Summary
  • Slant/Fin Oil-fired Boiler - page 1

    CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P A GE Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Installation Requirements: Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 C ...

  • Slant/Fin Oil-fired Boiler - page 2

    2 INTREPID Standard working pressure 30 psi water , 15 psi steam. All boilers hydrostatically tested — A.S .M.E. * For f orced hot water heating systems where the boiler and all piping are located within the area to be heated, the boiler may be selected on the basis of gross D .O.E. capacity output. The net I=B=R output ratings shown are based on ...

  • Slant/Fin Oil-fired Boiler - page 3

    I NTREPID 3 BOILER LOCA TION Provide a le v el, solid f oundation f or the boiler . Location should be near the chimney so that the Flue Pipe Connector or Breeching to the chim- ney is short and direct. A. The foundation m ust be capable of supporting the weight of the boiler when filled with water: B. The Intrepid Boiler has full wet base sections ...

  • Slant/Fin Oil-fired Boiler - page 4

    4 INTREPID Any oil-fired boiler must ha v e a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney dr aft* is unreliable , CO 2 and ov erfire draft* will change unpredictab ly . DO NO T v ent this boiler to the same chimney flue used b y a fireplace or coal or wood burning furnace or boiler. The d ...

  • Slant/Fin Oil-fired Boiler - page 5

    I NTREPID 5 Figure 3a. Appliances located in confined spaces. Air from inside the building. See T able 2 (2.3). Figure 3b. Appliances located in confined spaces. Air from out- doors. See T able 2 (2.4). Figure 3c. Appliances located in confined spaces. Air from out- doors through ventilated attic. See T able 2 (2.4). Figure 3d. Appliances located i ...

  • Slant/Fin Oil-fired Boiler - page 6

    6 INTREPID INST ALLING CONTROLS AND A CCESSORIES ON BOILER UNITS Note : Jac ket m ust be installed on boiler units prior to installation of trim. I. STEAM BOILER TRIM, see page 2 f or tapping locations, and figure 4 for illustr ation of steam boiler . A. Steam pressure gauge and pressure cut-out, install in tapping n o . 4, figure 4. B. Gauge glass ...

  • Slant/Fin Oil-fired Boiler - page 7

    I NTREPID 7 C . HO T W A TER RADIA TION VENTING - Manual air v ents should be installed at the top of all "drops"(where piping goes downward). Air must be vented or purged from all z one lines to permit proper system heating. D . PUMP LOCA TION-Locating low-head pump(s) on retur n to boil- er is only acceptable in residences of one or two ...

  • Slant/Fin Oil-fired Boiler - page 8

    8 INTREPID VENT PIPING AND DRAFT REGULA T OR A. V ent pipes must be installed having the same diameter as the boiler outlet. (See page 2) B. V ent pipes and breeching must be pitched upward a minimum of 1/4" per foot. C . Connect vent pipe to the chimney using as f ew elbows as possible . D . Horizontal vent connector into the chimne y should ...

  • Slant/Fin Oil-fired Boiler - page 9

    I NTREPID 9 CLEANING AND FILLING A NEW STEAM BOILER I. BEFORE USING STEAM BOILER A. Check burner to be cer tain it is ready for firing. DO NO T FIRE into an empty boiler . B. Be prepared to heat raw water to at least 180°F . as soon as it is introduced into the boiler . This procedure will remove dissolv ed, corrosive gases . C . Provide drain lin ...

  • Slant/Fin Oil-fired Boiler - page 10

    1 0 INTREPID CA UTION: When flushing float type low water cut-off control, hot water and steam will flow out the b low do wn valv e . Blow down v alve is illus- trated below . A. SPECIAL FLUSHING INSTRUCTIONS For ne w boiler installed in old system. Installation of new boiler ma y break loose a hea vy accumulation of sediment and scale from old pip ...

  • Slant/Fin Oil-fired Boiler - page 11

    I NTREPID 11 ...

  • Slant/Fin Oil-fired Boiler - page 12

    1 2 INTREPID B ASIC MODULE WIRING (less circulator) WIRING FOR P ACKA GED STEAM BOILER EQ UIPPED WITH McDONNELL NO .67 L.W .C.O . ...

  • Slant/Fin Oil-fired Boiler - page 13

    I NTREPID 13 WIRING FOR P ACKA GED STEAM BOILER F or alternate option PS-801-120 L.W .C.O . or Hydrole vel Cyc le Gar d 450 L.W .C.O . BOILER WIRING DIA GRAM FOR RIELLO ...

  • Slant/Fin Oil-fired Boiler - page 14

    1 4 INTREPID S TEAM BOILER WIRING FOR RIELLO BURNER AND McDONELL M ILLER P .S. 801 L.W .C.O . FOR CONNECTION T O LINE V OL T A GE W ALL THERMOST A T (BY O THERS) W A TER BOILER WIRING FOR RIELLO BURNER AND HIGH LIMIT , LINE V OL T A GE W ALL THERMOST A T (BY OTHERS) ...

  • Slant/Fin Oil-fired Boiler - page 15

    I NTREPID 15 ...

  • Slant/Fin Oil-fired Boiler - page 16

    1 6 INTREPID BURNER D A T A – BECKETT CF-375 BURNERS FOR P A CKA GED BOILERS ONL Y ( For knoc k ed-down & boiler b urner units see publication no . TR-42KB) TR-60 CF-375 2.60 2.25 45˚ P HA GO 135 10 3 1 TR-60 CF-375 2.85 2.25 45˚ P HA GO 160 10 2 2 TR-70 CF-375 3.00 2.5 45˚ SS HA GO 145 10 4 3 TR-70 CF-375 3.10 2.5 45˚ SS HA GO 155 10 4 4 ...

  • Slant/Fin Oil-fired Boiler - page 17

    I NTREPID 17 ...

  • Slant/Fin Oil-fired Boiler - page 18

    1 8 INTREPID NO TE: ELECTRODES ARE PRESET A T THE F ACT ORY . REGULA TION OF THE TURBULA TOR AND AIR SHUTTER FOR PROPER COMBUSTION T urbulator Setting 1. Loosen nut, 1, then turn the screw , 2, until the index marker , 3, is aligned with the correct index n umber . 2. Retighten the retaining nut, 1. TURBULA T OR SETTINGS - RIELLO 40 SERIES The numb ...

  • Slant/Fin Oil-fired Boiler - page 19

    I NTREPID 19 ...

  • Slant/Fin Oil-fired Boiler - page 20

    2 0 INTREPID ...

  • Slant/Fin Oil-fired Boiler - page 21

    I NTREPID 21 I. EXTENDED SHUTDOWN, CLEANING OR REMO V AL OF BOILER FROM SER VICE. D ANGER: Use CA UTION when handling chemicals and draining hot w ater from a boiler . Scalding water and/or chemicals can cause per - manent injur y to the skin, e y es and respir ator y system. A. Shut down burner by disconnecting all electrical power to the burner b ...

  • Slant/Fin Oil-fired Boiler - page 22

    - ...

  • Slant/Fin Oil-fired Boiler - page 23

    - ...

  • Slant/Fin Oil-fired Boiler - page 24

    SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE, Mississauga, Ontario www .slantfin.com ...

Manufacturer Slant/Fin Category Boiler

Documents that we receive from a manufacturer of a Slant/Fin Oil-fired Boiler can be divided into several groups. They are, among others:
- Slant/Fin technical drawings
- Oil-fired Boiler manuals
- Slant/Fin product data sheets
- information booklets
- or energy labels Slant/Fin Oil-fired Boiler
All of them are important, but the most important information from the point of view of use of the device are in the user manual Slant/Fin Oil-fired Boiler.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Slant/Fin Oil-fired Boiler, service manual, brief instructions and user manuals Slant/Fin Oil-fired Boiler. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Slant/Fin Oil-fired Boiler.

Similar manuals

A complete manual for the device Slant/Fin Oil-fired Boiler, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Slant/Fin Oil-fired Boiler by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Slant/Fin Oil-fired Boiler.

A complete Slant/Fin manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Slant/Fin Oil-fired Boiler - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Slant/Fin Oil-fired Boiler, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Slant/Fin Oil-fired Boiler, that we can find in the current document
3. Tips how to use the basic functions of the device Slant/Fin Oil-fired Boiler - which should help us in our first steps of using Slant/Fin Oil-fired Boiler
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Slant/Fin Oil-fired Boiler
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Slant/Fin Oil-fired Boiler in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Slant/Fin Oil-fired Boiler?

Use the form below

If you did not solve your problem by using a manual Slant/Fin Oil-fired Boiler, ask a question using the form below. If a user had a similar problem with Slant/Fin Oil-fired Boiler it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)