the equipment may be im ...

  • Emerson 3108 - page 6

    December 2014 6 Quick Start Guide  Obstructions in the tank, or well , may ge nera te echoes which can be con fused with the real liqui d sur face ech o. Obstructions within the beam angle gene rate strong false echoes. Whereve r possible, the transmitter should be positione d to avoid false echo es.  T o avoid detecting unwanted objec ts in ...

  • Emerson 3108 - page 7

    Quick Start Guide 7 December 2014 Note  T o help with alignment, the ech o size (signal strength) can be indicated on the Ro semount 3490 Se ries Cont rol Unit or a Field Communicator . Flange mounti ng The instrument (acces sory) flanges supplie d by Emerson are ma nufactured from PVC and are a full face design. Care must be take n when install ...

  • Emerson 3108 - page 8

    December 2014 8 Quick Start Guide Open c hannel flo w installations Mount an u ltrasonic tr ansmitter o ver an area o f clear liqu id. Avoid mo unting the transmitter directly over any inlet stream. Never suspend the transmitter b y the cable . The positioning is critical, and should be the correct distance upst ream from the flow structure as stat ...

  • Emerson 3108 - page 9

    Quick Start Guide 9 December 2014 Note  The transmitte r should be free from a situat ion where it is lik ely to 'drown' (ref er to the rele vant standard f or fur ther informa tion) Figure 8. Bottom ref erence of a ‘V’ notch w eir A. T ransmitt er bo ttom r ef ere nc e (i.e . true inve r t) B. Meniscu s level The Rosemount 3108 tr ...

  • Emerson 3108 - page 10

    December 2014 10 Quick Start Guide Connec ting the transmitter Note  T o comp ly wi th th e C SA req ui rem ents , t h e transmitters must be powered from a R osemoun t 3490 Series C ontrol Unit, or a cla ss 2 or separa te extra-low voltage (SEL V) source.  Other devices may res et if connecting the transmitter t o a multi-drop system while t ...

  • Emerson 3108 - page 11

    Quick Start Guide 11 December 2014 Configuration The transmitter can be configured and ve rified using a Field Communicator or a Rosemount 3490 Series Control Uni t. The parameter s in this section are for a sufficient for a basi c level, conten ts (volume), or open channel flo w application. For a more advanced application, refer to th e Rosemount ...

  • Emerson 3108 - page 12

    December 2014 12 Quick Start Guide T ransmitter bottom re fe renc e This is the transm itter’s Bottom R eference sett ing. It is the distance measured vertically along th e ultrasonic beam path from the User Preferred Sensor Reference Point (UPSRP) to t he Zero Level of a tank or a n open channel ( Figure 10 on page 13 ). The zero level establish ...

  • Emerson 3108 - page 13

    Quick Start Guide 13 December 2014 Figure 10. T ank geometr y The process value (e.g. liquid level) i s in dicated in the HART Pr imary Variable (D900), which drives the 4–20 mA output signal. Parameter Fa s t Ke y 3490 Series Menu Navigation Lowe r Blanking (P063) 2, 2, 5, 6 SETUP ,[T ag], ENGINEERING, Low er Blankin g Upper Bl anking (P023) 2, ...

  • Emerson 3108 - page 14

    December 2014 14 Quick Start Guide T ransmitte r primar y variable units (P012) This select s alternati ve display u nits for the HAR T Primary Vari able (PV), which are then reported to a HART Mast er Device such as a Rosemo unt 3490 Series Control Unit. Note  Selecting alte rnativ e displ ay units does not autom atically re-scal e the PV value ...

  • Emerson 3108 - page 15

    Quick Start Guide 15 December 2014 Field Communicator or AMS To change the tank shape / non linear profile: 1. From the Home scre en, selec t 2: Configure . 2. Select 2: Manual Setup . 3. Select 3: Profiling . 4. Select 2: Set Non-Linear Profile . 5. Select a new profile , and then press “ Enter ” to save th e sele ct ion. 6. Press “ SEN D ? ...

  • Emerson 3108 - page 16

    December 2014 16 Quick Start Guide T ransmitte r scale factor / K-factor (P013) Level measurement When the proces s value (PV) is a level meas urement in meters, feet, or inche s, this parameter con verts the level measurem ent into alternati ve units before being out put. Enter a value of 1.0 if alternative units are not required. V olume measu re ...

  • Emerson 3108 - page 17

    Quick Start Guide 17 December 2014 Field Communicator or AMS To view or change the scale factor / k- factor: 1. From the Home scre en, selec t 2: Configure . 2. Select 2: Manual Setup . 3. Select 3: Profiling . 4. Select 4: Scale F ac tor P013 or 4: k-factor P013 , depe nding on the Non-Linear Profile selected. 5. Input the factor , and press “ E ...

  • Emerson 3108 - page 18

    December 2014 18 Quick Start Guide Field Communicator or AMS To view or chan ge the diameter, maxim um height, or power factor: 1. From the Home sc reen, select 2: Configure . 2. Selec t 2: Manual Setup . 3. Selec t 3: Profiling . 4. Selec t 5: Non-Linear Profile Height P014 or 5:Po wer F actor P014 , depe nding on the Non-Linear Pro file se lected ...

  • Emerson 3108 - page 19

    Quick Start Guide 19 December 2014 Profile points 1 to 10 (P030 to P039) These parameters are used to define an irregular-shaped profile for calculating the process value (PV) from a live level reading. See Figure n on page 18 fo r a n e xam ple of how these paramet ers are used. Field Communicator or AMS To view or change the profile poi nt: 1. Fr ...

  • Emerson 3108 - page 20

    December 2014 20 Quick Start Guide Figure 12. V olume or flow from 2-stag e weir Rectangular weir V-notc h weir 4–20mA/HART Rose mo unt 3107 or 3108 Profile heig ht (P014) Bottom reference (P010) Ros emount 3490 Series control unit Y X 0, 0 P039 = Maximum process v alue (PV) Maximum height (P014) (Entered percentages relating output PV to maxim u ...

  • Emerson 3108 - page 21

    Quick Start Guide 21 December 2014 Product Cer tifications Approved manufactur ing locations Rosemount Inc. – Chanhassen, Minnes ota, USA Rosemount Measurement Limited – Slough, Berkshire, United Kingdom Emerson Process Management As ia Pacific Private Limit ed – Singapore Europe an Union directi ve inf or ma tion The EC Declaration of Confor ...

  • Emerson 3108 - page 22

    December 2014 22 Quick Start Guide Canadian Standards A ssociation (CSA) I6 Certificate Number: 02 CSA 1352094 X Ex ia IIC Intrinsicall y Safe wh en installed with cert ified barrier meeting transmit ter Entit y parame te rs: Ui=30V, Ii=120mA, Pi=0.82W, Ci=5nF, Li=27uH Temperature Co de T4 at Ta = –40 to 60 ° C or T6 at T a = –40 to 55 ° C. S ...

  • Emerson 3108 - page 23

    Quick Start Guide 23 December 2014 6. It is the responsibi lity of the user to ensur e the voltage and cu rren t limits f or this equipment are not ex ceeded. 7. T echnical Data : a. Mate rials of construc tion: UPV C moulded body and front face . P V C sheathed 2 c ore shielded cable . Glass fi lled nylon lock nut. 316S S hanging brack et. Epoxy a ...

  • Emerson 3108 - page 24

    December 2014 24 Quick Start Guide Figu re 13 . EC decla ration of con formit y cer tifi cate ...

  • Emerson 3108 - page 25

    Quick Start Guide 25 December 2014 ...

  • Emerson 3108 - page 26

    December 2014 26 Quick Start Guide ...

  • Emerson 3108 - page 27

    Quick Start Guide 27 December 2014 ...

  • Emerson 3108 - page 28

    Emerson Process Management Rose mo unt In c. 8200 Mark et Boulev ard Chanha ssen , MN USA 553 17 T (US) (8 00) 999-9307 T (Intnl) (952 ) 906-8888 F (952) 906-8889 Emerson Process Management Lati n Am er ica 1300 Conc ord T errace , Suite 4 00 Sunrise Florid a 33323 US A T + 1 954 846 5030 Emerson Process Management Asia Pacific P rivate Lim ited 1 ...

Manufacturer Emerson Category Satellite Radio

Documents that we receive from a manufacturer of a Emerson 3108 can be divided into several groups. They are, among others:
- Emerson technical drawings
- 3108 manuals
- Emerson product data sheets
- information booklets
- or energy labels Emerson 3108
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson 3108.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson 3108, service manual, brief instructions and user manuals Emerson 3108. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson 3108.

Similar manuals

A complete manual for the device Emerson 3108, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson 3108 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson 3108.

A complete Emerson manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson 3108 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson 3108, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson 3108, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson 3108 - which should help us in our first steps of using Emerson 3108
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson 3108