  • Lifebreath 1200ERV - page 1

    * LEA VE FOR HOMEOWNER NOTE: Due to ongoing research and product development, specifications, ratings and dimensions are subject to change without notice. OPERA TION AND INST ALLA TION MANUAL ® CLEAN • FRESH • AIR NOTE: AL THOUGH SOME MODELS DIFFER IN OPERA TION, THE BASIC STEPS ARE SIMILAR. CAUTION Before installation, careful consideration m ...

  • Lifebreath 1200ERV - page 2

    2 T able of Content s Introduction .................................................................... 2 ERV Questions and Answers ......................................... 3 Select Correct HRV/ER V to Match Climate.....................4 Select the Correct Size HRV/ER V ................................ 5 T echnical Data - Model 500DCS ............ ...

  • Lifebreath 1200ERV - page 3

    3 ER V Questions & Ans wers What is the difference between an HRV and an ERV? The core in an HRV (Heat Recovery Ventilator) transfers heat from one air stream to the other. This is called sensible heat. The term ERV (Energy Recovery Ventilator) is usually used to describe a unit with an enthalpic core that transfers moisture as well as heat fro ...

  • Lifebreath 1200ERV - page 4

    4 ...

  • Lifebreath 1200ERV - page 5

    5 MAKE UP HEA T REQUIREMENT at 1200 CFM (566L/s) Nominal Nominal Nominal Outdoor Temp. kW Req. for kW Req. for kW Req. for C° F° 20°C (68°F) 25°C (77°F) 30°C (86°F) Air Delivery Air Delivery Air Delivery 0 32 7 10 14 -10 14 10 14 17 -20 -4 12 15 19 -30 -22 15 19 22 -40 -40 17 21 24 Selecting the Correct Size HR V/ER V Commercial and Institu ...

  • Lifebreath 1200ERV - page 6

    6 OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min. (3 wire) 99-105 Programmable Ventilation Control includes Programmable Time Clock, Dehumidistat and Air Sentry™ 99-109 Air Sentry ™ Air Quality Monitor designed to accept remotely mounted Control Pad 99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Contr ...

  • Lifebreath 1200ERV - page 7

    7 Model 850 FD/DD SPECIFICA TIONS CORES Modular (6 section) patented aluminum heat recovery cores arranged for high efficiency crossflow ventilation. MOTORS Two PSC, 3 speed double shafted, 120 VAC, 3.95 Amps each (7.9 total on high speed). HP - 1/4, 1625 RPM. Watts - total on High Speed - 848. FILTERS Washable air filters in exhaust and supply air ...

  • Lifebreath 1200ERV - page 8

    8 Model 700 FD/DD SPECIFICA TIONS CORES Modular (2 section) patented aluminum heat recovery cores arranged for efficient cross-flow ventilation. MOTORS Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each (5.5 total on high speed). HP - 1/10, 1625 RPM. Watts - total on high speed - 648. FILTERS Washable air filters in exhaust and supply air str ...

  • Lifebreath 1200ERV - page 9

    9 SPECIFICA TIONS CORES Modular (3 section) patented aluminum heat recovery cores arranged for efficient cross-flow ventilation. MOTORS Two PSC, 3 speed double shafted, 120 VAC, 4 Amps each (8.1 total on high speed). HP - 1/4, 1625 RPM. Watts - total on high speed - 972. FILTERS Washable air filters in exhaust and supply air streams. BLOWERS Centri ...

  • Lifebreath 1200ERV - page 10

    10 Model 500ER V ® CLEAN • FRESH • AIR SPECIFICA TIONS LATENT RECOVERY (MOISTURE) TRANSFER CORES Modular (4 section) 2- Enthalpic, 2 Aluminum arranged for high efficiency crossflow ventilation. MOTORS - Two PSC, 5 speed double shafted, 120 VAC, 3.15 Amps each (6.3 total on high speed). HP - 1/10, 1625 RPM. Watts - total on High Speed - 610. FI ...

  • Lifebreath 1200ERV - page 11

    11 TI-131 0105 Model 700ER V ® CLEAN • FRESH • AIR SPECIFICA TIONS LATENT RECOVERY (MOISTURE) TRANSFER CORES Modular (2 section) enthalpic (moisture) transfer cores arranged for efficient cross-flow ventilation. MOTORS Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each (5.5 total on high speed). HP - 1/10, 1625 RPM. Watts - total on high ...

  • Lifebreath 1200ERV - page 12

    12 TI-132 0105 Model 1200ER V ® CLEAN • FRESH • AIR SPECIFICA TIONS LATENT RECOVERY (MOISTURE) TRANSFER CORES Modular (3 section) latent recovery (moisture) transfer cores arranged for efficient cross-flow ventilation. MOTORS Two PSC, 3 speed double shafted, 120 VAC, 4 Amps each (8.1 total on high speed). HP - 1/4, 1625 RPM. Watts - total on h ...

  • Lifebreath 1200ERV - page 13

    13 Location f or Mounting The HRV/ER V must be located in a conditioned space where the surrounding air temperature does not fall below 60˚F (16˚C). The unit must be mounted level (horizontal). The warranty will be void if these conditions are not met. T ypically the HRV/ER V is positioned close to an outside wall or the roof to simplify the conn ...

  • Lifebreath 1200ERV - page 14

    Outside W eatherhoods The weatherhoods must have built-in “bird” screen with 1/4 in (63.5 mm) minimum mesh to prevent birds and rodents from entering into the ductwork. Do not use smaller mesh as it will be very susceptible to plugging up. Gravity dampers at the vents must not be used as they will restrict air flow and often “seize up”. The ...

  • Lifebreath 1200ERV - page 15

    15 F resh Air Supply S yst em The fresh air supply ductwork from the HRV/ER V may be directly connected to the return air duct of the forced air system. Check the air flow balance of the HRV/ER V with the air handler blower both “ON” and “OFF” to determine that it does not imbalance the HRV/ER V more than 10%. Also, it is advisable to inclu ...

  • Lifebreath 1200ERV - page 16

    16 ECONOMIZER HRV/ERV FRESH AIR SUPPLY HRV/ERV UNIT STALE AIR EXHAUST TO HRV/ERV SUPPLY DUCT RETURN AIR DUCT or BREATHER T FRESH AIR SUPPLY STALE AIR EXHAUST ROOFTOP UNIT B.D. B.D. Example only - Duct connections not typical ROOFTOP UNIT HRV/ERV FRESH AIR SUPPLY SUPPLY DUCTWORK CEILING RETURN AIR PLENUM ROOF DECK STALE AIR EXHAUST HRV/ERV UNIT ECON ...

  • Lifebreath 1200ERV - page 17

    17 V arious Installation Types Figure 7A Saddle Installation Hang unit with suspended rods and "U" channel members. Threaded  rod and U channel (Supplied by others) Vibration Isolators (Supplied by others) Figure 7B Curb Mounted Mount unit on wooden or metal curb assembly. Unit must be raised an adequate height for ...

  • Lifebreath 1200ERV - page 18

    18 Electrical Connections It is recommended that a licensed electrician make all electrical connections. It is very important that the unit be properly grounded. It is recommended that a separate 15 amp/120 volt circuit be used. W ARNING: In order to prevent electric shock when cleaning or servicing the HRV/ER V , it is extremely important to confi ...

  • Lifebreath 1200ERV - page 19

    19 These models are equipped with a 3 speed control, low medium and high, as well as a lighted on/off switch and a 4 screw terminal strip. The terminal strip can be used to connect any low voltage device which will then jump the unit to high speed from whatever setting the speed control was on. The terminal strip can also be wired to allow the unit ...

  • Lifebreath 1200ERV - page 20

    20 ControlAir 15 OPTION AL REM OTE CONTROLS Model 500 Only 0011 NEW! AIR SENTR Y™ AIR QUALITY SENSOR LOCATION: Kitchen, basement, work place (connect 1/unit only). • Digital Air Quality Monitor. • Status light indicates fan speed. • Increases ventilation to remove odours and contaminants. • Among gases detected are cigarette smoke and for ...

  • Lifebreath 1200ERV - page 21

    Oper ating the ControlAir 15 Plugging in the HRV/ERV energizes the unit. A self test function will be performed every time the HRV/ERV is energized (refer to “Self Test” for more details). After the self test has completed successfully the HRV/ERV will default to Speed 1. This is the factory default setting. Follow the instructions found on the ...

  • Lifebreath 1200ERV - page 22

    22 T o select mode of oper ation for ControlAir 15 Model 500 Only Press and hold the fan selection button on the Control Pad. After 5 seconds the control will begin to cycle each mode holding each for 2 seconds. Release the button when the desired mode of operation is reached. Modes of Operation LED Indication OFF No LED’ s illuminated HRV/ER V i ...

  • Lifebreath 1200ERV - page 23

    It is necessary to have balanced air flows in an HRV/ERV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flows are not properly balanced, then; • The HRV/ERV may not operate at its maximum efficiency • A negative or positive air pressure may occur in the house • The unit may not de ...

  • Lifebreath 1200ERV - page 24

    Servicing your HRV/ER V on a regular schedule will result in optimum operating efficiencies and prolonged life of the equipment. Due to numerous applications in which this equipment can be installed, it is difficult to predict servicing intervals. In certain situations where there is heavy smoke, servicing the equipment every one - two months may b ...

  • Lifebreath 1200ERV - page 25

    25 FIL TERS Open front service door to access the filters located in both supply and exhaust air streams. Note to remove and install filters, it may be easier to first remove the core(s). See CORE . The filters are designed to stop large particles from entering in the core. The filters are fastened in place by a metal spring rod. T o remove filters ...

  • Lifebreath 1200ERV - page 26

    S Y MPTOM CA USE SOLUTION Poor Air Flows Supply air feels cold Dehumidistat is not Operating Humidity Levels are too High Condensation is appearing on the windows Humidity Levels are too Low HRV/ERV and / or Ducts Frosting up Condensation or Ice Build Up in Insulated Duct to the Outside Water in the bottom of the HRV/ERV • 1/4” (6 mm) mesh on t ...

  • Lifebreath 1200ERV - page 27

    27 DEFROST DETAILS T9 T10 T11 T12 T13 T14 T5 T4 T3 GROUND DOOR SWITCH WHITE WHITE BLACK BLACK HIGH VOLTAGE 12V LOW VOLTAGE FIELD INSTALLED LEGEND 12V LOW VOLTAGE GRN Note: Note: All control connections are labeled by colour. Connect to corresponding colour with low voltage wire ( 20 gauge minimum). A dry contact closure between red & black will ...

  • Lifebreath 1200ERV - page 28

    28 FAN DEFROST Remote Switching Analogue Style Controls Wiring Diagram TEMPERATURE SENSOR BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK WHITE WHITE WHITE WHITE WHITE WHITE BLACK ORANGE ORANGE WHITE WHITE ORANGE WHITE WHITE DEFROST TIMER DEFROST LIGHT INDICATOR TRANS- FORMER WHITE WHITE WHITE WHITE WHITE WHIT ...

  • Lifebreath 1200ERV - page 29

    29 TERMINAL BLOCK BLUE 1 FAN MOTOR CAPACITORS PURPLE Carling Switch 700 STYLE UNITS ONLY FAN MOTOR CAPACITORS BROWN ORANGE WHITE WHITE BLACK BLACK WHITE BLACK BLACK BLACK WHITE BLACK YELLOW WHITE WHITE BLACK BLUE RED RED BLUE TERMINAL BLOCK WHITE BLACK BLACK RED RED BLUE BLUE BLUE RED BLACK BLACK PURPLE YELLOW YELLOW GREEN GND. GND. ...

  • Lifebreath 1200ERV - page 30

    30 CO MMERCIAL LIFEBREA TH ® HEA T/ENERG Y RECOVER Y VENTILA TORS • 2 Y ear Limited W arranty • 15 Y ear Aluminum Core W arranty • 5 Y ear Paper Core W arranty NUTECH ENERGY SYSTEMS INC. ® (NUTECH) warrants to the purchaser of the Commercial LIFEBREATH ® model and accessories referred to below, to be free from manufacturing defects. This W ...

  • Lifebreath 1200ERV - page 31

    511 McCormick Blvd. London, Ontario N5W 4C8 Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com ...

Manufacturer Lifebreath Category Air Cleaner

Documents that we receive from a manufacturer of a Lifebreath 1200ERV can be divided into several groups. They are, among others:
- Lifebreath technical drawings
- 1200ERV manuals
- Lifebreath product data sheets
- information booklets
- or energy labels Lifebreath 1200ERV
All of them are important, but the most important information from the point of view of use of the device are in the user manual Lifebreath 1200ERV.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Lifebreath 1200ERV, service manual, brief instructions and user manuals Lifebreath 1200ERV. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Lifebreath 1200ERV.

A complete manual for the device Lifebreath 1200ERV, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Lifebreath 1200ERV by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Lifebreath 1200ERV.

A complete Lifebreath manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Lifebreath 1200ERV - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Lifebreath 1200ERV, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Lifebreath 1200ERV, that we can find in the current document
3. Tips how to use the basic functions of the device Lifebreath 1200ERV - which should help us in our first steps of using Lifebreath 1200ERV
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Lifebreath 1200ERV
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Lifebreath 1200ERV in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Lifebreath 1200ERV?

Use the form below

If you did not solve your problem by using a manual Lifebreath 1200ERV, ask a question using the form below. If a user had a similar problem with Lifebreath 1200ERV it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)